Operating principle
The diagram below demonstrates the operating principle of zone-selective interlocking:
- - -
A
E
The ZSI function acts on the S and G ranges of the tripping characteristic. Currents within
the I range (instantaneous short circuit) continue to cause instantaneous tripping.
3VA molded case circuit breakers with UL and IEC certification
Manual, 01/2019, L1V30435333-01
Communication cable
Output, transmits the blocking signal
Input, receives the blocking signal
t
"Virtual" tripping time of I protection
i
t
Delay time setting of S protection
SD
t
Delay time of all molded case circuit breakers
ZSI
which detect the short circuit but do not receive
a blocking signal when ZSI is activated
Description
2.5 Protection functions
77