Access to the fan 2.7.1 Replacing the fan 3 Installation Transport and Unpacking 3.1.1 Transport 3.1.2 Unpacking Installation of the PC in the control cabinet 3.2.1 Flexible mounting mechanism 3.2.2 Preparation of the control cabinet Power Supply of the Industrial PC C6030-0060...
Page 4
5 Troubleshooting 6 Assembly dimensions 7 Technical Data 8 Appendix Beckhoff Support and Service 8.1.1 Beckhoff branches and partner companies 8.1.2 Beckhoff company headquarters Approvals for USA and Canada FCC Approvals for the United States of America FCC Approval for Canada...
Modifications to hardware or software configurations other than those described in the documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG. 1.1.6 Delivery conditions In addition, the general delivery conditions of the company Beckhoff Automation GmbH & Co. KG apply. C6030-0060...
CAUTION Hazard to devices and environment If you do not adhere the notice adjoining this symbol, there is obvious hazard to materials and environment. Attention Note or pointer This symbol indicates information that contributes to better understanding. Note C6030-0060...
• if connecting cables internal to the PC are removed or inserted during operation. • if plug-in cards are removed or inserted when the PC is switched on. C6030-0060...
1.4.3 Operator requirements Anyone who uses the Industrial PC must have read these operating instructions and must be familiar with all the functions of the software installed on the Industrial PC to which he has access. C6030-0060...
Both the new ultra-compact motherboard and the housing, which is made of die-cast zinc and aluminium, have been newly developed in line with the high standards Beckhoff is known for, such as industrial suitability, manufacturing Made in Germany, reliability and premium look-and-feel. With integrated multi- core support, the C6030 can be used simultaneously for high-performance automation, visualisation and communication.
Page 10
Industrial PC generation in the same way as the predecessor TwinCAT 2 with its single-core support. The C6030-0060 Industrial PC revolutionises the already extremely successful C69xx series Industrial PCs for control cabinet installation and adds a more powerful new version to the ultra-compact C6015 Industrial The Industrial PC offers the following benefits: •...
Product Description 2.2 Appropriate Use The C6030-0060 is a Industrial PC for space-saving control cabinet installation. Risk of explosion! The Industrial PC must not be used where there is a risk of explosion. Danger 2.3 Access to the connectors The connectors of the Industrial PC are located at the front side of the housing.
USB3.0 standard is supported. 2.4.4 DisplayPort (X110, X111) The DisplayPorts (X110, X111) are used for transferring the video signal. 2.4.5 Protective Earthing (PE) protective earthing (PE) The low-resistance protective earthing of the Industrial PC is established via the screw connection (PE). C6030-0060...
Any connected devices with its own power supply must have the same potential for “PE” and “GND” like the Panel PC system (no potential difference). 2.5 Status LEDs The Status LEDs are located at the front side of the C6030-0060: Status LEDs Description of the Status LEDs: UPS Link not defined...
Replace battery only with the identical type or an alternative type recommended by the manufacturer. Notice correct polarity! WARNING Handling of Batteries Batteries should not be recharged, exposed to fire, opened, short-circuited and they WARNING should be protected against sunlight and moisture. C6030-0060...
First remove the two red self-adhesive flaps at the top and the bottom of the housing. You have now access to the four Torx TX10 screws (see arrows): After screwing out the four screws the fan housing can be removed and allows access to the fan. C6030-0060...
Page 16
Product Description After removing the two Torx TX20 screws (see arrows) the fan can be exchanged. Therefor disconnect the supply cable from the motherboard After exchanging the fan the reassembly takes place in reverse order. C6030-0060...
4. Please keep the associated paperwork. It contains important information for handling the unit. 5. Check the contents for visible shipping damage. 6. If you notice any shipping damage or inconsistencies between the contents and your order, you should notify Beckhoff Service. C6030-0060...
Installation 3.2 Installation of the PC in the control cabinet The C6030-0060 Industrial PC is designed for mounting in control cabinets for machine and plant engineering applications. The ambient conditions specified for operation must be observed (see chapter Technical Data).
1. Check that the external power supply is providing the correct voltage. 2. Insert the power supply cable that you have assembled into the Industrial PC's power supply socket. Then connect it to your external 24 V power supply. C6030-0060...
Once the PC has shut down, the Power Status output is switched from 24 V to 0 V. Via this output a signal lamp can be connected or a contactor for de-energizing the whole system. The maximum load for the Power Status output is 0.5 A and a suitable fuse should be provided. C6030-0060...
The low-resistance protective earthing of the Industrial PC is established via the screw connection (PE). Establish a low-impedance connection from the earthing point on the Industrial PC housing (see chapter Protective Earthing (PE)) to the central earthing point on the control cabinet wall, in which the computer is being installed. C6030-0060...
If the PC was ordered without operating system, you have to install the operating system and the driver software for any auxiliary hardware yourself. Please follow the instructions in the documentation for the operating system and the additional devices. C6030-0060...
Housing components (polycarbonate, polyamide (PA6.6)) are suitable for plastic recycling • Metal parts can be sent for metal recycling • Electronic parts such as disk drives and circuit boards must be disposed of in accordance with national electronics scrap regulations. C6030-0060...
Procedure Nothing happens after the Industrial No power supply to the Industrial Check power supply cable PC has been switched on Call Beckhoff Service Other cause The Industrial PC does not boot Setup settings are incorrect Check the setup settings...
Assembly dimensions 6 Assembly dimensions Industrial PC C6030-0060, with mounting sheet for rear wall installation Notice mounting orientation The assembly of the unit must take place with the orientation diagrammed here. Attention All dimensions in mm. C6030-0060...
Page 26
Assembly dimensions Industrial PC C6030-0060, with mounting sheet for side wall installation Notice mounting orientation The assembly of the unit must take place with the orientation diagrammed here. Attention All dimensions in mm. C6030-0060...
Technical Data 7 Technical Data Risk of explosion! Do not use the Industrial PC in areas of explosive hazard! Danger Product name C6030-0060 Dimensions (B x H x T) see chapter Assembly dimensions Weight approx. 1460 g without mounting sheet approx.
Please contact your Beckhoff branch office or partner company for local support and service on Beckhoff products! The contact addresses for your country can be found in the list of Beckhoff branches and partner companies: www.beckhoff.com. You will also find further documentation for Beckhoff components there.
Technological changes to the device may cause the loss of the FCC approval. Note 8.4 FCC Approval for Canada FCC: Canadian Notice This equipment does not exceed the Class A limits for radiated emissions as described in the Radio Interference Regulations of the Canadian Department of Communications. C6030-0060...