Commissioning
4.2 Commissioning
No.
Input screen of the IOP
27/21
Save settings
28/28
Saving, please wait
1) If the IOP Assistant does not offer this setting, after completing the basic commissioning, set parameter p1900 to a value
of 1 using the parameter menu.
Identifying motor data
Alarm A07991 is output for as long as the converter has still not identified the motor data.
You must switch on the motor (e.g. from the IOP) to identify the motor data. The frequency
converter switches-off the motor after the motor data identification has been completed.
Motor data identification for dangerous loads
Secure dangerous plant and system parts before starting the motor data identification, e.g.
by fencing off the dangerous location or lowering a suspended load to the floor.
You have completed the converter's basic commissioning.
4.2.2
Enable "Safe Torque Off" safety function
Requirements:
● Commission a CU240E-2 Control Unit.
● In the basic commissioning, you selected a setting for the interfaces in which two
terminals are reserved for a safety function.
The "Basic Safety" wizard guides you through the enabling of the "Safe Torque Off (Basic
Safety)" safety function in a maximum of 18 steps. Depending on the sources for "Safe
Torque Off", you can skip individual steps.
NOTICE
STO via terminal
If you implement the "Safe Torque Off" via digital inputs, DI4 and DI5 are brought together
to form a fail-safe digital input (FDI). You may not use these digital inputs for other
commands.
46
Selected setting on the IOP
Save
CAUTION
Converter with Control Units CU230P-2; CU240B-2; CU240E-2
Getting Started, 11/2013, A5E32885834B AA
Parameter
Confirm with OK
Confirm with OK