Installation & Maintenance Instructions MM-601(C) Series FS4-3 ® General Purpose Liquid Flow Switch F L O (specified models only) with Stainless Steel Paddles Series FS4-3 OPERATION This control is an independently mounted water flow sensing device that makes or breaks an electrical circuit when flow stops or starts.
FLOW RATES Flow rates required to activate flow switch are shown Settings will vary when used to sense flow of other in chart below. The values are calculated for sensing fluids or if located in a vertical pipe. water (potable, non-polluted) in a horizontal pipe. NOTE: DO NOT USE LIQUID FLOW SWITCHES Max.
INSTALLATION – STEP 1 - Paddle Sizing Determine the correct paddle length for your installation from the chart below. Pipe Size Paddle Trim to Length (Standard Length) (mm) (mm) (mm) 1" (25mm) (25) (25) 2" (51mm) (32) (51) (32) (40) (51) (38) 3"...
Page 5
STEP 2 - Determine the Location of the Flow Switch • The flow switch should be located in a horizontal section of pipe where there is a straight horizontal run of at least 5 pipe diameters on each side of the flow switch.
b. Apply pipe sealing compound or Teflon tape to the flow switch pipe threads. ® Teflon NOTE: Do not apply sealant to first threads as this F L O switch is grounded (earthed) via the pipe mounting. c. Insert the flow switch into the pipe tee. Turn the flow switch two (2) or three (3) revolutions FLOW clockwise until tight.
Page 7
b. Electrical Conduit Connection • Connect electric conduit to flow switch electrical enclosure. • Follow accepted electrical practices when installing fittings and making connections. • Refer to and follow local codes and standards when selecting the types of electrical fittings and conduit to connect to flow switch.
STEP 6 - Adjustment Adjustment is necessary only if required flow/no- Single Switch Models Double Switch Models flow setpoints are above factory set minimum. a. Turn off power. Remove switch cover. b. Turn the adjusting screw clockwise to increase setpoint. IMPORTANT: Do not attempt to lower flow switch setpoint from original factory minimum setting.