Dual input inverter, the commercial power as default source, ac backup in a dc environment, leverage your existing dc infrastructure, one stop shop, wide output power range, harshest ac input conditions, without compromising the quality of the ac output,
Page 1
TSI BRAvo - 230vAC user manual v7.0 BEyonD ThE InvERTER ThE nEW gEnERATIon of poWER ConvERTERS DuAl InpuT InvERTER The Commercial power as default source AC BACkup In A DC EnvIRonmEnT leverage your existing DC infrastructure onE STop Shop wide output power range...
8.2.5 DC input ............................... 8.2.6 AC input ..............................8.2.7 AC output.............................. 8.2.8 Signalling.............................. 8.2.9 Remote on/off ............................ 8.2.10 Internal buss (TSI Bus 6 pin / TSI Bus 8 pin) ..................8.2.11 Rear cover ............................– TSI Bravo – user manual – v7.0...
Page 3
14.2 manual by-pass <20kvA ........................... 14.3 normal to By-pass ............................14.4 By-pass to normal ............................14.5 manual by-pass >20kvA ..........................14.5.1 normal to By-pass ..........................14.5.2 By-pass to normal ..........................15. finishing ................................... – TSI Bravo – user manual – v7.0...
Page 4
20. Appendix .................................. 20.1 Cabinet foot print, layout ........................... 20.2 Single phase circuit diagram ..........................20.3 Three phases circuit diagram ........................... 20.4 main connection, Single phase ......................... 20.5 mains connection, Three phases ........................– TSI Bravo – user manual – v7.0...
1. Abbreviations Twin Sine Innovation Enhanced power Conversion Regular Digital Signal processor Alternating current Direct current Electro Static Discharge main Earth Terminal manual By-pass TCp/Ip Transmission Control protocol/Internet protocol universal Serial Bus – TSI Bravo – user manual – v7.0...
If the equipment is dismantled, to dispose of the products it consists of, you must stick to the local regulations in force in the country of destination and in any case avoid causing any kind of pollution. – TSI Bravo – user manual – v7.0...
Indoor sites min Class II outdoor sites min Class I + Class II or combined Class I+II 2.3 other Isolation test must not be performed without instructions from the manufacturer. – TSI Bravo – user manual – v7.0...
0ms source transfer time and controlled down stream clearing capacity. BOOST L’ FILTER FILTER N’ FILTER User Interface Redundant Local Signaling Commuication 1 | nova EpC (94%), media EpC (95%), Bravo EpC (96%) – TSI Bravo – user manual – v7.0...
Isolation test must not be performed without instructions from the manufacturer. L’ FILTER FILTER N’ User Interface Redundant Local Signaling Commuication 2 | veda REg 88%, nova/media/Bravo REg 91% – TSI Bravo – user manual – v7.0...
Ip 20 in open rack max 10kvA (6kvA ) per shelf 480 (D) x 19” (W) x 2u (h) 6 kg empty 1 | +24vDC version 2 | +24vDC version – TSI Bravo – user manual – v7.0...
3 outgoing alarms 2 digital input moD bus CAn bus uSB front connector In depth, read the TxS manual xxx.xxx – TSI Bravo – user manual – v7.0...
WARnIng If ATS (automatic transfer switch) IS InSTAllED upSTREAm. mAkE SuRE ThAT ThE ATS SWITCh DoES noT AlloW TRAnSfER BETWEEn AC SouRCE ouT of SynC. ThE mAXImum AlloWED phASE ShIfT IS 10°. – TSI Bravo – user manual – v7.0...
40A 5.3.2 mCCB AC output distribution via mCCB in the range up to 400A (1p, 2p or 3p) max two mCCB per inverter cabinet. – TSI Bravo – user manual – v7.0...
6.1.1 Display Backlit 2 line dot matrix The display show two values simultaneous 6.1.2 TCp/Ip Agent The TCp/Ip interface board is mounted on the CanDis shelf and is powered within the system. – TSI Bravo – user manual – v7.0...
Seamless transfer (0ms) between primary and secondary source of supply no single point of failure flexible AC output distribution full modularity full redundancy 3 | +24v version 4 | Bravo EpC -48vDC/230vAC – TSI Bravo – user manual – v7.0...
(5) in the cabinet front and rear frame of the left and the right side fix the left and right slider of the cabinet with the supplied screws (4) – TSI Bravo – user manual – v7.0...
Wire all positions in the sub-rack for future expansion Input AC / output AC / Input DC / Signal cables shall be separated Cable crossings shall be done in 90 deg angles – TSI Bravo – user manual – v7.0...
CB per inverter module Cable, min Connector Torque +24vDC 2 x 25mm -48vDC / Bravo pack 2 x 16mm -60vDC 2 x 10mm 1.5nm +110vDC 2 x 6mm +220vDC 2 x 2.5mm – TSI Bravo – user manual – v7.0...
Minor (NUA) Digital input characteristics (Digital In 1 / 2) ln 1 Digital 1 Signal voltage +5vDC (galvanic insulated) Common max wire size ln 2 Digital 2 – TSI Bravo – user manual – v7.0...
2-3 Status Indication open open normal operation All (green) Closed open AC output (off) AC Input (green) DC Input (green) open Closed normal operation All (green) Closed Closed normal operation All (green) – TSI Bravo – user manual – v7.0...
Remove material using a pair of side cutters to allow cables enter and exit. The rear cover is ordered separately Connect cables Cut holes to allow cable access Clip rear cover in place – TSI Bravo – user manual – v7.0...
Input AC / output AC / Input DC / Signal cables shall be separated Cable crossings shall be done in 90 deg angles Empty inverter positions shall be covered with blanks – TSI Bravo – user manual – v7.0...
The top cover is possible to split in three parts to facilitate cabling. The top cover has support to strap the cables with nylon tie straps. ground DC Input (X1) Alarm (X3, X5, X6) AC Input (X2) AC output (X4) – TSI Bravo – user manual – v7.0...
The three phase input is 123, ABC, RST phase sensitive, clock wise rotation is recommended. phase one to start shall be 0° phase shift, the other phases will organize -120° phase shift and + 120° phase shift resulting in three phase output. – TSI Bravo – user manual – v7.0...
Screws and nuts are not included in the delivery. m10 holes Internal DC distribution with circuit breakers (Q01-Q32) per inverter module. max 3x240mm per pole – TSI Bravo – user manual – v7.0...
Page 26
Individual DC input per module/shelf and common return. note: Screws and nuts are not included in the delivery. m5 holes , bus bar thickness (check) max 35 mm per connection terminal. – TSI Bravo – user manual – v7.0...
The AC input supply breaker shall be 2p (for single phase) and min 3p (for three phase) power (kvA) AC Input Screw terminal fuse/CB Cable mm 125A 3x40A 3x10 160A 200A 240A 3x80A 3x25 280A 3x100A 3x35 320A – TSI Bravo – user manual – v7.0...
2x60A 160A 3x60A 220A 2x500A live: Screw terminal 260A Common: Cable lug. 2.5mm 2x750A m5-2,5nm torque 315A 3x500A 360A 400A 3x600A 420A 2x1000A 9.4.13 Signalling All relays are in non energized position – TSI Bravo – user manual – v7.0...
Page 31
Initial start of system must be performed with operational T2S. Should the T2S be missing at start-up the modules will fail to start. The following sequence of the Remote on/off will force system to start without the T2S #3 ==> #2 ==> #3 will force modules to start. – TSI Bravo – user manual – v7.0...
60 seconds delay - non urgent 30 second delay uSB port parameter setting via laptop or Copy/paste. factory default according to list of set values, see Table of set values – TSI Bravo – user manual – v7.0...
Read T2S manual for detailed setup 11.1 Communication setting Bits per second 115200 Data bits parity none Stop bits flow control none – TSI Bravo – user manual – v7.0...
0 > Return to index 1 > force refresh of configuration textes and constants 2 > force refresh of events description texts 4 > Security Access 0 > Return to index 1 > Enable password protection – TSI Bravo – user manual – v7.0...
A) Slide the module in B) push firmly till the connection is C) Close the cover and latch the module properly engaged in place if too hard redo step B – TSI Bravo – user manual – v7.0...
Replace front, make sure that the front latch properly. plug in Check fan for operation Access T2S and reset the fan run time alarm from within the action menu – TSI Bravo – user manual – v7.0...
A wide range of breakers is used. Breakers in picture may be different upon delivery. make sure that the breaker is in off position Connect load cables to the terminal Switch the breaker on – TSI Bravo – user manual – v7.0...
The manual by pass operates via three individual switches (S2, S1, S3) that creates a by-pass from mains input via output AC distribution. Inverter modules are by-passed and possible to disconnect without impacting the load. – TSI Bravo – user manual – v7.0...
14.5.1 normal to By-pass 0 1 1 0 1 0 14.5.2 By-pass to normal 0 1 pAuSE, wait until the inverter modules have come to full operation (30-60 seconds) 0 1 1 0 – TSI Bravo – user manual – v7.0...
Cover empty inverter positions with blanks. make sure that the Remote on/off is appropriately wired according to local regulations. make sure that the point of AC supply meets local regulations. – TSI Bravo – user manual – v7.0...
Installation and commissioning must be done and conducted by trained people fully authorized to act on installation. It is prohibited to perform any isolation test without instruction from manufacturer. Equipments are not cover by warranty if procedures are not respected. – TSI Bravo – user manual – v7.0...
Switch off AC input (commercial power failure) and check the alarm according to the configuration Switch off DC input (DC power failure) and check that the alarm according to the configuration Check the different digital input according to the configuration (when used) – TSI Bravo – user manual – v7.0...
Check that the RJ45 cable is connected between T2S shelf and CanDis shelf no value on TCp/Ip: Check that the RJ45 cable is connected between T2S shelf and CanDis shelf Wait approx 2 minutes to allow the system to collect serial data. – TSI Bravo – user manual – v7.0...
With an infrared camera check termination hot spots - Tighten terminations 18.4 manual by-pass If mains failure during operation the load is lost perform a manual by-pass operation – TSI Bravo – user manual – v7.0...
The RmA number should be mentioned on all shipping documents related to the repair. Be aware that products shipped back to CE+T power without being registered first will not be treated with high priority! – TSI Bravo – user manual – v7.0...
20.4 mains connection, Single phase TN - C - S (400/230VAC) TN - S (400/230VAC) TT (400/230VAC) TN - C (400/230VAC) – TSI Bravo – user manual – v7.0...
20.5 mains connection, Three phases TN - C - S (400/230VAC) TN - S (400/230VAC) TN - C (400/230VAC) TT (400/230VAC) – TSI Bravo – user manual – v7.0...