2 channels electronic
time switch weekly cycle
User instructions
EG203E
Major characteristics
•
Product delivered with current time and date set.
•
Automatic change of winter / summer time
.
Programming key
.
•
- for permanent overrides,
- for program copy or save.
Programming for day or group of days.
•
•
56 program steps On, Off.
•
Permanent overrides On or Off (
permanent light on).
•
Temporary overrides On or Off (
flashing).
•
Holiday mode
: overrides On or Off between two dates.
Simulation of presence
.
•
•
Display bar graph of daily profile for both channels.
•
Keyboard locking possible
.
Programmable with power off.
•
•
Back lit screen.
Keys:
menu
: selection of operating mode
auto : mode of running according to the pro-
gram selected.
prog : new for programming mode.
prog : modif to modify an existing
program.
: checking of the program.
: modification of time, date and
selection of the winter / summer time
+
change mode
2
A
B
: holidays.
+and-
: navigation or setting of values.
1
A
-: in auto, mode, selection of overrides,
ok
menu
B
waivers or random operation
ok
: to validate flashing information
4
3
on display.
: to return to the previous step.
You may return into auto mode at any moment
EG005
using menu.
If no action is taken for 1 min, the switch
returns into auto mode.
Reset:
• Program reset:
the program may be completely cleared by simultaneously pressing the 3 following keys:
menu, ok,
. The time and the date will be kept.
• Total:
pressing simultaneously the -, +, ok, menu, keys lets you clear the entire contents of the
product.
Following a total reset it is necessary to reset the time and day of the device.
2
Hager SAS - 132 bld d'Europe - BP 78 - 67 212 Obernai cedex (FRANCE) - Tél. +333 88 49 50 50 - www.hagergroup.net
Technical specifications
Electrical characteristics
• Supply voltage:
230 V AC ± 15%
• Frequency:
50/60 Hz
• Power consumption:
max. 6 VA à 50 Hz
• Output: 2 changeover volt free contacts
• Maximum load:
AC1
μ16A 250 V~
Cos φ = 0,6
μ10A 250 V~
Incandescent lighting
Halogen lighting 230 V
Compensated fluorescent tubes //
(max. 45 μF)
Non compensated fluorescent tubes,
compensated in series
Compact fluorescent lamps
• Minimum current.
AC1
100 mA 250 V~
• Galvanic insulation between power supply and
output < 4 kV
Functional characteristics
• Programming capacity: 56 steps
• Minimum time between 2 steps: 1 minute
• Running accuracy: ± 1,5 sec / 24h
• Operating reserve: lithium battery provides
5 years of backup.
• The product is set into standby state
(display switched-off) after 1 minute with
power off.
It switches back into auto mode as soon as
power is back or when pressing any key.
• Protection degree: IP 20
Environment
• Operating temperature:
-5 °C to +45 °C
• Storage temperature:
-20 °C to +70 °C
Connection
• Flexible capacity:
1 to 6 mm
• Rigid capacity:
1,5 to 10 mm
.
Connection diagram:
L
N
1 3 5 7
2 4 6 8
Programming: prog new
Programming may be done for each day or
for a group of days. In this case instructions are
common to several days.
Days: 1 = Monday, 2 = Tuesday, 3 = Wednesday...
7 = Sunday.
prog
new
ok
On
0
6
12
18
24
1. Select the prog mode using menu, then ok.
2. Select the channel (A or B) using
+
or -, then ok.
The number of remaining program steps appears
2300 W
for a short time.
2300 W
3. Choose the day(s) using
+
or -. Validate with ok.
400 W
4. ok flashes. Use
ok
to validate the group of days.
-
or
makes it possible to reset the group of
1000 W
days if necessary
500 W
5. Using
+
or -, select the state of the instruction:
On, Off or
. Press
ok
to validate the state.
6. Enter the time of switch-on using
+
or -.
Validate with ok.
7. Enter minutes with
+
or -. Validate with ok.
8. For On
, set the duration (seconds, then
minutes) in the same way as for the switch-on
schedule.
Program the other instructions of the group of
days by repeating operations 3 to 8.
The day or the group of days may be modified at
the during step 3 by pressing the
+
-
or
.
,
At the end of programming return to auto mode
using the
menu
button.
To set the program of the other channel, return to prog
new mode and proceed according to steps 2 to 8.
In this mode it is also possible to add an instruction to
the program set up.
Proceed as described above.
Display
To check the daily profile set up without the risk of
modification or deletion:
Select the mode
using
menu
and press ok.
Select the channel (A or B) using
+
or
-
and
ok.
The first step of Monday is displayed as well as
2
the daily profile.
2
Two options available for display :
1. Pressing repeatedly
+
or -: lets you shift days.
In this case only the first daily step is displayed
as well as the daily profile.
2. Pressing ok: all steps of each day appear one
after the other.
Modification or clearing of a program step :
prog modif
Select the prog mode with
menu
and press ok.
Select the channel (A or B) using
+
or
-
and
ok.
Select the modif mode with
+
or -.
Validate with ok.
The number of remaining program steps appears
for a short time.
The first step of the first day or group of days
appears.
Repeatedly pressing the
ok
key displays all
programmed steps one at a time.
Any flashing field (state, hour, minutes) may be
modified using
+
or -, then validated with ok.
When the cursor is positioned on
ok
located
behind the group of days, you may display
successively the days or the groups of days and
switch directly to the one that has to be modified
using
+
or -.
To remove a program step :
select the state of the channel (One, Off or
),
press simultaneously
+
and -.
Clear appears on the screen. Validate with ok.
Key
Holidays
As soon as the key appears on the switch
Allows you to override the output, On or Off
appear on the screen.
for a given period.
Once done, this override will be removed
Two types of operation:
and will not be carried over to the following
year.
A. Permanent override:
Select the mode
Insert the key into the switch.
With
+
or -, select the state of override: On or
After 10 seconds the program contained in the
Off,
ok
to validate.
key will be executed without clearing the program
Enter the day then the month of the starting
contained in the time switch.
period (date 1) using
As soon as the key is removed the program of
Enter in the same way the day and the month
the time switch is again valid.
of the ending period (date 2).
In auto mode,
B. Copy (load) / Save (save):
a period of holidays was programmed.
The key makes it possible to save a program
becomes permanent during the period.
contained in the time switch.
It is also possible to copy the contents of
The override will be effective at 0:00 of the
the key into the clock.
1st date until 23:59 from the 2nd date.
1. Insert the key and wait for 2 sec.
If date 1 is set before the day of
2. Using menu select the mode:
programming, the period of holidays is
save to save a program contained in the time
valid for the following year.
switch,
To clear a period of holidays return to the
load to load the program of the key into the
mode, press simultaneously the
time switch,
Clear appears. Confirm with ok.
to check the program contained in the key.
3. Validate the selection with ok.
4. For save and load reconfirm with ok.
Override -
The following error messages may appear
Random operation
on the screen:
no prog: the key is empty, it does not contain any
Pressing repeatedly
program.
If the state of the output is On:
Error: the key is that of a one-channel switch.
1
st
press:
In these two cases:
Only the save save is possible.
•
The error message remains on display as long as
•
2
nd
press:
the key is present, but in this case the program of
the time switch is executed.
3
rd
press:
Setting time and day
4
th
press:
Winter / summer time change
Select the mode
with
menu
then ok.
Modify the day, month, year, the hour and the
minutes using
+
or
-
and ok.
The time switch next suggests the winter / summer
5
th
pressure: return to the automatic mode.
time changes
.
Select the type of change desired using
+
or
-
.
Validate with ok.
Locking
The type of change depends on the geographical
To prevent all undesirable actions, the
zone
keyboard of the time switch may be locked
Types available :
using a key EG004.
Unlocking is done in the same way.
Type Start of time
Start of time
Zone
change Summer change Winter
of application
Euro Last Sunday
Last Sunday
European Union
of March
of October
*
USA First Sunday
Last Sunday
North America
of April
of October
GB
Last Sunday
Fourth Sunday
Only for the
of March
of October
United Kingdom
AUS Last Sunday
Last Sunday
Australia
of October
of March
USER Date freely
Date freely
programmed
programmed
No
No
No
change
change
* type according defect
The change always takes place between 2:00 and
3:00 a.m.
When the USER type is selected:
Waranty
1. Enter the day then the month of the date of change
of the summer time (+ 1hour) with
+
or
-
and ok.
A warranty period of 24 months is offered on hager products,
from date of manufacture, relating to any material or manufac-
2. Enter the day then the month of the date of change
turing defect. If any product is found to be defective it must
of the winter time (- 1hour) with
+
or
-
and ok.
be returned via the installer and supplier (wholesaler).
The warranty is withdrawn if :
The time switch will check which days of which
- after inspection by hager quality control dept the device is
found to have been installed in a manner which is contrary to
weeks correspond to these dates and will apply
IEE wiring regulations and accepted practice within the indus-
changes to the same periods for the following years
try at the time of installation.
independently of the date.
- the procedure for the return of goods has not been followed.
Explanation of defect must be included when returning goods.
using
menu
then ok.
+
or
-
then ok.
flashes to indicate that
+
and -keys.
-.
temporary waiver. Off and
flash. The next program step will
let you return to the automatic
mode.
permanent override. On and
are permanent. This override must
be cancelled manually.
permanent override. Off and
are permanent. This override must
be cancelled manually.
random operation. Simulation of
presence,
as well as the state
of the output are displayed. Must
be cancelled manually.
In this case the steps of the
program are shifted randomly
within a range of ± 59 min.
GB
6E 6321.c
Need help?
Do you have a question about the EG203E and is the answer not in the manual?
Questions and answers