Integrated Suppression Module S U R G E P R O T E C T I O N Installation, Operation and Maintenance Manual PN 750-0072-010 Electrical Transient Suppression Filter Systems...
CURRENT TECHNOLOGY INTEGRATED SUPPRESSION MODULE ® The ISM (Integrated Suppression Module) is an electrical transient suppression filter system that protects today’s facilities from costly downtime and equipment damage caused by routine or catastrophic electrical disturbances . The ISM contains individual thermally fused and protected MOVs, surge-rated copper busing, robust filtering and advanced remote communications capabilities .
CURRENT TECHNOLOGY INTEGRATED SUPPRESSION MODULE ® Thank you for choosing Current Technology’s ISM Surge Suppression System . Guide to Installation We look forward to fulfilling your facility wide surge suppression filter system and Assistance needs . Should you have questions about installing the ISM surge suppression system please call Monday through Friday 8:00 a.m.
Page 4
CURRENT TECHNOLOGY INTEGRATED SUPPRESSION MODULE ® The ISM offers a full range of monitoring options when connected to an Guide to Installation & optional monitoring package from the most sophisticated power quality Assistance monitoring features offered in any surge suppression product . These features...
CURRENT TECHNOLOGY INTEGRATED SUPPRESSION MODULE ® W A R N I N G ! THE ISM WARRANTY IS VOIDED if the unit is damaged as a result of improper installation or the installer’s failure to verify the following conditions prior to installation.
CURRENT TECHNOLOGY INTEGRATED SUPPRESSION MODULE ® Figures 1-4 show the electrical relationship between the ISM and these four Service Configurations basic service configurations: WYE, DELTA, High-Leg DELTA and SPLIT-PHASE . Figure 1 3-Phase, 4-Wire WYE LOAD Xo BOND ISM Unit...
Page 8
CURRENT TECHNOLOGY INTEGRATED SUPPRESSION MODULE ® Figure 3 3-Phase, 4-Wire High-Leg DELTA N B* LOAD Xo BOND ISM Unit EARTH GROUND *NOTE: HIGH LEG MUST BE B PHASE Figure 4 1-Phase, 3-Wire SPLIT-PHASE LOAD Xo BOND ISM Unit EARTH GROUND...
ISM to a circuit breaker, molded case switch or fused disconnect . If a breaker or molded case switch is used for connecting the phase conductors, Current Technology recommends a 100 amp rating. ®...
CURRENT TECHNOLOGY INTEGRATED SUPPRESSION MODULE ® W A R N I N G ! Prior to proceeding, ensure the SPD unit does not have voltage applied to its input terminals. ISM models equipped with an EMI filter system (“-F” suffix), and have a...
NEMA rating . For systems requiring end-use regulatory compliance, Current Technology recommends mounting the ISM inside a sturdy polymeric enclosure (0 .125" minimum thickness) or metal enclosure (min 15 gauge) with a minimum clearance of 1/2"...
ISM . Check with the owner or owner’s representative to see if this test is required at your site . If you have questions about Field Startup Testing or would like to arrange for this service, call Current Technology Technical Support at ®...
CURRENT TECHNOLOGY INTEGRATED SUPPRESSION MODULE ® ➤ If your ISM has M1X Standard Monitoring (See Figure 6): Verify Proper Operation Verify that only the green indicating lights are illuminated and that there are no red lights illuminated . Green lights indicate a normal condition for each phase .
CURRENT TECHNOLOGY INTEGRATED SUPPRESSION MODULE ® Table 4: LED and Display Alarm Status Conditions Alarm Condition Corresponding Phase LED M3 Status Message Priority * Cond Phase Loss (<80%) LED Off “Alarm: Phase x Loss” Phase Low (80 to <90%) LED Short Blink Green (≈25% duty) “Alarm: Phase x Low”...
CURRENT TECHNOLOGY INTEGRATED SUPPRESSION MODULE ® Your Current Technology ISM surge suppression system does not require ® Troubleshooting periodic maintenance . The unit contains no serviceable parts . (Avertissement: Aucune pièce remplaçable ou réparable .) The unit’s heavy-duty design should preclude the need for any repairs;...
. This test should be coordinated with scheduled maintenance events in your facility . It can be performed in-house with the aid of the DTS-2 Portable Test Set or requested as a service from a Current Technology authorized service ®...
LIABILITY EVER EXCEED THE PURCHASE PRICE PAID FOR SUCH DEFECTIVE PRODUCT . This warranty is not transferable and may only be enforced by the purchaser . Claims under this warranty must be submitted to Current Technology within ® thirty (30) days of discovery of any ISM product defect .