Summary of Contents for Siemens 6ES7134-4FB51-0AB0
Page 1
Preface SIMATIC ET 200S distributed I/O 2AI U HS analog electronic module (6ES7134-4FB51-0AB0) ______________ Properties ______________ Parameters SIMATIC ______________ Diagnostics ET 200S distributed I/O 2AI U HS analog electronic module ______________ Analog value representation (6ES7134-4FB51-0AB0) ______________ Connecting Manual 04/2007 A5E01076015-01...
Page 2
Trademarks All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Additional support If you have any questions relating to the products described in these operating instructions, and do not find the answers in this document, please contact your local Siemens representative. http://www.siemens.com/automation/partner...
Page 4
● The bulletin board, a worldwide knowledge exchange for users and experts. ● Your local contact for Automation & Drives in our contact database. ● Information about on-site services, repairs, spare parts. Lots more can be found on our "Services" pages. 2AI U HS analog electronic module (6ES7134-4FB51-0AB0) Manual, 04/2007, A5E01076015-01...
Table of contents Preface ..............................3 Properties ..............................7 2AI U HS analog electronic module (6ES7134-4FB51-0AB0)............7 Parameters .............................. 11 Parameters...........................11 Parameter description........................12 Diagnostics .............................. 13 Diagnostics using LED display.....................13 Error types............................14 Interrupts ............................14 Analog value representation ........................15 Introduction ..........................15 Analog value representation for measuring range with SIMATIC S7 ..........15...
Page 6
Table of contents 2AI U HS analog electronic module (6ES7134-4FB51-0AB0) Manual, 04/2007, A5E01076015-01...
Properties 2AI U HS analog electronic module (6ES7134-4FB51-0AB0) Properties ● 2 inputs for measuring voltage ● Input ranges: ± 10 V, resolution 13 bits + sign ± 5 V, resolution 13 bits + sign ± 2.5 V, resolution 13 bits + sign 1 V to 5 V, resolution 13 bits ●...
Page 8
Properties 1.1 2AI U HS analog electronic module (6ES7134-4FB51-0AB0) Usable terminal modules Usable terminal modules for 2AI U HS (6ES7134-4FB51-0AB0) TM-E15C26-A1 TM-E15C24-A1 TM-E15C24-01 TM-E15C23-01 (6ES7193-4CA50- (6ES7193-4CA30- (6ES7193-4CB30- (6ES7193-4CB10- Spring terminal 0AA0) 0AA0) 0AA0) 0AA0) TM-E15S26-A1 TM-E15S24-A1 TM-E15S24-01 TM-E15S23-01 (6ES7193-4CA40- (6ES7193-4CA20-...
Page 9
Properties 1.1 2AI U HS analog electronic module (6ES7134-4FB51-0AB0) 2AI U HS technical specifications (6ES7134-4FB51-0AB0) Dimensions and weight Width (mm) Weight Approx. 40 g Module-specific data Supports isochronous operation Number of inputs Cable length Shielded • Max. 200 m Parameter length...
Page 10
Properties 1.1 2AI U HS analog electronic module (6ES7134-4FB51-0AB0) Suppression of interference, limits of error Common mode interference (U ) < 100 VSS) > 70 dB • Crosstalk between the inputs > 50 dB Operational limit ± 0,3 % (in the entire temperature range, with reference to the input range) Basic error limit (operational limit at 25°C with...
Low limit • Channel overrange Note If you deactivate a HS module channel, you do not gain any advantages in terms of speed, due to the measuring procedure used. 2AI U HS analog electronic module (6ES7134-4FB51-0AB0) Manual, 04/2007, A5E01076015-01...
The following diagrams show the step response with the various smoothing factors depending on the number of subassembly cycles. Figure 2-1 Smoothing for 2AI U HS (6ES7134-4FB51-0AB0/ 6ES7134-4FB50-0AB0) 2AI U HS analog electronic module (6ES7134-4FB51-0AB0) Manual, 04/2007, A5E01076015-01...
Event (LED) Cause Remedy No configuration or incorrect Check the parameter module plugged in. No load assignment. Check the load voltage.present There is a voltage. Evaluate the diagnostic message. diagnostics. 2AI U HS analog electronic module (6ES7134-4FB51-0AB0) Manual, 04/2007, A5E01076015-01...
Correct the module/actuator value limit fallen underrange. tuning. below Interrupts Hardware interrupt of analog input modules Figure 3-1 Structure as of Byte x+4 and Byte x+5 for hardware interrupt (analog input) 2AI U HS analog electronic module (6ES7134-4FB51-0AB0) Manual, 04/2007, A5E01076015-01...
Analog value Bit number Significance of the bits Sign The sign (S) of the analog value is always in bit number 15: ● "0" → + ● "1" → – 2AI U HS analog electronic module (6ES7134-4FB51-0AB0) Manual, 04/2007, A5E01076015-01...
L+ missing 7FFF POWER ON STOP L+ present Process value L+ missing 7FFF POWER OFF L+ present L+ missing 2AI U HS analog electronic module (6ES7134-4FB51-0AB0) Manual, 04/2007, A5E01076015-01...
End of the overshoot range +1 plus overflow bit Underflow 8000 End of the undershoot range -1 plus overflow bit Prior to parameter assignment, or 7FFF 7FFF incorrect parameter assignment 2AI U HS analog electronic module (6ES7134-4FB51-0AB0) Manual, 04/2007, A5E01076015-01...
To ensure that the permitted value is not exceeded, you must take different steps depending on the whether the sensors are isolated or non-isolated. The steps you have to take are described in this chapter. 2AI U HS analog electronic module (6ES7134-4FB51-0AB0) Manual, 04/2007, A5E01076015-01...
Page 20
The following figure illustrates the connection of isolated measuring sensors to the floating analog input modules. ① Logic ② Backplane bus ③ Ground bus ④ Central grounding point ⑤ Isolated measuring sensors 2AI U HS analog electronic module (6ES7134-4FB51-0AB0) Manual, 04/2007, A5E01076015-01...
Page 21
When a sensor is connected or a wire break is repaired during a measuring operation, false measurements and false diagnostics can occur on both inputs if the permissible input current is exceeded. 2AI U HS analog electronic module (6ES7134-4FB51-0AB0) Manual, 04/2007, A5E01076015-01...
● Use shielded wires to the sensors and actuators. ● Lay out the wire shields on the shield connection. ● Connect the shield connection with low impedance to the ground bus. 2AI U HS analog electronic module (6ES7134-4FB51-0AB0) Manual, 04/2007, A5E01076015-01...
Shield contact, 22 Connection of measuring sensors to analog inputs, 19 Smoothing, 12 Disposal, 3 Technical Support, 4 Training center, 4 Internet Service & Support, 4 Isolated measuring sensors, 20 2AI U HS analog electronic module (6ES7134-4FB51-0AB0) Manual, 04/2007, A5E01076015-01...
Page 24
Index 2AI U HS analog electronic module (6ES7134-4FB51-0AB0) Manual, 04/2007, A5E01076015-01...
Need help?
Do you have a question about the 6ES7134-4FB51-0AB0 and is the answer not in the manual?
Questions and answers