Page 6
Service Without Removal From Line • Every valve factory-tested The Cla-Val Model 100-04 Hy-Check Valve is a hydraulically operated diaphragm valve with a built-in check feature to prevent return flow. Available in globe or angle pattern, it consists of a body, cover and diaphragm assembly.
Page 7
Rubber ® Stem, Nut & Spring Stainless Steel BODY OUTLET For material options not listed, consult factory. Cla-Val manufactures valves in more than 50 different alloys. PIPE PLUG (TYP) INLET Options Epoxy Coating - suffix KC Approvals Viton Rubber Parts - suffix KB This option NSF 61 Listed and FDA ®...
Page 9
Service Cla-Val Control Valves operate with maximum efficiency when mounted in horizontal piping with the main valve cover UP, however, other positions are acceptable. Due to component size and weight of 8 inch and larger valves, installation with cover UP is advisable. We recommend isolation valves be installed on inlet and outlet for maintenance.
Page 10
• Drip Tight, Positive Seating • Globe or Angle Pattern • Packless Construction The Cla-Val Model 100-23 Hy-Check Valve is a hydraulically operated diaphragm valve with a built-in check feature to prevent return flow. Available in a globe or angle pattern, it consists of three parts: body, cover and diaphragm assembly.
Page 11
Rubber ® Stem, Nut & Spring Stainless Steel For material options not listed, consult factory. Cla-Val manufactures valves in more than 50 different alloys. Options 12" Globe, Flanged Epoxy Coating - suffix KC For assistance in selecting appropriate valve options or valves manufactured...
Page 13
Service and Installation Cla-Val Control Valves operate with maximum efficiency when mounted in horizontal piping with the main valve cover UP, however, other positions are acceptable. Due to component size and weight of 10 inch and larger valves, installation with cover UP is advisable. We recommend isolation valves be installed on inlet and outlet for maintenance.
Page 14
60 Series Booster Pump Control Valves - Electrical Controls Note: Please refer to Cla-Val. drawing #69548, the Product Data Catalog and the Installation, Operation, & Maintenance Manual shipped with the Control Valve. Start Up Procedure The limit switch (SW2) on the valve should be adjusted After the above adjustments have been made the before the pump control valve is placed in service.
INSTALLATION AND BULLETIN 8320 MAINTENANCE INSTRUCTIONS 3-WAY SOLENOID VALVES, NORMALLY OPEN ASCO NORMALLY CLOSED AND UNIVERSAL CONSTRUCTION FORM NO. V5291R2 SOLENOID TEMPERATURE DESCRIPTION Standard catalog valves are supplied with coils designed for contin- Bulletin 8320 is a small 3-way solenoid operated valve with all three uous duty service.
INSTALLATION AND BULLETIN 8016G MAINTENANCE INSTRUCTIONS OPEN-FLAME, GENERAL PURPOSE, ASCO WATERTIGHT/EXPLOSIONPROOF SOLENOIDS FORM NO. V6583R5 -SERVICE NOTICE- FOR BLACK ENCLOSURE TYPES 7 AND 9 ONLY CAUTION: To prevent fire or explosion, do not install solenoid and/or valve ASCO ® solenoid valves with design change letter "G" in the catalog where ignition temperature is less than 165˚...
Page 19
in-lbs (1,7 - 2,3 Nm). On solenoids with screw terminals, the socket head All solenoid operators and valves should be cleaned periodically. The time between cleaning will vary depending on medium and service conditions. screw holding the terminal block to the solenoid is the grounding screw. In general, if the voltage to the solenoid is correct, sluggish valve operation, Torque the screw to 15 - 20 in-lbs (1,7 - 2,3 Nm).
Page 20
Torque Chart Part Name Torque Value in inch-Pounds Torque Value in Newton-Meters solenoid base sub-assembly 175 ± 25 19.8 ± 2.8 valve bonnet (3/4" bonnet constructions) 90 ± 10 10.2 ± 1.1 bonnet screw (3/8" or 1/2" NPT pipe size) bonnet screw (3/4"...
Page 22
The Cla-Val Model X105L/X105L2 Limit Switch Assembly is a rugged, dependable and positive acting switch assembly actuated by the opening or closing of a Cla-Val control valve on which it is mounted. The single pole, double throw micro switch can be connected either to open or to close an electrical circuit when actuated.
Page 23
1/2-14 N.P.S.M. Thread Fig. 3 (Conduit Connections) 2.44 Valve Size Fig. 2 Valve Size 1 1/4" Thru 8" 1 1/4" Thru 24" X105LOW 3.00 X105LCW X105LOX X105LCX 1.70 2.00 3.13 F i g . 5 Va l v e S i z e 1 0 "...
PARTS LIST X105L Limit Switch Assembly Parts list shown is for sizes 16” and smaller. Please consult factory for parts on sizes 18”, 20”, 24”, 30”, 36”, 42” and 48”. Part Valves Sizes Item Description Number Used On 20441701E Collar W/Set Screw 67578-21B Screw, Machine (2) 67584-23F...
Page 25
Stilling Well Used for any electrical operation which can be performed by The X105L Series Limit Switch Assembly is used on Cla-Val 60 either opening or closing a switch; such as alarm systems, Series Booster Pump Control Valves. Flexible conduit is used for process control, pump control, motor starting or stopping, electrical connections to the solenoid control and the limit switch.
Page 39
INLET SIZE & inquiries concerning valve operation, it is important to CAT NO. EINTRITT STOCK properly identify Cla-Val products already in service CODE ENTREE by including all nameplate data with your inquiry. MFD. BY CLA-VAL ENTRADA Pertinent product data includes valve function, size, NEWPORT BEACH, CALIF, U.S.A.
This product. Cla-Val shall not be liable for any damages or charges for warranty is expressly conditioned on the purchaser’s providing written labor or expense in making repairs or adjustments to the product.
Need help?
Do you have a question about the 60-31 and is the answer not in the manual?