Pressure sensor SPAN
Operating instructions
Original: de
Pressure sensor SPAN
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
Product description
The operating instructions describe the entire function range. The function range is
limited, depending on the product variant.
Note
You can find detailed specifications for the product, the device description file
(IODD) with a description of the IO-Link parameters and the declaration of con
formity at: è www.festo.com/sp.
1.1 Overview
1
6
5
4
1
Display
2
Electrical connection
3
Pneumatic connection
Fig. 1
Representation of other variants can deviate from this
1.2 Characteristics
Characteristic
Value
Type
SPAN
Pressure
-B2, -B11, -P025, -P05, -P1, -P2,
measuring range
-P6, -P10, -P12, -P16, -V025,
-V05, -V1
Supply port
R
Pneumatic port
-G18, -R18, N18, -M5,
-Q4,
Thread type
M
F
Electrical
-PNLK
output 1
-PN
Electrical
-PNVBA
output 2
-PN
Electrical
-L1
connection
Certificate
+T
Fig. 2
Festo AG & Co. KG
Postfach
73726 Esslingen
Germany
+49 711 347-0
www.festo.com
8049275
1607
[8049280]
English
4
B-key
5
Edit button
6
A-key
Description
Pressure sensor
è Technical data
Relative pressure
Thread Gx, Rx, NPTx, M5
Push-in connector 4 mm
None
Male thread
Female thread
Switching output PNP / NPN / IO-Link
PNP / NPN
PNP / NPN / 0...10 V / 1...5 V / 4...20 mA
PNP / NPN
Plug connector, design L1
Without
With inspection report
2
Safety
Intended use
The pressure sensor SPAN is intended for monitoring pressure of compressed air
and inert gases in the piping.
General safety information
Only use the product in its original status, without any unauthorised modifications.
Only use the product if it is in an excellent technical status.
The product is intended for use in industrial environments. Measures may need
to be implemented in residential areas for radio interference suppression.
Take into consideration the ambient conditions at the location of use.
Operate the product only with compressed air of the specified air quality class
(è Technical data).
Observe the specifications on the rating plate.
Comply with all applicable national and international regulations.
Disposal
Observe the local specifications for environmentally friendly disposal.
3
Function and application
The sensor converts pneumatic pressure values (relative pressure) into electrical
signals, which can be used for control or regulating functions. Measurements are
carried out using a piezoresistive sensor element with a following electronic evalu
ation unit. Interfacing to the higher-level system is provided by 1 or 2 switching
outputs, an optional analogue output and an optional IO-Link interface.
The switching outputs can be configured for monitoring of a threshold value,
a pressure range or a differential pressure. The outputs can be set as PNP or NPN
and normally open (NO) or normally closed (NC). Via the IO-Link interface, process
values can be read out and parameters changed and transmitted to additional
devices.
3.1 Operating statuses
Operating status
RUN mode
SHOW mode
EDIT mode
TEACH mode
2
Fig. 3
3.2 Switching functions
Threshold value comparator for monitoring of a pressure threshold
3
Function
Switching function:
– 1 switching point (SP)
TEACH mode:
– 2 teach-in points (TP1, TP2)
– SP = ½ (TP1+TP2)
Fig. 4
Window comparator for monitoring of a pressure range
Function
Switching function:
– 2 Switching points
(SP.Lo, SP.Hi)
1)
TEACH mode
:
– 2 teach-in points (TP1, TP2)
– TP1 = SP.Lo, TP2 = SP.Hi
1) SP.Lo = smaller pressure/vacuum value, SP.Hi = larger pressure/vacuum value, dependent on the
Teach sequence
Fig. 5
Auto difference monitoring d_|¯|_
This funciton permits monitoring of a pressure value for constancy.
If the applied pressure is constant in the range between [SP.Lo] and [SP.Hi], the refer
ence pressure PRef is automatically determined. The result is a switching operation at
the output. The signal change signals the start of pressure monitoring.
If the pressure remains in the monitoring range [d.SP] around PRef, the pressure is
stable. When the monitoring range is left (e.g. caused by a leakage in the system),
the output switches back.
Function
– Basic status after the operating voltage is switched on
– Display of the current measured value
– Display of the current settings
– Setting or modification of parameters
– Acceptance of the current measured value to determine switching
points
NO (normally open)
Out
HY
1
0
p
SP
TP1
TP2
NO (normally open)
Out
HY
HY
1
0
p
TP1=SP.Lo TP2=SP.Hi
NC (normally closed)
Out
HY
1
0
p
SP
TP1
TP2
NC (normally closed)
Out
HY
HY
1
0
p
TP1=SP.Lo TP2=SP.Hi