iPro Parameter List
Parameter Name
Fan Operation Mode: OnR-OfD-Fan on with refrigeration off
FOp
defrost. OnR-OnD-Fan on Refrigeration on defrost. OnF-OfD-Fan on
continuously off defrost. OnF-OnD-Fan on continuously, on
defrost.
FAd
Fan After Defrost: Temperature-Activate after defrost based on Fst,
Fhy. Time-Activate after defrost based on Ftd.
FSt
Fan Temp Setpoint
FHy
Fan Temp Hysteresis
Ftd
Fan Time Delay
FanAmpOn
Amps required for Fan status to be considered ON
FanAmpDel
Time delay for status change once amps reach threshold
ALU
Maximum control temperature alarm, relative to active setpoint
ALL
Minimum control temperature alarm, relative to active setpoint
AHy
Alarm hysteresis
ALd
Alarm delay time before displaying alarm active
SHF%
Superheat Control Temp failure-position valve is driven to in the
event of superheat reading failure
SCF%
Suction Control Temp failure-position the valve is driven to in the
event of control temperature failure
AIC01
Configuration of Probe 1
AIC02
Configuration of Probe 2
AIC03
Configuration of Probe 3
AIC04
Configuration of Probe 4
AIC05
Configuration of Probe 5
AIC06
Configuration of Probe 6
AIC07
Configuration of Probe 7
AIC08
Configuration of Probe 8
AIC09
Configuration of Probe 9
AIC10
Configuration of Probe 10
Table 16-1 - iPro Parameter List
Commissioning the Device in E2E
Description
Fan Parameters
Alarm Parameters
Analog Input Parameters
Range
OnR-OfD, OnR-OnD, OnF-OfD,
OnF-OnD
Temperature/Time
-10-70°
1-30°
0:00-10:00 minutes
0-60 amps
1-90 seconds
0-99° above setpoint
-99-0° below setpoint
0-20°
0-255 minutes
0-100%
0-100%
Discharge 1-6, Return 1-3, Defrost Term
1-6, Coil Out 1-3, Pressure 1-3, Fan
Amperage, Defrost Amperage
iPro Parameter List • 61