CI Safety Relay
(Cat. No. 440R-S13R2)
Application and Wiring Examples
The application and wiring examples in this chapter show you how to put the
inputs and outputs together to create an operating safety system. These circuit
diagrams are examples; many features are interchangeable between relays.
Publication
SAFETY-WD001
diagrams.
In
Figure
42, the CI safety relay is monitoring a device (an E-stop push button)
with mechanically operated contacts. The CI safety relay is configured for
monitored manual (MM) reset. The output turns on if the E-stop is released
and the reset push button is pressed and released between 0.25...3 seconds. The
CI safety relay monitors the status of the two output contactors, K1 and K2. If
either fails to close their N.C. contacts, the CI safety relay does not reset. An
auxiliary signal, terminals 41/42, is sent to the PLC when the E-stop is pressed.
Figure 42 - Mechanical Contacts with Monitored Manual Reset
24V DC
K1
K2
Reset
S11
S21
S34 A1 13
0
RESET
AM
MM
CI
440R-S13R2
S12
S22
A2
L11
24V Com
Rockwell Automation Publication 440R-UM013E-EN-P - March 2017
provides additional application and wiring
23
33 41
14
24
34 42
To PLC
K1 K2
9
Chapter
53