7. In the I/O Configuration, right-click the PowerFlex drive and choose
Properties.
The Module Properties dialog box appears.
8. Click Change.
The Module Definition dialog box appears.
9. In the Input Data column, click Browse (...).
The Parameter Properties dialog box appears.
10. From the pull-down menu, choose the port and parameter for each
DataLink.
11. Click OK.
The DataLinks that handle communication between the drive and
controller, carry over to the Module Definition dialog box.
12. Repeat
step 9
and
These are the required DataLinks to add to your project:
• Predictive Maintenance Status (Port 0, Parameter 469)
• Start Inhibits (Port 0, Parameter 933)
• Drive Status 1 (Port 0, Parameter 935)
• Drive Status 2 (Port 0, Parameter 936)
• Last Fault Code (Port 0, Parameter 951)
• Fault Status A (Port 0, Parameter 952)
• Fault Status B (Port 0, Parameter 953)
Rockwell Automation Publication SYSLIB-RM044D-EN-P - February 2017
step 10
until you have added all DataLinks.
PowerFlex 753 Drive (P_PF753)
29
Need help?
Do you have a question about the PowerFlex 753 and is the answer not in the manual?
Questions and answers
TRYING TO FIND THE PARAMETERS FOR SETTING THE REFERENCE INPUT MIN / MAX AND THE OUTPUT FREQUENCY, MIN / MAX TO THE MOTOR
The parameters for setting the reference input minimum/maximum and the output frequency minimum/maximum for the Rockwell Automation PowerFlex 753 are:
- Cfg_SpeedRefRawMin: Sets the raw minimum reference input.
- Cfg_SpeedRefRawMax: Sets the raw maximum reference input.
- Cfg_SpeedFdbkEUMin: Sets the engineering units minimum for speed feedback.
- Cfg_SpeedFdbkEUMax: Sets the engineering units maximum for speed feedback.
These parameters define the scaling range for both input reference and output feedback.
This answer is automatically generated