Spirax Sarco AE36 Installation And Maintenance Instructions Manual
Spirax Sarco AE36 Installation And Maintenance Instructions Manual

Spirax Sarco AE36 Installation And Maintenance Instructions Manual

Automatic air eliminators / air vents for liquid systems

Advertisement

0170550/5
Automatic Air Eliminators/ Air Vents for Liquid Systems
Installation and Maintenance Instructions
Printed in the UK
IM-P017-03 ST Issue 5
AE36 and AE36A
IM-P017-03
1. General
safety information
2. General
product information
3. Installation
4. Commissioning
5. Operation
6. Maintenance
7. Spare parts
© Copyright 2004
ST Issue 5
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AE36 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Spirax Sarco AE36

  • Page 1: Safety Information

    0170550/5 IM-P017-03 ST Issue 5 AE36 and AE36A Automatic Air Eliminators/ Air Vents for Liquid Systems Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation 4. Commissioning 5. Operation 6. Maintenance 7. Spare parts Printed in the UK IM-P017-03 ST Issue 5 ©...
  • Page 2: General Safety Information

    Before attempting any maintenance consider what is or may have been in the pipeline. Ensure that any pressure is isolated and safely vented to atmospheric pressure before attempting to maintain the product, this is easily achieved by fitting Spirax Sarco depressurisation valves type DV (see separate literature for details). Do not assume that the system is depressurised even when a pressure gauge indicates zero.
  • Page 3: General Description

    2. General product information 2.1 General description The AE36 range of automatic air eliminators /air vents are designed for use on hot and cold water installations. The body and cap are of austenitic stainless steel type 316L. They are available as follows:...
  • Page 4 2.3 Pressure /temperature limits Pressure psi g Pressure bar g The product should not be used in this region as damage to the internals may occur. Body design conditions PN10 PMA Maximum allowable pressure 10 bar g @ 150°C (145 psi g @ 302°F) TMA Maximum allowable temperature 150°C (302°F)
  • Page 5 3. Installation Note: Before actioning any installation observe the 'Safety information' in Section 1. Referring to the Installation and Maintenance Instructions, name-plate and Technical Information Sheet, check that the product is suitable for the intended installation: Check materials, pressure and temperature and their maximum values. If the maximum operating limit of the product is lower than that of the system in which it is being fitted, ensure that a safety device is included in the system to prevent overpressurisation.
  • Page 6: General Information

    All work must be carried out by a suitably competent person. Before starting work ensure that suitable tools are available. Use only Spirax Sarco replacement parts. Before attempting to work on the air vent ensure that it is isolated from the rest of the pressurised system. Allow time for the temperature of the air vent to normalise.
  • Page 7 AE36A only Fig. 4 Table 1 Recommended tightening torques Item (lbf ft) 10 - 12 (7.0 - 8.6) Cheesehead M4 x 6 2.5 - 2.8 (1.8 - 2.0) IM-P017-03 ST Issue 5...
  • Page 8: Spare Parts

    Always order spares by using the description given in the column headed 'Available spares' and state the size and type of automatic air vent. Example: 1 - Maintenance kit for a Spirax Sarco ½" AE36A automatic air eliminator /air vent with check valve.