Page 1
The power behind competitiveness Delta UPS - Amplon Family RT Series, Single Phase 1/ 1.5/ 2/ 3 kVA External Battery Pack User Manual www.deltapowersolutions.com...
When the UPS is operating during a power outage, the battery pack provides DC power, which maintains inverter operation to supply power to the critical loads connected to the UPS. (Figure 1: Delta External Battery Pack Front View) Amplon RT Series...
Chapter 2 : Important Safety Instructions Chapter 2 : Important Safety Instructions Servicing of batteries and battery packs must be performed or supervised by qualified service personnel knowledgeable in batteries, battery packs and the required precautions. Keep unauthorized personnel away from batteries and battery packs.
Page 6
2. Use tools with insulated handles. 3. Wear rubber gloves and boots. 4. Do not lay tools or metal parts on the top of batteries. 5. Disconnect the charging source prior to connecting or disconnecting the batteries’ terminals. Amplon RT Series...
Chapter 3 : Package List Chapter 3 : Package List ITEM Q’ty Drawing External 1 PC Battery Pack User Manual 1 PC Tower Stand 4 PCS Extender Rail Kit 1 SET External 1 PC Battery Cable Fastener 1 SET...
See Figure 2. (Figure 2: Mount the Bracket Ears) Follow steps ① to ④ to install the Delta external battery pack in Delta’s rail kit (provided). See Figure 3. Step ① : Adjust the length of the rails according to your rack.
Page 10
(Figure 3: Insert the Delta External Battery Pack to Your Rack) NOTE: If you want to use a non-Delta rail kit, please only follow step ④. Tower Mounting Connect your UPS’s tower stands with the provided tower stand extender(s) according to the width of your UPS and the Delta external battery pack.
Page 11
(Figure 5: Rotate the Delta External Battery Pack’s Control Panel & Delta Logo Nameplate) Carefully lift the Delta external battery pack upright with the Delta logo facing up. A minimum of two people are required. See Figure 6. (Figure 6: Place the Delta External Battery Pack Upright)
Page 12
(Figure 7: Place the Delta External Battery Pack and the UPS into the Tower Stands) Use the provided fasteners to join the top of the UPS and Delta external battery pack together. Please refer to Figure 7. Connect the Delta External Battery Pack with the UPS ...
Page 13
UPS. Parallel the Delta External Battery Packs To extend the backup time, you may parallel the Delta external battery packs before connecting them to the UPS. WARNING: For parallel application, only use the same type of Delta external battery packs (same material No.)
Page 14
(Figure 9: Parallel the Delta External Battery Packs) NOTE: Once the parallel connection is completed, please refer to the steps mentioned in ‘Connect the Delta External Battery Pack with the UPS’ to connect any of the parallel Delta external battery packs to the UPS. Amplon RT Series...
Follow Delta Amplon RT Series 1/ 1.5/ 2/ 3kVA UPS User Manual to execute input/ output connection. Follow Chapter 4 : Installation Procedures to connect the UPS and the Delta external battery pack. Follow Delta Amplon RT Series 1/ 1.5/ 2/ 3kVA UPS User Manual to turn on the UPS.
Dimensions (W × D × H) (17.3 x 13.2 x 3.5 inch) (17.3 x 16.9 x 3.5 inch) 16 Kg 23.1 Kg Weight (35.3 lb) (50.9 lb) Operating 0°C~50°C (32°F~122°F) Temperature Environment Relative 5%~95% (No condensing) Humidity Amplon RT Series...
Page 17
Delta External RT-2KB RT-3KB Battery Pack Applicable to Amplon 2kVA 3kVA RT Series UPS Type VRLA Battery Q’ty 2 × 4 × 12V/9Ah 2 × 6 × 12V/9Ah 440 × 430 × 88.2 mm 440 × 565 × 88.2 mm Dimensions (W ×...
Need help?
Do you have a question about the Amplon RT Series and is the answer not in the manual?
Questions and answers