7. Test Pin

7. Test Pin
When the test pin on the outdoor unit control PCB is short-circuited, each part can be operated individually.
• After turning OFF the main unit power, short-circuit the test pin (CN22, black), then turn the power back ON.
Output is performed in the sequence shown in the table below, for 0.5 seconds each.
Output
1
Relay RY12
4-way valve (20s)
2
Relay RY4
Bypass valve (BPV)
3
Relay RY6
Oil recovery valve (ORVR)
4
Relay RY11
Refrigerant balance valve (RBV)
5
Relay RY10
Refrigerant control valve (RCV)
Operation
6
7
8
9
3-33
Output
Relay RY8
Save valve (SAVE)
Relay RY1
Crankcase 1 (CH1)
Relay RY2
Crankcase 2 (CH2)
Relay RY3
Crankcase 3 (CH3)