EWPlus 961/971/974
Electronic controllers for refrigeration units
:
NOTE
When switched on, the device performs a Lamp Test; the
display and LEDs will flash for several seconds to check that
they all function correctly.
UP
Press and release
Scroll menu items
Increases values
Press for at least 5 sec
Activates the Manual Defrost function
The device is designed for panel mounting. Drill a 29x71 mm hole and insert the instrument; secure it with the special brackets
provided. Do not install the instrument in damp and/or dirty places; in fact, it is suitable for use in places with ordinary or normal levels
of pollution. Keep the area around the instrument cooling slots adequately ventilated.
70 mm
EN
USER INTERFACE
Reduced SET / Economy LED
Permanently on: Energy Saving active
Flashing:
Quick flashing: access to level2 parameters
Off:
Compressor LED
Permanently on: compressor active
Flashing:
Off:
Defrost LED
Permanently on: defrost active
Flashing:
Off:
°C LED
Permanently on: °C setting (dro = 0)
Off:
°F LED
Permanently on: °F setting (dro = 1)
Off:
Alarm LED
Permanently on: alarm active
Flashing:
Off:
DOWN
Press and release
Scroll menu items
Decrease values
Press for at least 5 sec
Function can be configured by the user
((see parameter H32)
MOUNTING - DIMENSIONS
71 mm
74 mm
Reduced SET active
otherwise
a delay, a protection or a
locked start-up
otherwise
manual or D.I. activation
otherwise
otherwise
otherwise
alarm acknowledged
otherwise
KEYs
STAND-BY (ESC)
Press and release
Returns to the previous menu level
Confirms parameter value
Press for at least 5 sec
Attiva la funzione Stand-by (OFF)
(quando non sono all'interno dei menu)
Fans LED
Permanently on: fans active
Off:
otherwise
Aux LED
Permanently on: Aux output active
Flashing:
Deep Cooling cycle active
Off:
Aux output not active
HEAT mode LED
Permanently on: compressor in HEAT mode
Off:
otherwise
(only EWPlus 961)
NOTE:
If the instrument is set in the COOL mode, in order to use
it in the HEAT mode it is necessary to reprogramme the
instrument by using the properly programmed Copycard.
The same procedure should be followed to pass from the
HEAT mode to the COOL mode.
NOT USED
(only EWPlus 961)
SET (ENTER)
Press and release
Displays alarms (if active)
Opens Machine Status menu
Press for at least 5 sec
Opens Programming menu
Confirm commands

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EWPlus 971 and is the answer not in the manual?

Questions and answers

Summary of Contents for Eliwell EWPlus 971

  • Page 1 EWPlus 961/971/974 Electronic controllers for refrigeration units USER INTERFACE Reduced SET / Economy LED Fans LED Permanently on: Energy Saving active Permanently on: fans active Flashing: Reduced SET active Off: otherwise Quick flashing: access to level2 parameters Off: otherwise Compressor LED Aux LED Permanently on: compressor active Permanently on: Aux output active...
  • Page 2 Pb1 probe 230Va (±10%) 4.5W 10-11 Digital Input 1 9 10 230Va power supply TTL input EWPlus 971 TERMINALs PLUS Compressor relay ( ) 230Va power supply input N.O. Defrost relay ( ) 230Va (±10%) 4.5W N.C. Defrost relay ( )
  • Page 3: "Machine Status" Menu

    DISPLAYING THE PROBES: When labels Pb1 or Pb2* are present, press the key to view the value measured by the corresponding probe. N.B.: 1) Pb2 is only present on EWPlus 971/974 models. 2) the value cannot be modified. MENU' DI PROGRAMMAZIONE To access the “Programming”...
  • Page 4: Manual Defrost Cycle Activation

    - E1: in the event of cold room probe faulty (Pb1), the indication “E1” will appear on the display. - E2: in the event of defrost probe faulty (Pb2), the indication “E2” will appear on the display (EWPlus 971/974 models only).
  • Page 5: Further Informations

    Better than 0,5% of full-scale + 1 digit Resolution: 0,1 °C Buzzer: YES (it depends from model) 1 NTC input (EWPlus 961) or 2 NTC inputs (EWPlus 971/974) Analogue Input: Digital Input: 1 voltage-free digital input (D.I.1) Output Characteristics Digital Output:...
  • Page 6 TABLE OF "INSTALLER" MENU PARAMETERS PAR. DESCRIPTION RANGE M.U. EWPlus 961 EWPlus 971 EWPlus 974 LEVEL Temperature control SEtpoint. LSE ... HSE °C/°F The SEtpoint is visible from the "machine status" menu only. COMPRESSOR ('CP' folder) dF1 diFferential. Compressor relay activation differential.
  • Page 7 PAR. DESCRIPTION RANGE M.U. EWPlus 961 EWPlus 971 EWPlus 974 LEVEL Maximum temperature alarm. Temperature value (intended either as distance from HAL (!) Setpoint or as an absolute value based on Att) which, if exceeded in an upward direction, LAL ... 320 °C/°F...
  • Page 8: Liability And Residual Risks

    - installation/use on panels not complying with current standards and regulations. DISCLAIMER This document is the exclusive property of ELIWELL CONTROLS SRL and may not be reproduced or circulated unless expressly authorised by ELIWELL CONTROLS SRL itself. Every care has been taken in preparing this document; nevertheless ELIWELL CONTROLS SRL cannot accept liability for any damage resulting from its use.