Error Code List For Outdoor Unit - Ecoer EODA18H-2436 Service Manual

Esi(ultra) unitary system
Hide thumbs Also See for EODA18H-2436:
Table of Contents

Advertisement

ESI(Ultra) Service Manual
Past error codes can be spot checked from default mode by BS3 button, and seen from Ecoer Smart

Error code List for Outdoor Unit

Service App.
P1
High pressure protection
Error Code
Description
E1
System locks up when P1 has occurred six times in 3 hours.
P2
Low pressure protection in cooling mode
E2
System locks up when P2 has occurred six times within 3 hours.
P3
Compressor discharge temperature (TD) protection
E3
System locks up when P3 has occurred six times within 3 hours.
P4
Compressor discharge temperature (TD) sensor is disconnected or damaged
P5
Inverter module temperature (TF) protection
E5
System locks up when P5 has occurred six times within 3 hours.
P6
Compressor over-current protection
E6
System locks up when P6 has occurred six times within 3 hours.
P7
Liquid slugging protection
E7
System locks up when P7 has occurred three times within 5 hours.
P8
Low compressor voltage protection
E8
System locks up when P8 has occurred three times within 60 minutes.
P9
Abnormal compressor line sequence
PA
DC fan motor over-load protection
F1
Ambient temperature(TA) sensor fault
F2
Compressor suction temperature(TS) sensor fault
F3
Liquid line temperature(TL) sensor fault
F4
Defrost temperature(TH) sensor fault
F5
Compressor discharge temperature(TD) sensor fault
F6
Inverter module temperature(TF) sensor fault
F7
High pressure(HP) sensor fault
F8
Low pressure(LP) sensor fault
E4
Communication fault between main chip and INV drive chip
H1
Ambient temperature limit operation in cooling mode
H2
Ambient temperature limit operation in heating mode
H3
Abnormal switch alarm for 4-way valve
H4
Defrost temperature(TH) sensor is disconnected or damaged
H5
EEPROM fault
H6
Low voltage alarm
C0-C9
Compressor INV module protection
E0
System locks up when C0~C9 has occurred three times within 60 minutes.
1. On the case there is an "E" code, manually turn off the power supply for 5 minutes to reset, then turn on the
Remarks:
system to recover.
2. System goes to backup running under sensors fault varies from 7 to 180 days. Allow up to two sensors
backup running at the same time.
Manufacturer reserves the right to change specifications or designs without notice.
31/62
www.ecoer.com
Legend
Cannot restart *1
Cannot restart *1
Cannot restart *1
Cannot restart *1
Cannot restart *1
Cannot restart *1
Cannot restart *1
Cannot restart *1
Backup running*2
Backup running*2
Backup running*2
Backup running*2
Backup running*2
Backup running*2
Backup running*2
Backup running*2
Cannot restart *1
Just show alarm
Cannot restart *1
09.2018