Installation Instructions
4 Technical Data
Parameter
Functionality
PN IO Conformance classes
Processor
Memory
SPI Interface
Ethernet interface
Ethernet Connection Format
Ethernet Connection medium
Ethernet Cable impedance
Ethernet Transmission speed
Ethernet max. network
segment expansion
Ethernet Function
Power Requirements
Storage Temperature Range
Ambient Temperature Range
Table 3: Technical Data
4.1 Use in hazardous locations
The module is only suitable for use in nonhazardous locations.
PROFINET IO with 100 MBit/s may not be used in hazardous locations.
Value
PROFINET IO Device
LLDP supported
SNMP MIB2 Physical Device
Max. 254 bytes input and 254 bytes output data
16 PROFINET IO slots supported
Min. 1 mS cycle time with RT
Min. 250 uS cycle time with IRT
Acyclic communcation Read/Write Record with max.
256 Bytes
Supported alarm types: Process Alarm, Diagnostic
Alarm, Plug Alarm, Pull Alarm
NRT, RT, IRT
ARM 9 at 150 MHz
32 Mbyte SRAM
4 Mbyte Flash Type Memory
SPI Slave up to 4 MBit/s
2 Port PROFINET IO Realtime switch
8-pin RJ45-female connector
Twisted pair cable with a conductor cross-section of
0,14 mm²..0,22 mm²
100 Ω
100 MBit/s
100 m
100 Base-T(X)
1.7 W Active Mode (Transmitting and Receiving)
-40 °C – +85 °C
0 °C – +50 °C
cRIO PN-Installation-V0.3/12.05.2017
Business Confidential/
Proprietary
Technical Data
5