To Set the Motor Poles
1
Press ESC to enter programming mode
2
Press ESC until parameter H001 is on the
display of your drive
3
Press the UP key until H004 is reached
4
Then press the SET key to enter the H004
parameter
5
Now you can set the motor poles based on
the speed of your motor
6
Press the SET key to save the data
Motor poles = 120*60/synchronous speed
(1200, 1800, 3600 RPM)
To Set the Speed Reference
1
Press ESC to enter programming mode
2
Press ESC until parameter A001 is on the
display of your drive
3
Then press the SET key to enter the A001
parameter
4
Select the speed reference from the options
below
00- To use the Keypad
Potentiometer
01- Analog input (0-
10Vdc, or 4-20mA)
from the terminals
02- When using
the Keypad set
the speed with
parameter F001
03- When setting the
speed via Modbus
communication
network
5
Press the
SET key to
save the
data
04- Option card used
for speed
06- If your application
is using a pulse
train input
07- When setting the
speed via the
Easy Sequence
programming
10- When the speed
is a result of an
operation used
in your drive
programming

Advertisement