Status Indicators
Status Indicators for the
1756-IF8I Module
Diagnostics
Topic
Status Indicators
Status Indicators for the 1756-IF8I Module
Status Indicators for the 1756-IRT8I Module
Status Indicators for the 1756-OF8I Module
All 8-channel modules have Status (ST) and Fault (FLT) indicators on the
front of the module that have no equivalent on the 6-channel modules. All
8-channel ST and FLT indicators operate according to the description in the
8-channel module manual, even when in Emulation mode. Also in Emulation
mode, only ST, and FLT indicators 0...5 are active, indicators 6...7 are always
off.
The following table describes the status indicators.
Indicator
Status
OK
Steady green
Flashing green
Flashing red
Steady red
ST
Steady yellow
Flashing yellow
Off
FLT
Off
Steady red
Flashing red
Rockwell Automation Publication 1756-RM011A-EN-P - June 2016
Page
27
27
29
29
Description
The module is in a normal operating state in Run mode.
The module passed internal diagnostics and is not actively controlled or
the connection is open and the controller is in Program mode.
Previously established communication has timed out.
Replace the module.
The channel is operating as expected.
The channel is being calibrated.
The channel is not in use or is faulted.
The channel is operating as expected.
• The channel is faulted. Possible causes of the fault include:
– Underrange/overrange detection
– Triggered process alarm
– Triggered rate alarm
– Wire off detection
– Calibration fault
One of the following:
• The channel is faulted. See the previous row for more information
about faults.
• The channel is being calibrated.