® ADOS MWS 897 Operating Instructions Multi-channel Gas Warning Unit Issue: 08/15 Version: 1.1 A D O S G m b H T E L . : + 4 9 ( 0 ) 2 4 1 9 7 6 9 - 0 E s t .
The alarm outputs can be tested without any application of gas. The unit incorporates a RS232 interface for data communications and a voltage output of 0-5V. The ADOS gas warning unit MWS 897, depending on the model, can be operated on 230 V~, 110 V~ or 24 V= voltage supplies.
Page 4
ADOS GmbH MWS 897 Page 2 After switch-on the unit is automatically ready for normal cyclic measurement operation. To prevent alarm errors during the stabilising/warm up phase of the gas sensors, the alarm and fault monitoring is suppressed for approximately 5 minutes after switch on.
ADOS GmbH MWS 897 Page 3 Equipment settings / Menu Navigation through menu To modify the basic factory settings, both keys must be hold pressed. The input code is necessary to protect against unauthorised modification. To enter the code “897", the “SELECT” key must be pressed to increment the digit.
ADOS GmbH MWS 897 Page 4 Menu Function Service Switch the maintenance modus “ON” or “OFF” to avoide false alarms during repair or calibrating the sensors. If the maintenance mode is active, all alarm and faults are supressed. By selecting “ON" the duration is 60 minutes after leaving the menu.
ADOS GmbH MWS 897 Page 5 3.5.4 Menu Function Sensor->Limit-relay Assign the alarm relay to the limit value of a measuring point. The allocation is optional, each limit value can be assigned to a maximum of 3 alarm relays. One alarm relay can also be assigned more than once (e.g.
Vol.%, ppm, %LEL, etc. Range: upper and lower measure range z.B. ADOS TOX CO 300 ppm -> MIN = 0 und MAX = 300 GTR 196 with ph -> MIN = 2 und MAX = 13...
The owner or operator of the system is offered the possibility of completing a maintenance contract with the manufacturer, the ADOS GmbH company, which will guarantee a smooth and efficient servicing by the company's own customer service.
ADOS GmbH MWS 897 Page 9 Cable list Mains 230V/50Hz NYM-J 3 x 1,5 mm Mains 230V/50Hz for horns and warning banners NYM-J 3 x 1,5 mm Sensors J-Y(ST)Y 2 x 2 x 0,8 mm , screened bzw. J-Y(ST)Y 4 x 2 x 0,8 mm...