Tricel NOVO EN6-50 User Manual

Wastewater treatment plants

Advertisement

Quick Links

Technical & Installation Manual
Tricel
Wastewater treatment systems
®
TTM T106 Rev 06 Nov 13

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NOVO EN6-50 and is the answer not in the manual?

Questions and answers

Summary of Contents for Tricel NOVO EN6-50

  • Page 1 Technical & Installation Manual Tricel Wastewater treatment systems ® TTM T106 Rev 06 Nov 13...
  • Page 2: Table Of Contents

    4.3 Stage 3: Final settlement chamber: ..........................7 Plant Dimensions: ............................8 Plant Drawings: ............................10 Technical drawing of Tricel pumped plant: ....................15 Lid locking points: ............................15 Manhole risers – (deep inverts): ........................16 10. Installation: ..............................17 10.1 Pre –installation tank inspection: ..........................
  • Page 3: Health And Safety Precautions

    All electrical work to be carried out by competent persons using suitable materials for the application. ® • Do not open the Tricel Novo cover without firstly isolating the mains power • Electrical work must be carried out strictly to the manufacturer’s instructions and to the relevant national rules for electrical installations.
  • Page 4: Installation

    1.3 Installation: • Excavation work should be planned with due regard to health and safety requirements. • Excavation should either be shored or battered back to a “safe” angle • Use appropriate lifting equipment • Care should be taken around grounds work machinery •...
  • Page 5 Ensure sufficient lifting height can be achieved and is available on site. If not a lifting bar as per option 2 is required. Option 1* Option 2* 6. Tanks which are greater than 4 modules (4.6m) in length should be lifted using the slings provided as per option 3, shown below.
  • Page 6: Introduction

    1. Introduction: Tricel Novo wastewater treatment plants are manufactured from Sheet Molding Compound (SMC) ensuring a durable and strong product. The Tricel Novo is manufactured in modular components and these modules are fabricated together to make different size tanks. The Tricel Novo Submerged aeration plant is suitable for domestic and light commercial applications. These plants use a simple proven technology, comprising of 3 treatment zones.
  • Page 7: The Wastewater Purification Process

    A sludge return system pumps this sludge back to the primary settlement zone. The remaining treated liquid now meets the required standard to be safely passed out of the Tricel Novo plant.
  • Page 8: Plant Dimensions

    1. Plant Dimensions: Tricel Novo wastewater treatment plants, certified to EN 12566-3:2005 Design population UK10 UK12 UK18 UK24 UK30 Nominal inlet/outlet pipe diameter Overall length Overall width 1.64 1.64 1.64 1.64 1.64 1.64 1.64 Overall height 2.24 2.24 2.24 2.27 2.27...
  • Page 9 Design population UK36 * UK42* UK50* Plant A Plant B Plant A Plant B Plant A Plant B Nominal inlet/outlet pipe diameter mm Overall length Overall width 1.64 1.64 1.64 1.64 1.64 1.64 Overall height 1.99 2.27 1.99 2.27 1.99 2.27 Inlet invert to base 1.35...
  • Page 10: Plant Drawings

    1. Plant Drawings: Tricel Novo UK6 gravity plant: Tricel Novo UK8 gravity plant: Tricel Novo UK10 gravity plant:...
  • Page 11 Tricel Novo UK12 gravity plant: Tricel Novo UK18 gravity plant:...
  • Page 12 Tricel Novo UK24 gravity plant: Tricel Novo UK30 gravity plant: Tricel Novo UK36 gravity plant – 2 tank plant:...
  • Page 13 Tricel Novo UK42 gravity plant – 2 tank plant:...
  • Page 14 Tricel Novo UK50 gravity plant 2 tank plant: Example of “stepped installation”.
  • Page 15: Technical Drawing Of Tricel Pumped Plant

    1. Technical drawing of Tricel pumped plant: All plants are available as pumped options. The pump is housed in the final settlement chamber of each plant. Other pump options are available to customer specifications. Pump Specification • Min discharge rate 60l/min •...
  • Page 16: Manhole Risers - (Deep Inverts)

    500mm enter the plant 750mm Only a Tricel Novo manhole risers should be used *Plants with a manhole riser of 500mm or 750mm must have a concrete installation. 500mm and 750mm risers cannot be retrofitted unless the correct installation is in place.
  • Page 17: Installation

    This is the responsibility of the onsite contractor. The Tricel Novo is suitable for a maximum manhole riser of 750mm which gives a maximum inlet invert of 1310mm, as per picture. The Tricel Novo is not suitable where a deeper installation is required.
  • Page 18: Quick Installation Guidelines

    10.2 Quick installation guidelines: A dry site is one where the water table never rises higher than the base of the Tricel Novo plant. A wet Site is one where the water table may rise higher than the base of the Tricel Novo plant.
  • Page 19 Lift tank into position and align height for connecting pipe work.   Ensure correct inlet and outlet orientations of the plant, which may   contain 1 or more tanks. Ensure that each tank is 100% level.   Connect pipe work, as required.
  • Page 20: Detailed Installation Information

    10.3 Detailed installation information: The Tricel Novo must be situated a minimum of 7m from the dwelling and as far away as practically possible considering topography and pipe work levels. The Tricel Novo should not be installed in an area subject to flooding or excessive water runoff.
  • Page 21 Excavation Size Excavation Size Tank Size Tank A (m) Tank B (m) 2.6 x 2.14 3.1 x 2.14 UK10 3.6 x 2.14 UK12 4.1 x 2.14 UK18 5.1 x 2.14 UK24 6.1 x 2.14 UK30 7.1 x 2.14 UK36 3.1 x 2.14 6.1 x 2.14 UK42 4.1 x 2.14...
  • Page 22 (or its concrete surround). If this slab is constructed immediately above the tank, it should be separated from the concrete surrounding the tank by a compressible material. Installation guidelines are available from www.uk.tricel.eu 10.3.4 Control of groundwater: During installation tanks must not be subjected to buoyant forces.
  • Page 23: Gravel Installation

    A gravel surround can be used in dry site conditions if the inlet invert is less than 810mm (maximum 250mm riser). A dry site is one where the water table never rises higher than the base of the Tricel Novo tank. 10.4.1 Tank base/plinth: •...
  • Page 24: Concrete Installation

    810mm and 1310mm (plants with 500mm and 750mm risers). A wet site is one where the water table may rise higher than the base of the Tricel Novo tank. The option of a reinforced concrete slab or deadman anchor may also be used. This should be designed by an on-site structural engineer to suit site conditions.
  • Page 25: Plinth And Backfill Specifications

    10.5.2 Installing onto the base/plinth: • Mechanically lift the plant carefully into the centre of the hole before the concrete sets. • The tank must be dead level on the plinth. • Connect and seal the pipe work to the tank appropriately. 10.5.3 Backfilling a wet site: Refer to backfill specification appropriate for site conditions •...
  • Page 26 The following materials are approved as primary backfill: Rounded pea gravel: Minimum particle size 3mm, maximum 18 mm, compacted to a relative density of >70%. Gravel shall be clean and free flowing, free from large rocks, dirt, sand, roots, organic materials or debris. Upon screening analysis the backfill material shall have no more than 5% by weight passing 2.36 mm Sieve Crushed or processed stone: Minimum particle size 3 mm, maximum 12 mm, compacted to a relative density of >40%...
  • Page 27: Electrical Installation

    The plumbing to and from the plant should be completed by a competent person in accordance with national regulations and best practices. Important Do not: Plumb storm-water (water) from roofs, drains, footpaths etc., into the Tricel Novo Wastewater treatment plant...
  • Page 28: Ancillary Installation Notes

    Grease Trap: Best practice indicates that a grease trap be fitted before the plant particularly in applications where high quantities of grease exist in the wastewater. Sampling chamber: Best practice indicates that a chamber be fitted after every unit to allow easy access for sampling purposes. The inlet of the chamber must be higher than the outlet to facilitate sampling cup.
  • Page 29: Access

    All units are fitted with an alarm, which will alert of irregularities in the plant. 1. Disposal of treated water: The treated wastewater from the Tricel Novo plant should be disposed of as per guidelines from the planning regulations issued by your local authority.
  • Page 30: Maintenance

    The inlet and outlet should be inspected and rodded to remove any blockages if necessary. The Tricel Novo plant will require a full service every year to guarantee the efficiency of the plant is maintained. Service personnel must be accommodated with clear access to the tank.
  • Page 31: Production Of Sludge

    16.3.1 De-sludging (emptying the solid waste from chamber 1 the primary chamber): • Remove the de-sludging access cover(s) • Empty the Tricel Novo plant using the vacuum tanker. Care must be taken not to damage the plant with the hose of the vacuum tanker • Replace the de-sludging access cover securely 1.
  • Page 32 • The Tricel Novo plant is one part of the overall wastewater treatment system, which includes many components (plumbing, ventilation, plant and polishing filter. Each component has to function correctly for the overall system to work which is the responsibility of the homeowner.
  • Page 33: Troubleshooting

    • Should the plant be used intermittently or if extended periods of non-use are expected, it is recommended that the plant remain on and in operation. The contents of the plant should not be allowed to go septic due to non-use. •...
  • Page 34 Blowers runs Thermal overload tripped Protect installation from the sun. intermittently Air supply vent blocked, clean if necessary Filter blocked, replace if necessary Discharge hose blocked or kinked, remove obstruction Electrical fault Get a qualified person to check that the alarm is installed correctly and the power supply to the plant is correct Pump runs...
  • Page 35 Symptom Possible causes Corrective action Effluent odour Pipe connections to toilets / Check that the traps / U - bends in the drains are directly outside the drains not connected correctly. fitted and the joints sealed house or inside the house Air vent on pipe work not fitted Ensure all effluent pipes are vented correctly, vents...
  • Page 36 Small wastewater treatment system for up to 50PT – Packaged and/or Site Assembled Domestic Wastewater Treatment Plant as set out in EN12566 Part3 2. Name of Product: Tricel Novo UK6 – UK50 3. Product Characteristics Material Glass Reinforced Plastic (GRP)
  • Page 37 8. Declared Performance: Treatment Performance Essential Characteristic Performance* Harmonised Technical Specification Nominal Organic Daily Load 0.36 kg/d Nominal Hydraulic Daily Load 0.90 m 91.6% 52 mg/l 95.9% 11mg/l 95.3% 16 mg/l 79.9% 8mg/l EN12566-3 Electrical Power 1.1 kWh/d Consumption *Performance results obtained at average organic daily load of 0.26kg/d and hydraulic daily load of 0.9m **Determined at temperatures >12 Material Performance...
  • Page 38 GL10 3SA, United Kingdom DOP01CPRUK03201414 EN 12566-3 Packaged wastewater treatment plants for treatment of domestic wastewater Product: Tricel Novo UK6 – UK50 Range of Wastewater Treatment Plants Material: Notified Body: Prüfinstitut für Abwassertechnik GmbH Hergenrather Weg 30 52074 Aachen Number.:...