Spare Parts
Preventative Maintenance
Spare Parts and Preventative Maintenance
Part No.
PN-504125
PN-271938
PN-35744
440R-N23132
1606-XLP50E
ATTENTION: In addition to the restart procedure in the user manual, perform
the Verify Operation procedures on
components.
The estimated time required to verify if the functional safety system in the
drive is functioning is less than 0.5 hours.
IMPORTANT See the PowerFlex™ 7000 user manual for detailed preventative
maintenance schedule and procedure for other non-safety related parts.
Replace the following parts at 12 year intervals to maintain the SIL rating of
the drive.
Part
OIBBS
OIB2
SGCTs
MSR127
Rockwell Automation Publication 7000-UM203C-EN-P - September 2018
Description
Optical Interface Base Board Safety (OIBBS)
Optical Interface Board (OIB2)
Safety Industrial Relay
Safety Relay
XLP 50 W Power Supply
page 23
after replacing any of these
Quantity
2
2/4/6 (based on voltage class)
12/24/36 (based on voltage class)
1
B
Appendix
Quantity
1
1
1
1
1
39
Need help?
Do you have a question about the PowerFlex 7000 Series and is the answer not in the manual?
Questions and answers