Siemens SICAM AK Manual page 39

Rtus. redundancy,
Table of Contents

Advertisement

Column name/
Parameter
DR#
DB
CPU-pair
Priority BSE failure
Delay after BSE failure
Priority BSE task
suspend
Priority PE failure
Priority assignment
Option: switchable
Option: preferred
position
Option: type of use
Option: general
interrogation
SICAM RTUs, SICAM AK Redundancy
DC2-026-2.07, Edition 10.2016
Settings for BSEs (CPU Redundancy)
Description/Value
Predefined CPU-pairs
Definition of the priority level for the failure
of the BSE concerned (hardware or firmware
damage)
Definition of the time period, after the expiry
of which the priority is canceled for a BSE
failure following a going BSE failure (in
seconds)
Definition of the priority level, when a
CAEx plus task is stopped
Definition of the priority level, when the PE
fails (hardware or firmware damage or PE
not coupled)
See following section
See following section
See following section
singular
redundant
Defines, whether a GI is to be sent after the
switchover of the relevant BSE to active (GI
after active) or not (no GI after active)
Unrestricted
Redundancy via SCA-RS
Comment
Not editable
Not editable
Not editable
To edit: double click in the
field and enter the required
value (0-254)
Specific setting for AU-
redundancy (line-by-line
redundancy switchover
with SCA-RS)
Specific setting for AU-
redundancy (line-by-line
redundancy switchover
with SCA-RS, global
redundancy switchover
with SCA-RS, global
redundancy switchover
with application-related
voting)
Specific setting for AU-
redundancy (line-by-line
redundancy switchover
with application-related
voting
Specific settings for CPU
Redundancy
The CPUs of the predefined
CPU pairs 1/2, 4/5 etc.
(connected via fixed
installed HSL at the back of
the module rack) can each
be a singular CPU, which
can then not be switched
over.
The predefined CPU pairs
are used as such.
39