CurrentGuard S U R G E P R O T E C T I O N Installation, Operation and Maintenance Manual PN 750-0098-002 Surge Protective Devices CurrentGuard Compact...
CURRENT TECHNOLOGY CURRENTGUARD COMPACT INSTALLATION, OPERATION AND MAINTENANCE MANUAL ® Thank you for choosing the Current Technology CurrentGuard Compact (CGC) ® Guide to Installation series Surge Protective Device (SPD) . We look forward to fulfilling your facility- and Assistance wide surge protection needs .
CURRENT TECHNOLOGY CURRENTGUARD COMPACT INSTALLATION, OPERATION AND MAINTENANCE MANUAL ® Confirm that the voltage(s) and service configuration shown on the ✓ Pre-Installation Checklist CurrentGuard product label are consistent with the voltage and service configuration of the facility . The model number can be found on the left side of the CurrentGuard unit .
CURRENT TECHNOLOGY CURRENTGUARD COMPACT INSTALLATION, OPERATION AND MAINTENANCE MANUAL ® Figures 1–3 show the electrical relationship between CurrentGuard and these Service Configurations three basic service configurations: Split-Phase, 3-Wire; 3-Phase, 4-Wire Wye; and 3-Phase, 3-Wire Delta . Figure 1 Split-Phase, 3-Wire...
CURRENT TECHNOLOGY CURRENTGUARD COMPACT INSTALLATION, OPERATION AND MAINTENANCE MANUAL ® Following all applicable National Electrical Code standards as well as state ✓ Plan Your Installation and local codes, connect phase, neutral* and ground to CurrentGuard . CurrentGuard units come with 36" of #10 AWG conductors . Ensure that the conductor lengths are kept as short and straight as possible .
CURRENT TECHNOLOGY CURRENTGUARD COMPACT INSTALLATION, OPERATION AND MAINTENANCE MANUAL ® CAUTION: Prior to installation ensure the system configuration and voltage is Electrical Connections equivalent to the CurrentGuard unit being installed . The CurrentGuard units come with 36" of #10AWG conductors . Each phase conductor is labeled (Phase A, B or C) .
Page 9
CURRENT TECHNOLOGY CURRENTGUARD COMPACT INSTALLATION, OPERATION AND MAINTENANCE MANUAL ® Remote Monitoring All CurrentGuard units with the -M monitoring option come with one set of Form “C” dry relay contacts for the surge protective device status . These contacts are for connection to a user-provided remote alarm and monitoring circuit .
We will immediately ship a replacement for the defective parts free of charge (installation labor and site preparation excluded) . Return the defective parts to Current Technology within 30 days of receiving the replacement . Failure to return the defective parts will result in billing for the replacement parts . To help...
Page 11
CURRENT TECHNOLOGY CURRENTGUARD COMPACT INSTALLATION, OPERATION AND MAINTENANCE MANUAL ® Thomas & Betts Power Solutions warrants that CurrentGuard Compact surge 10 Year Limited Warranty protective device (the “Product”), shall meet applicable industry standards and specifications and be free from defects in materials and/or workmanship .
Page 12
CURRENT TECHNOLOGY CURRENTGUARD COMPACT INSTALLATION, OPERATION AND MAINTENANCE MANUAL ® Model # Date of Purchase Date Installed Installer Thomas & Betts Power Solutions 5900 Eastport Blvd . • Richmond, VA 23231-4453 USA Tel: (804) 236-3300 • Toll free: (800) 238-5000 • Fax: (804) 236-4841 tnbpowersolutions.com/current_technology...