Technician Settings
Enter Technician Settings mode:
1. Adjust the setpoint temperature to 10ºC or 50ºF.
2. Press and hold the [C/F] button for 10 seconds to enter Technician Settings mode. "P01" will appear on display.
View objects and make adjustments:
Use the [Mode] button to step forward between different settings.
Use the [Fan] button to step backward between different settings.
Press the [On/Off] button to exit Technician Settings and return to normal display.
If no button is pressed for 60 seconds, the thermostat will automatically exit Technician Settings and return to normal display.
Use the [+] and [-] buttons to make adjustments when required.
P01 – Offset for temperature readings calibration
Range:
-6...+6°C / -9...+9°F.
Default: 0°C / 0°F.
Note: The offset will influence both internal
or external sensors.
P02 – Setpoint limit for cooling
Range:
5...35°C / 41...95°F.
Default: 10°C / 50°F.
Note: The thermostat will stop cooling regardless of
the user's setpoint
P03 – Setpoint limit for heating
Range:
5...35°C / 41...95°F.
Default: 30°C / 86°F.
Note: The thermostat will stop heating regardless of
the user's setpoint
P04 – Enable/Disable the option to lock the [Fan] button
"LF" + " "
[Fan] button can be locked
"LF" only
[Fan] button cannot be locked
Note: When enabled, press and hold both [-] and [Fan] buttons
for 7 seconds to actually lock the buttons.
- 40 -
Offset for temperature calibration
(°C)
(°F)
Setpoint limit for cooling
(°C)
(°F)
Setpoint limit for heating
(°C)
(°F)
[Fan]
[Fan]
Can
Cannot
be locked
be locked
Need help?
Do you have a question about the ComfortVu TB-24-HM and is the answer not in the manual?
Questions and answers