Web page programming
There are lower level tabs located on this Web page.
Click the "Panelboards" tab.
This will open the "Panelboard Configuration" screen.
N
otee:
The screen list may be blank or incomplete until a
"Discover Breakers" command has been issued.
This screen displays the BCBs connected to the controller
and the configuration of the panelboards. If there are four
BCBs connected to the controller, there will be four listed in
this screen as left or right.
Discover breakers
The controllable circuit breakers in the panelboards must
be discovered by the PRC-E controller. The "Discover
Breakers" command must be initiated at the commissioning
of the system, after any addition of controllable circuit
breaker(s) in a panelboard(s), after any addition of PRC
Expansion (PRCEP) panelboard(s) to a system or after a
panelboard configuration change. During this discovery
process, the BCBs in the Master panelboard, and all
PRCEP panelboards connected to it, will be scanned for
the presence of controllable circuit breakers. The presence
of each controllable circuit breaker is captured and stored
in the controller's database. The BCB addressing is critical
for this process to be successful. In the Master and PRCEP
panelboards, each BCB should have a unique address of
1–8. See the "BCB Addressing" section of this document.0
48
PRC-E Series Instruction Manual MN014003EN August 2015 www.eaton.com
To initiate a "Discover Breakers" command, click the
"Discover Breakers" button at the bottom of the
"Panelboard Configuration" Web page.
During the "Discover Breakers" initiation the mouse pointer
changes to a wait timer.
Once complete, the "Panelboard Configuration" screen
will become active again and any BCBs discovered will be
displayed in the list.
By default, the BCBs are configured as 42-circuit
panelboards. The table below shows the default settings
that will be applied to the connected BCBs in 42-circuits
panelboards.
Default BCB addressing auto-configuration
Panelboard
Type
1
Left
2
Right
3
Left
4
Right
5
Left
6
Right
7
Left
8
Right
BCB ID (Address)
BCB Name
1
PNL1
1
PNL1
2
PNL2
2
PNL2
3
PNL3
3
PNL3
4
PNL4
4
PNL4
Need help?