16 | ELECTRIC WIRING
8.2 SW2 query instructions
Use application of the SW2 spot check
Table.8-1
No.
Normal display
1
0. --
2
1. --
3
2. --
4
3. --
5
4. --
6
5. --
7
6. --
8
7. --
9
8. --
10
9. --
11
10. --
12
11. --
13
12. --
14
13. --
15
14. --
16
15. --
17
16. --
18
17. --
19
18. --
20
19. --
21
20. --
Discharge pressure corresponding to the saturation temperature
22
21. --
23
22. --
24
23. --
25
24. --
26
25. --
27
26. --
28
27. --
29
28. --
30
29. --
31
30. --
32
31. --
33
32. --
34
33. --
35
34. --
36
35. --
37
36. --
38
37. --
39
38. --
40
39. --
The display contents as followings:
Normal display:
When standby, the above position displays the address of the outdoor unit, and the low position displays the Qty. of indoor units that can communicate with the
outdoor unit. When it is operating, it will display the rotation frequency of the compressor.
Operation mode:
0-Off; 2-Cooling; 3-Heating; 4-Forced cooling; 5-Mixed cooling; 6-Mixed Heating.
Fan speed:
0-stop; 1~15 speed increase sequentially, 15 is the max. fan speed. EXV opening angle: Pulse count=Display value×8;
State of the evaporator or condenser:
0-close/condenser; 1-All evaporator; 2-Left evaporator/right condenser; 3-Left evaporator/close
Night noise control mode:
0-Night noise control mode; 1-silent mode; 2-Super silent mode; 3-No priority
Static pressure mode:
0-static pressure is 0 Mpa; 1-Low static pressure; 2-Medium static pressrue; 3-High static pressure
6 720 862 437 (2016/10)
Display content
Outdoor unit address
Individual Outdoor unit capacity
Modular outdoor unit qty.
Operation mode
Total capacity of outdoor unit
Cooling capacity
Heating capacity
T4 ambient temp. revision of cooling capacity
T4 ambient temp. revision of heating capacity
The outdoor unit actual operating capacity
Speed of fan A
Speed of fan B
T2 average temp.
T2B average temp.
T3 pipe temp. (Left pipe temp.)
T5 pipe temp. (Right pipe temp.)
T4 ambient temp.
Discharge temp. of inverter compressor A
Discharge temp. of inverter compressor B
Modual temp.
The minimum overheating temp. of discharge
Current of inverter compressor A
Current of inverter compressor B
State of the evaporator or condenser
Opening angle of EXV A
Opening angle of EXV B
High pressure
Qty. of indoor units
Qty. of cooling indoor units
Qty. of heating indoor units
Reserve
Night noise control mode
Static pressure mode
DC voltage A
DC voltage B
Reserve
Reserve
Remove fault number of times
Note
0, 1, 2, 3
8, 10, 12, 14, 16
Available for main unit
0, 2, 3, 4, 5, 6
Capacity requirement
(Auxiliary unit only display) capacity for main mode
(Auxiliary unit only display) capacity for main mode
Capacity requirement
0, 1, ······, 14, 15
0, 1, ······, 14, 15
Actual value
Actual value
Actual value
Actual value
Actual value
Actual value
Actual value
Actual value
Actual value+30
Actual value
Actual value
Actual value
0, 1, 2, 3
Actual value÷8
Actual value÷8
Actual value×10
That can communicate with indoor units
Actual value
Actual value
0, 1, 2, 3
0, 1, 2, 3
Actual value÷10
Actual value÷10
Display code 8.8.8
Check end