INSTALLATION AND TECHNICAL SERVICE INSTRUCTIONS

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the R32 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Riello R32 Series

  • Page 1 AARIA MONO S3 SERIES R32 INSTALLATION AND TECHNICAL SERVICE INSTRUCTIONS...
  • Page 2 While your technical skills and knowledge will certainly be more than sufficient, this booklet contains all the information that we have deemed necessary for the device’s correct and easy installation. Thank you again, and keep up the good work. RIELLO COMPLIANCE R AARIA MONO S3 heat pumps are compliant with the following European Directives: —...
  • Page 3: Table Of Contents

    AARIA MONO S3 TAbLE OF CONTENTS GENERAL INFORMATION ....p. 4 General Notices ......p. 4 Safety precautions .
  • Page 4: General Information

    GENERAl INfORMAtION GENERAL INFORMATION The R32 refrigerant gas is slightly inflammable and odour- General Notices less. Carefully read the safety data sheet available from the dealer. This booklet is an integral part of the device, and must When you get the product, check immediately that the con- therefore be carefully preserved, and must ALWAYS accom- tents are all present and undamaged.
  • Page 5: Unit Description

    Safety and adjustment devices The device safety and setting are achieved thanks to — compressor motor thermal protection, which is triggered in RIELLO Spa - Via Ing. Pilade Riello, 37045 LEGNAGO (VR) - Italy case the current consumed by the compressor is excessive...
  • Page 6: Technical Specifications

    GENERAl INfORMAtION Technical specifications Outdoor unit data Model Cooling performance [A35 / A27] Nominal capacity 2,60 3,50 Nominal power input 0,65 0,87 Rated frequency Maximum frequency Minimum frequency Nominal current consumption 2,90 3,90 Max. current input 5,30 5,80 Minimum current consumption 1,30 1,60 Heating performance [A7 / A20]...
  • Page 7: Operating Limits

    GENERAl INfORMAtION Operating limits A (°C) A (°C) B (°C) B (°C) Outdoor air temperature Outdoor air temperature Internal air temperature Internal air temperature The graphs are based on the following condition: — pipe length: 5 m — air flow: maximum —...
  • Page 8: Installation

    The Instruction book comes with the equipment and it should be taken, read and kept carefully. The document envelope must be kept in a safe place. Any duplicate must be requested from Riello S.p.A. which re- serves to charge the cost. Labels positioning...
  • Page 9: Handling And Removal Of The Packing

    INStAllAtION — screw the fixing screw The product must be stored of according to the regulations in force. — handle the unit by grasping the handles provided. — remove the document envelope Handling and removal of the packing In manual operation it is compulsory to respect always the maximum weight per person provided for by the national laws and standards.
  • Page 10: Recommended Distances

    INStAllAtION Recommended distances Positioning on floor The distances for the device installation and maintenance are shown in the figure. The indicated spaces are necessary in order to prevent the airflow from being blocked, as well as to allow normal cleaning and maintenance operations to be carried out. Fastening screw M4 Anti-vibration element (supplied) Spirit level...
  • Page 11: Installation On Old Systems Or Systems In Need Of

    INStAllAtION Model Connections Condensate discharge attachment Ø Hanging position Properly sized supporting brackets must be used if the de- vice is installed in suspension. Ensure that the wall section does not include bearing ele- ments, pipes or electric lines. Liquid line connection Gas line connection Service connection Model...
  • Page 12 INStAllAtION Pipe Ø thickness inches 6,35 9,52 12,70 15,88 Maximum operating pressure 4.3 Mpa. In case of a drop in excess of 5 m, a siphon must be installed every 5-7 metres. — cut the pipe end square using a pipe cutter —...
  • Page 13 INStAllAtION — use insulating material that is thicker than 15 mm — ensure that the insulating material adheres to the pipe without gaps — fix using adhesive tape Do not tighten the adhesive tape excessively to prevent damaging the insulation. Avoid partial insulation of the pipes.
  • Page 14 INStAllAtION Do not use oxygen or acetylene or other flammable or poi- Valve Plug sonous gases in the refrigerating circuit, as they can cause Pipe Ø tightening tightening wrench explosions. torque torque — reach a pressure equal to 0.3 Mpa inches —...
  • Page 15 INStAllAtION If the pressure has risen again: 2-way shut-off valve On-off valve cover plug Hex wrench Opening by 1/4 of a turn Opening Closing — open the 2-way shut-off valve by a quarter of a turn Service connection blanking plug —...
  • Page 16: 2.11 Wiring Diagram

    INStAllAtION 2.11 Wiring diagram Compressor CN28 BR(OR B) R(U) C(W) AC-L S(V) CN25 BL(OR W) AC-N FUSE1 T25A 250VAC CN24 CN36 Communication module CN11 COMB MAIN PCB COMA CN6 CN7 CN8 CN9 BL(OR W) CN23 CN10 AC-L OUT Power module BR(OR B) COMPRESSOR PCB AC-L OUT...
  • Page 17 INStAllAtION 1 (N) 2 (L) 3 (C) 1 (N) 2 (L) 230V 1-N 50HZ Terminal blocks Terminal board cover panel Connections cover 3(C) 2(L) 1(N) — unscrew the fastening screw — push down the connection covering panel — remove the connection covering panel —...
  • Page 18 INStAllAtION The cable sections specified in the table are minimum re- It is forbidden to earth the device together with pipes, quirements. The correct size must be calculated taking in- lightning conductors or the earthing system of a telephone to account the actual length, the type of routing and other line.
  • Page 19: Commissioning And Maintenance

    COMMISSIONING ANd MAINtENANCE COMMISSIONING ANd MAINtENANCE Avoid using mobile phones. Preparation for first commissioning Additional refrigerant charge Prior to commissioning, it is necessary to check that: — all the safety conditions have been met The units are supplied with a sufficient amount of refrigerant gas —...
  • Page 20: Ordinary Maintenance

    COMMISSIONING ANd MAINtENANCE Any gas leaks indoors can generate toxic gases if they come All described operations MUST be carried out under the fol- into contact with naked flames or high temperature bodies, lowing conditions: in case of leaks, please air the rooms thoroughly. —...
  • Page 21: Operation Signal And Alarms

    COMMISSIONING ANd MAINtENANCE — stop the device for about 3 minutes led 2 description — connect the charging tube of the pressure gauge unit to Indicates that the unit is supplied with the three-way valve service connection on gas side electricity —...
  • Page 22 COMMISSIONING ANd MAINtENANCE led 1 description Remarks The alarm activates 5 minutes after the unit start Lack of refrigerant After 2 consecutive interventions in 20 minutes, the unit resets after problem resolution The alarm activates 5 minutes after the unit start The alarm activates when, in 4-way valve Heating mode, the temperature...
  • Page 23: Disposal

    RECYClING ANd dISPOSAl dISPOSAl Packaging materials shall be disposed of separately so as to re- cover and recycle them. Refrigerant and oil must be recovered and not dispersed into the environment. At the end of its ser- vice life, the device shall be disposed of according to the existing legislation.
  • Page 24 RIELLO S.p.A. - 37045 Legnago (VR) tel. +39 0442 630111 - fax +39 0442 630371 www.riello.it As the manufacturer is constantly improving its products, the aesthetic or dimensional features, the technical data, the equipment and accessories indicated could be subject to variations.