Inputs / outputs ....................................11 Power failure ...................................... 11 Diagnose ......................................12 Status request ....................................13 Configuration of the SMS Relay with the „FAST SMS Set™“ Software ..................13 General ......................................13 Create connection ....................................13 Edit telephone book ................................... 14 6.3.1...
With the password option, unauthorized remote access to the SMS Relay by a third party is avoided. The SMS relay sends out a message at regular intervals as for example in case of a power loss, whereby the SMS relay is able to send a last warning message before it shuts down. If the power is restored, the CMS-10 will announce its operational status again with a new message.
Page 4
Comat AG cannot accept any responsibility for the application and use of the SMS relay. In particular Comat AG cannot guarantee the connection security with the mobile network.
Comat SMS Relay Short instructions 1. The SMS Relay must be separated from the power supply. 2. Place the SIM card into the card holder 3. Connect the RS232 interface of your PC or Notebook with the programming interface of the SMS Relay. Use the programming cable.
4. Connect the power supply to the SMS Relay. Obey connection diagram 5. As soon as the SMS Relay is ready (after approx. 100 sec), Status-LED & GSM- LED are flashing regularly in a cycle of 1 second. Start the programming software FAST SMS Set™...
240VAC must be avoided on the device. The SMS relay is isolation protected and does not need grounding. The SMS relay must be connected according to the following schematic:...
All relays outputs are reset to the home position if the button is pushed for minimum 15 secs.. That means for the first change over contact: 12-14 open / 12-13 closed. The characteristic of all change over contacts is the same. TEST-BUTTON RESET-Button Test and Reset Buttons Operating instructions SMS Relay ba_smsrelay_1010_e...
To avoid this, change the screen resolution of your computer system. Select “Start” – “System controls” – “Display” and then the register “Settings”. Please set the screen resolution to 1024 x 768 pixels in minimum. Operating instructions SMS Relay ba_smsrelay_1010_e...
(→ chap.5). Run Mode LED status display The SMS relay has two LEDs, the GSM LED und the status LED. Both LEDs can be seen from the outside and are located below the cover. The following statuses are indicated: 5.1.1...
(depending on the set mode) before the device shuts down. The device restarts automatically after the power supply is restored. The registration of the SMS Relay in the GSM network is restored and the same status of the outputs is initiated as before the power failure (Memory function).
The SMS Relay together with the programming software „FAST SMS Set™“ allows the display of the actual signal strength. For that function, the SMS Relay has to be connected to a PC / Notebook with the programming cable. To get to the diagnose function, select Option –...
USB slots. Connect power supply to the SMS Relay As soon as the Status-LED of the SMS Relay flushes in a cycle off 1 second, the software can be started. Choose a saved file or create a new one.
Phonebook entry REMARK Not all special characters can be used for SMS messages. The characters are recognized by the programming software and displayed in an error window. Subsequently, the respective characters have to be erased. Operating instructions SMS Relay ba_smsrelay_1010_e...
SIM manual. In order to do this, the SIM card must be removed from the SMS Relay and inserted into a mobile phone. Now the card can be unblocked according to the details of the network providers.
Remote access integrated. Input signal 0-10V. CMS-10ADF/DC12-48V CMS-10ACDF analogue This type allows using 4 inputs as analogue 0-10V or digital inputs. Additional this device has 2 current inputs 4- 20mA (I5 and I6). Remote access integrated. CMS-10ACDF/DC12-48V Operating instructions SMS Relay ba_smsrelay_1010_e...
6.4.4 SMS Relay identification The SMS Relay can be described with a name or a description. All messages sent from this SMS Relay receive the name as entered in the field “SMS Relay description”. The SMS Relay identification can be deactivated so that the messages can be sent without this identification (this function is only available in devices with firmware version FW >...
(Firmware Version 2.8 and Software 1.3.0) Message at the start A message for each start up (switching on / return of power) of the SMS relay is sent (According to the phone number assigned to the event). The message contents can be edited.
Trailing information Input configuration 6.6.1 General The SMS Relay has 6 inputs. Depending of the device type, all this inputs can be used as digital inputs only (CMS-10F/AC110-240V and CMS-10F/DC12-48V) or as digital / analogue inputs (CMS-10ADF/DC12-48V and CMS-10ACDF/DC12-48V). 6.6.2...
If the confirmation code word is not activated, the phone number identification is carried out as a security check and it is sufficient to send an empty SMS message to the SMS Relay. REMARK The display of special characters in the GSM network can cause problems.
If there is an input signal, the respective message transmission can be time delayed, i.e. the SMS relay only sends the pre-defined message after the preset time has elapsed and if the signal has remained ON constantly during that time. In other words, the input signal is ignored during the set delay time.
The top and the bottom thresholds have to be defined to allow sending of messages. Description of the range The value between the max and the min value is the range R. This range has an important function in the designation of the thresholds. Operating instructions SMS Relay ba_smsrelay_1010_e...
Upper Limit uL = Max. value – B x 0.05 = 600m3/h – (450m3/h x 0.05) = 577.3m3/h Lower Limilt iL = Min value + B x 0.005^= 150m3/h + (450m3/h x 0.05) = 172.5m3/h Operating instructions SMS Relay ba_smsrelay_1010_e...
Page 24
On this example the actual measured value is below the set Lower Level The system is not in its normal status. The value is below the lower limit. A message is sent (if this is activated by ). The message text can be freely configured. Operating instructions SMS Relay ba_smsrelay_1010_e...
Page 25
A certain difference between the actual value and the last sent value is exceeded The SMS Relay monitors the analogue value. A message is sent if the difference exceeds a certain value (if this is activated by ). The message text can be freely configured. The maximal value for this is 50%.
If the confirmation code word is not activated, the phone number identification is carried out as a security check and it is sufficient to send an empty SMS message to the SMS Relay. REMARK The display of special characters in the GSM network can cause problems.
6.7.1 General The SMS Relay has 4 relay outputs (change over contacts 10A, 250V). The outputs can be controlled by a message i.e. they can be switched ON and OFF. Each output can be activated individually. The message text can be edited individually. However, the device only accepts the exact expression i.e.
FAST SMS Set (from version 3.0) and a GSM modem (DATA call to the SMS Relay). After the remote connection is established, all the modifications can be done in the usual environment of FAST SMS Set The first start-up shall be executed as described in chapter “1.1 Short description SMS Relay CMS Comat...
Remote Access can only be enabled again over a conventional serial cable connection (RS232) with a PC/notebook. Warning „disable remote access‟ Operating instructions SMS Relay ba_smsrelay_1010_e...
Comat SMS Relay Connection establishment A SMS Relay with activated remote access and a GSM modem are necessary to establish a connection for communication. The GSM modem is connected to a PC or a notebook (the SMS Relay has a GSM modem already integrated).
Page 31
Comat SMS Relay The connection to the remote SMS Relay is now built up and established. In the menu list and in the menu Option, the remote access button is shown active. Remote access button „activated“ If remote access is selected, FAST SMS Set starts to establish a data connection via the modem.
I/O states display window. This takes some time and depends on the scanning cycle. REMARK The data transfer over GSM (remote access) takes more time as the direct access over the serial interface. Read I/O states Operating instructions SMS Relay ba_smsrelay_1010_e...
10V (20mA) corresponds to 100m , the measuring bar will show with half of the maximal length (corresponds to 50m ). Other values will be displayed proportional to the measuring range. Operating instructions SMS Relay ba_smsrelay_1010_e...
Language selection General Several languages of the SMS Relay configuration software “Fast SMS Set”™ are available. The languages can be selected from a library. It is not necessary to restart the program after selecting another language. Select the language menu to access the available configuration languages and click onto the required language from the library.
Analogue: 0…10V analogue signal, 10 Bit A/D-converter (LSB: 12.5 mV) 2 current inputs (I5 and I6), for each only analog Analogue: 4…20mA analogue signal, 10 Bit A/D-converter (LSB: 20 µA) Outputs 4x CO contacts Provider (Phone / Network) User selectable (depending on SIM card) Operating instructions SMS Relay ba_smsrelay_1010_e...
CMS-10ADFKIT/DC12-48V Complete installation kit for SMS Relay DC 12-48V with 6 digital and/or analogue inputs CMS-10ACDFKIT/DC12-48V Complete installation kit for SMS Relay DC 12-48V with 2 analog current inputs and 4 analog voltage inputs Accessories CMS-RS232 SMS Relay programming cable RS232 USB→RS232 interface converter (incl.
Comat SMS Relay Overview of your devices and phone numbers Devices SMS Relay Device type N° Password Phone number description Modem SMS Relay Device type N° Password Phone number description Operating instructions SMS Relay ba_smsrelay_1010_e...