Mitsubishi Electric MODBUS TCP User Manual

Communication unit for energy measuring unit (emu4-fd1-mb)

Advertisement

Quick Links

MODBUS
®
TCP Communication Unit for Energy Measuring Unit (EMU4-FD1-MB)
Model EMU4-CM-MT
User's Manual
・Before using the product, please read this manual carefully to ensure correct use.
・Make sure that the end users read this manual and then keep the manual in a safe place for future reference.
・Make sure to deliver this manual to the end-user.
About this manual
You can download User's manual of this Unit from the following site.
http://www.mitsubishielectric.co.jp/haisei/lvs/downloads/handling.htm
1. Features
This Unit is the optional dedicated product for Energy Measuring Unit (EcoMonitorLight Model: EMU4-FD1-MB)
This Unit enables to transfer measured data to programmable controllers for data acquisition via MODBUS
2. Checking package content
These following items for this device are included in package. Check that no items are missing.
(1) MODBUS
®
TCP Communication Unit ×1
(2) User's manual ×1
3. Safety Precautions
3.1 Precautions for Operating Environment and Conditions
This Unit is premised on being used in pollution degree II environment. When used in higher pollution degree, protect this Unit from pollution on another device side to be incorporated.
For the definition of the pollution degree and the over voltage category, refer to EN61010-1/2010.
Do not use this product in the places listed below. Failure to follow the instruction may cause malfunctions or decrease of product-life.
・Places the Ambient temperature exceeds the range -5-+55°C
・Dust, corrosive gas, saline and oil smoke exist
・Places the Relative humidity exceeds the range 30-85% or places with dewfall
・Places exposed to rain or water drop
・Operating altitude exceeds 2000m
・Vibration and impact exceed the specifications
・Places metal fragments or conductive substance are flying
・Places the average daily temperature exceeds +35°C
・Places in strong electromagnetic field or places large amounts of external noise exist
・Places exposed to direct sunlight
This unit is the open type device, which are designed to be housed within another device for prevention of electric shock. House this unit within the device such as the control panel
before use. (Indoor use)
3.2 Matters concerning the precaution before use
・Use the Unit in the specified usage environment and conditions.
・Before using this Unit, set MODBUS
®
TCP IP address, Subnet mask, Default gateway existence and Default gateway address.
※Please refer to "user's manual of EMU4-FD1-MB".
3.3 Installation Precautions
・For installation and wiring works, make sure that the power source is shut off for all outside phases.
DANGER
If all phases are not turned off, it may cause an electric shock or product damages.
・Any person who is involved in installation and wiring of this Unit should be fully competent to do this work.
CAUTION
・Work under the electric outage condition when installing and wiring. Failure to do so may cause electric shock or a failure of the Unit, a fire etc.
・In 100Mbps communication by the 100BASE-TX connection, a communication error may occur under the influence of high frequency noise from devices other
than this device in the installation environment.
・Take the following action to prevent the influence of high frequency noise in the construction of a network system.
(1) Wiring connection
・Do not install a twisted pain cable together with the main circuit and power cables, etc.
CAUTION
・Place the twisted pair cable in a duct.
(2) Communication system
・Increase the number of communication retries if necessary.
・Change the hub used for connection into a 10Mbps hub, and make communication at a transmission speed of 10Mbps.
3.4 Precautions for Use
・Before operating the product, check that active bare wire and so on does not exist around the product. If any exposed conductor is found, stop the operation immediately and take
an appropriate action such as isolation protection
・In the event of a power outage during the setting, the Unit is not set correctly. Please set again after power recovery.
・When you connect to Energy Measuring Unit of the Unit, Contrast of the LCD display of Energy Measuring Unit is reduced to small.
・Do not touch the live part. It may cause electric shock, electric burn injury or burnout of the device.
DANGER
・Work under the electric outage condition when installing and wiring.
・Do not disassemble or modify this Unit It may cause failure, malfunction, injury or fire.
・Do not touch the MODBUS
TCP communication connectors when communicating. It may cause a malfunction or failure of the Unit.
®
CAUTION
・Push the RESET switch with an appropriate force (1.6N). The addition of force than necessary, it may cause a malfunction or failure of the Unit.
3.5 Maintenance Precautions
・Use a soft dry cloth to clean off dirt of the Unit surface. Do not let a chemical cloth remain on the surface for an extended period of time nor wipe the surface with thinner or benzene.
・Check for the following items to use this Unit properly for long time.
<Daily maintenance>
(1) No damage on this Unit
(3) No abnormal noise, smell or heat
(2) No abnormality with LED indicators
(4) No looseness with installation and wire connection
(Check item No.4 under the power failure condition. Failure to do so may cause electric shock, failure of the Unit or a fire.)
3.6 Storage Precautions
To store this Unit, put it in a plastic bag. For long-time storage, avoid the following places. Failure to follow the instruction may cause a failure and reduced life of the Unit.
・Places the ambient tempe rature exceeds the range -10-+60°C
・Places the average daily temperature exceeds +35°C
・Places exposed to rain, water drop or direct sunlight
・Places the Relative humidity exceeds the range 30-85% or places with dewfall
3.7 Disposal Precautions
・When disposing of this Unit, treat it as industrial waste.
3.8 About packaging materials and this manual
For reduction of environment load, packaging materials are produced with cardboard, and this manual is printed on recycled paper.
If you are considering using this module for special purpose such as nuclear power plants,
aerospace, medical care or passenger vehicles please refer to our sales representative.
®
TCP communication.
・Vibration and impact exceed the specifications
・Places metal fragments or conductive substance are flying
・Places where dust, corrosive gas, saline and oil smoke exist
4. Name and function of each part
Front view
1)
2)
<Name and function of each part>
No.
Name of part
1)
LED
Operation status of MODBUS
2)
Connector for MODBUS
®
TCP communication
10BASE-T/100BASE-TX connector (RJ45)
3)
IEC rail stop
This is used to fix to an IEC rail.
4)
Connection stop
This is used to connect the MODBUS®TCP communication Unit to the Energy Measuring Unit.
5. How to wire
Connect the MODBUS
®
TCP communication Unit to the Energy Measuring Unit.
*This unit can be attached to EcoMonitorLight in below.
(1) Remove the blank label stuck to the side of
(2) Insert the connector of the MODBUS
the Energy Measuring Unit.
Unit into the connector of the Energy Measuring Unit and
make these Units closely-attached.
Blank label
・Work under the electric outage condition when connecting the Energy Measuring Unit. Failure to do so may cause electric shock, a failure of the Unit, a fire etc.
CAUTION
6. Mounting the Unit
There are two mounting methods, surface mounting and panel mounting.
6.1 Mounting the Unit on an IEC rail
*This unit can be attached to EcoMonitorLight in below. This unit can be attached to EcoMonitorPlus as well.
●Applicable IEC rail
●Mounting
(1) Hold the module and pull the stopper
of IEC rail down.
1
More than 7.3
(3) Push the Unit
Left-side view
4)
4)
Functions
®
TCP communication is displayed.
®
TCP communication
(3) Slide the connection stops (green-colored) of upper
and lower of the MODBUS
Unit to lock it.
DISP
+/PHASE
−/RESET
SET
EMU4-FD1-MB
Model
●How to remove
(2) Hook on the rail
IEC rail
(2) Pull tha module
(4) Push the stopper of
the IEC rail above.
(1) Hold the module and pull the
stopper of IEC rail down.
Back view
3)
®
TCP communication

Advertisement

loading

Summary of Contents for Mitsubishi Electric MODBUS TCP

  • Page 1 4. Name and function of each part Front view Left-side view Back view MODBUS ® TCP Communication Unit for Energy Measuring Unit (EMU4-FD1-MB) Model EMU4-CM-MT If you are considering using this module for special purpose such as nuclear power plants, aerospace, medical care or passenger vehicles please refer to our sales representative.
  • Page 2 9. Specifications 6.2 Screw mounting ●Panel cut dimension ●Attachment <Basic Specifications> External dimensions of External dimensions of Attach the plate by screws (M3×10). MODBUS ® TCP communication Unit Energy Measuring Unit Tightening torque:0.63N ・m Item Specifications Mounting screw Product Energy Measuring Unit (EMU4-FD1-MB) MODBUS TCP Communication Unit ®...