Elmdene GEN2-08 Series Instruction Sheet page 3

Switch mode power supply
Table of Contents

Advertisement

S
O
IGNALLING
UTPUTS
Rating:
EPS Fault:
GEN Fault:
Tamper:
C
ONNECTIONS
O/P +, -
EPS Fault:
GEN Fault:
BATT +, -
I
NSTALLATION AND
This unit is only suitable for installation as permanently connected equipment. This PSU is NOT SUITABLE for
external installation. EQUIPMENT MUST BE EARTHED. Before installation, ensure that external disconnect
device is OFF. The PSU should be installed according to all relevant safety regulations applicable to the
application.
FUSED
SPUR
3A min
Mains Input cable rated:
3A, 300Vac minimum
Technical Support: +44(0)23 9269 6638 (option 3)
0.10A @ 60Vdc 16Ω solid state relay contacts, volt free.
Open if Loss of mains for >8s
Open if Battery terminal voltage < 11.5v (when operating in standby with no
mains present), battery not present or Output and/or battery fuse blown
0.5A @ 30Vdc volt free contact. Open when lid is open.
Connection to equipment to be powered (Observe polarity)
Relay output for mains fail. Open if loss of mains.
Relay output for General Fault. Open in fault condition
Connection to standby battery. Use cables provided (Observe polarity)
C
OMMISSIONING
Min 10cm clearance
L E N
Fig 1 Mounting of Power Supply
PAK200545_03B May 2016
Load output cable:
Current rating to
match maximum load
Fasten cables
using cable tie
©2016 ELMDENE INTERNATIONAL LTD