Chapter 2: Installation
Supra interior layout
CON3
R69
14
20
16
COM
Saver
15
3
F2
3
F1
VAR1 VAR2
RLY 1
5
1
Voltage selection switch – set this switch to the correct voltage before installing the Supra.
2
Incoming power fuse (F5) – 1 A, 250 VAC non-time-delay glass fuse.
Variable stage fuses (F1 to F4) – 15 A, 250 VAC fast-acting ceramic. F1 is for variable stage 1, F2 for stage 2, and
3
so on.
4
Ground plate screw – connect a ground wire to this screw.
Variable stage terminals (VAR1 to VAR4) – connect variable heating or cooling equipment such as fans or heat
5
lamps to these terminals.
General-purpose relay terminals (RLY1 to RLY12) – connect single stage (on or off) equipment to these terminals.
6
You can configure these relays as heat, cool, duty cycle, timed event, curtain control, or inlet control.
7
Incoming power terminal – connect the incoming power (120/230 VAC, 50/60 Hz) to this terminal.