CAUTION: Leave the shield drain wire insulated and disconnected at the detector. You will
connect the opposite end of the cable's drain wire at the controller.
8.
Secure the junction box cover to the junction box.
9.
Route the cable or wires in conduit leading from the detector through one of the
conduit hubs at the controller. Use appropriate conduit fittings.
10. Connect the wires to the appropriate controller detector terminal strip. See the
controller operator's manual for wiring instructions.
CAUTION: Do not route power and detector wiring through the same conduit hub. The power
cable may disrupt the transmission of the detector signal to the controller.
Figure 2: Wiring the Oxygen Detector to a Controller
(-)
Controller Oxygen
Green
Detector Terminals
(+)
White
J-Box
Terminal Strip
White
Detector Wires
Green
Oxygen Detector
65-2502RK/65-2510RK Oxygen Detector• 7