WES
Troubleshooting Guide
3
LED Codes
Green LED
Active units with no faults will flash their green LEDs once every 4 seconds
to indicate that the unit is operational.
Amber LED
Each WES
unit monitors itself for a number of faults. These are indicated
3
via the amber LED, which will flash in grouped patterns with longer than
usual gaps in between them.
Units displaying one of these patterns require further investigation and
should not be relied upon as part of the fire alarm and detection system
until the fault has been corrected. Use the chart below to determine the
nature of the issue:
Base Station Warning Codes
The Base Station will alert you to various system faults using the codes below:
Warning Code
Warning
MED
Medical Alert
BAT
Low Battery
DET
Detector Tamper
EXT
External Tamper
FLT
Flat Battery
INT
Internal Tamper
LAT
Latched
REM
Removed
SIG
Low Signal
TST
System Test
NEW
Unexpected Unit
GON
Unit Missing
Group Flash 1 - Low Battery
Group Flash 2 - Low signal
Group Flash 3 - Unpaired
Group Flash 4 - Tamper
Group Flash 5 - Re-arm or Unit latched
Red LED
If a detector has raised the alarm, its red LED indicator will flash during a fire
alarm.
It is recommended that the fire system is tested weekly or whenever a
significant change has been made to the installation or the building under
construction. WES
test the radio link between units without activating an audible fire alarm.
You can therefore ensure each unit in the system has a robust radio link with
sufficient capacity to allow for environmental fluctuations without disturbing
the site.
Description
Medical assistance required at Unit NNN
Unit NNN has a low battery
Unit NNN has had detector head removed
Unit NNN has been removed from wall/ceiling
Unit NNN has turned off, its battery is flat
Unit NNN has been opened
Call point button on unit NNN is still depressed
Unit NNN has been deactivated and removed
Unit NNN has a low radio signal
Unit NNN initiated a System test
Unit NNN added since last system poll
Unit NNN removed since last system poll
Taken from WES
is equipped with a system test function that allows you to
3
Self-Clearing
No
No
Yes
Yes
No
No
Yes
No
Yes
Yes
No
No
Installation and Operations Manual V1.4 Ramtech Electronics 2018
3
SMS Setting
8
5
3
4
5
2
10
9
6
7
Via WES App
Via WES App
Need help?
Do you have a question about the WES3 and is the answer not in the manual?
Questions and answers