1. Introduction 1. Introduction Thank you for purchasing the Forza Atlas FDC 106K/110K Online UPS. To enjoy all the features and benefits of this unit, please read and follow all installation and operation instructions thoroughly before unpacking, installing or operating this 1.1 Transportation and storage...
Warning: This product is intended for commercial and industrial applications. Installation in the proper environment is required. 6K/10K 2. Installation and operation 1 2 3 The Forza Atlas series is offered in two different models, as shown in the table below. Model Capacity FDC-006K 6000 VA (6000 W)
1. RS-232 communication port Note 1: Make sure that the input and output wires and the input and output terminals are connected tightly. 2. USB communication port Note 2: There are two output terminal configurations to meet customers’ diverse requirements for serial or parallel connection. 3.
Option 3: 5. In order to access as Administrator, input the password: 111296. 6. When your computer restarts, the management software will appear as a light blue round icon located in the system tray, near the clock. For Mac users, please refer to the ForzaTracker quick installation guide inside the Mac folder. 3.
Indicates the inverter circuit is working. Indicates the output connector is working properly. LCD panel: Battery information Backup Fault Mute Operation Time Info Info Input & Battery Output & Battery Indicates the battery is charged at 0-25%, 26-50%, 51-75%, and Voltage Info Voltage Info 76-100% of its capacity.
Page 7
Low battery and low voltage indicator. Input and battery voltage information 9. Muting the buzzer 3) If the UPS is overloaded, the buzzer will beep twice every second. 4) In the event of an overload, all unnecessary loads must be removed one by one, to lower the total loads connected to the 1) To silence the buzzer, press the Mute button for at least 0.5 second.
13. Changing charging current 1. Failure to connect the Non-isolated neutral between each UPS may permanently damage the units. 2. Connect the output of each UPS to an output breaker. 1) This operation should only be performed by trained and qualified technicians. 3.
Note: All parameter settings will be saved only when UPS shuts down normally with internal or external battery connection. (Normal Abbreviation Display content Meaning UPS shutdown means turning off input breaker in bypass/no output mode). 01: Output voltage settings Interface Setting Not allowed Parameter 3: Output voltage...
Page 10
03: Voltage range for bypass 08: Bypass mode setting Interface Setting Interface Setting Parameter 2: Sets the acceptable low voltage for bypass operation. Setting Parameter 2: ranges from 110V to 209V, with a default value of 110V. OPN: Bypass allowed. When selected, the UPS will operate in Bypass mode Parameter 3: Sets the acceptable high voltage for bypass operation.
3-8. Operating mode/Status description 12: Hot standby function enable/disable Interface Setting When parallel UPS systems are successfully set up, an additional screen with “PAR” in parameter 2 will be displayed and assigned Parameter 2: a number in parameter 3, as shown below. The master UPS will be assigned “001” as default, while the slave UPSs will be identified HS.H: Enables or disables the Hot standby function.
3-9. Fault codes Operating mode/status When the input voltage exceeds the acceptable range or during a power failure, the Fault event Fault code Icon Fault event Fault code Icon Description UPS will start supplying power from the battery while the alarm will beep every 4 Bus start failure None Battery SCR short circuited...
4. Troubleshooting guide 5. Storage and maintenance If the UPS system does not operate correctly, use the table below to troubleshoot the problem. 5-1. Storage Charge the UPS for at least 7 hours before storing the unit. Cover the UPS, and place it upright in a cool, dry location. During Symptom Possible cause Solution...
* Derate capacity to 50% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC. 6. Technical specifications ** If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.