Smoke and heat detector

Advertisement

Quick Links

TSD-1
SMOKE AND HEAT DETECTOR
The TSD-1 multisensor detector can detect the early stages of fire development when there is some visible
smoke and/or temperature rise. This manual applies to the detector with electronics version 1.5 or higher.
1. Features
Selection of detector operating mode:
smoke and heat detection;
smoke detection;
heat detection.
EN54-7 compliant visible smoke sensor.
EN54-5 compliant heat sensor.
Alarm memory option.
Selection of alarm output type:
NO;
NC;
2EOL/NO;
2EOL/NC.
Configuration of the detector parameters by means of DIP-switches.
Detection of optical chamber contamination.
Red LED for optical signaling.
2. Functional description
An optical method is used for the detection of visible smoke. When the concentration of smoke in the optical
chamber exceeds a given threshold, an alarm is triggered. The smoke sensor operating parameters are
modified depending on the temperature changes recorded by the heat sensor (thermistor).
The heat sensor operates according to the requirements of Class A1R (EN 54-5). The alarm will be triggered
after exceeding a certain threshold temperature (54°C - 65°C) or in the event when the temperature rises too
rapidly (see Table 1).
Air temperature rise velocity
1 °C/min
3 °C/min
5 °C/min
10 °C/min
20 °C/min
30 °C/min
If the event of an alarm, the detector output is activated and the LED lights up.
3. Installation
The detector is designed for indoor installation. In its typical applications at home or in office, the detector
should be installed on the ceiling, at a distance of at least 0.5 meters from the walls or other objects.
Do not install the detector in places with high concentration of dust and/or formation and
condensation of water steam.
The detector should not be mounted in the vicinity of heaters and cookers.
Disconnect power before making any electrical connections.
1. Remove the plastic dust cap.
2. Turn the cover counter-clockwise (Fig. 5) and remove it (Fig. 6).
®
Lower limit of response time
Table 1. Response time limits for the heat sensor.
29 min
7 min 13 s
4 min 9 s
1 min
30 s
20 s
tsd-1_en 03/12
Upper limit of response time
40 min 20 s
13 min 40 s
8 min 20 s
4 min 20 s
2 min 20 s
1 min 40 s

Advertisement

loading
Need help?

Need help?

Do you have a question about the TSD-1 and is the answer not in the manual?

Questions and answers

Summary of Contents for Satel TSD-1

  • Page 1 SMOKE AND HEAT DETECTOR tsd-1_en 03/12 The TSD-1 multisensor detector can detect the early stages of fire development when there is some visible smoke and/or temperature rise. This manual applies to the detector with electronics version 1.5 or higher. 1. Features ...
  • Page 2: Configuring The Detector

    TSD-1 SATEL 3. Using wall plugs (screw anchors) and screws, fasten the enclosure base to the ceiling. 4. Using DIP-switches, configure the detector appropriately (see: C ONFIGURING THE DETECTOR 5. Screw the wires to the corresponding terminals in the enclosure base (see: C ONNECTING WIRES 6.
  • Page 3: Specifications

    Minimum static response temperature ......................54 °C Maximum static response temperature ......................65 °C Environmental class according to EN50130-5 ......................II Operating temperature range ......................-10 °C...+55 °C Maximum humidity............................93±3% Enclosure dimensions.........................ø108 x 61 mm Weight................................164 g The declaration of conformity may be consulted at www.satel.eu/ce...
  • Page 4 TSD-1 SATEL SATEL sp. z o.o. ul. Schuberta 79 80-172 Gdańsk POLAND tel. + 48 58 320 94 00 info@satel.pl www.satel.pl...