Download Print this page

GE VersaPoint IC220ALG221 System Manual page 10

Analog in 15 bit voltage/current 8ch

Advertisement

ANALOG IN 15 BIT VOLTAGE/CURRENT 8CH IC220ALG221
Bit 3 to bit 0:
Code
Measuring Range (Voltage)
bin
dec
0000
0
0 V to 10 V (default)
0001
1
±10 V
0010
2
0 V to 5 V
0011
3
±5 V
0100
4
0 V to 25 V
0101
5
±25 V
0110
6
0 V to 50 V
0111
7
Reserved
The differential voltage between different terminal inputs must not exceed 50 V.
If, for example, the 0 V to 50 V range is used on one channel, the use of bipolar ranges is
not permitted on any other channel.
10
Code
Measuring Range (Current)
bin
dec
1000
8
0 mA to 20 mA
1001
9
±20 mA
1010
10
4 mA to 20 mA
1011
11
Reserved
1100
12
0 mA to 40 mA
1101
13
±40 mA
1110
14
Reserved
1111
15
Reserved
6226B_GE