Sanyo 85464359982001 Installation Instructions Manual
Sanyo 85464359982001 Installation Instructions Manual

Sanyo 85464359982001 Installation Instructions Manual

W-2way system air conditioner
Table of Contents

Advertisement

07-007 W-2WAY_II_NA
1/23/07
I R410A Models
Indoor Units
X
4-Way Air Discharge Semi-Concealed Type
A
1-Way Air Discharge Semi-Concealed Type
U
Concealed Duct Type
Concealed Duct
D
High-Static Pressure Type
T
Ceiling-Mounted Type
K
Wall-Mounted Type
Outdoor Units
C
ECO-i W-2WAY
* Refrigerant R410A is used in the outdoor units.
Optional Controllers
Timer Wired Remote Controller
Wireless Remote Controller (For U, D Type)
Wireless Remote Controller (For X Type)
Wireless Remote Controller (For A, T Type)
RC Wireless Remote Controller (For K Type)
Simplified Remote Controller
System Controller
Intelligent Controller
Communication Adaptor
Remote Sensor
LonWorks Interface
85464359982001 ©SANYO 2006
6:09 PM
Page a

INSTALLATION INSTRUCTIONS

– W-2WAY System Air Conditioner –
for Refrigerant R410A
Class
AHX0752
UHX0752
KHX0752
Class
90
CHDX09053 CHDX14053
RCS-TM80BG
RCS-BH80AAB.WL
RCS-SH80AAB.WL
RCS-TRP80AAB.WL
RCS-SH1AAB
RCS-KR1AGB
SHA-KC64UG
SHA-KT256BA
SHA-KA128AAB
ART-K45AGB
SHA-LN16UAB
7
9
12
XHX1252
XHX1852
AHX0952
AHX1252
UHX1252
UHX1852
THX1252
THX1852
KHX0952
KHX1252
KHX1852
140
18
24
36
XHX2452
XHX3652
UHX2452
UHX3652
DHX3652
DHX4852
THX2452
KHX2452
SANYO Electric Co., Ltd.
Gunma, Japan
X
A
48
U
D
T
K

Advertisement

Table of Contents
loading

Summary of Contents for Sanyo 85464359982001

  • Page 1: Installation Instructions

    Wireless Remote Controller (For A, T Type) RC Wireless Remote Controller (For K Type) Simplified Remote Controller System Controller Intelligent Controller Communication Adaptor Remote Sensor LonWorks Interface 85464359982001 ©SANYO 2006 Page a INSTALLATION INSTRUCTIONS for Refrigerant R410A XHX1252 AHX0752 AHX0952 AHX1252...
  • Page 2: Important

    Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers. Page 2 When Installing…...
  • Page 3: Check Of Density Limit

    If a single unit of the multi air conditioner system is to be installed in a small room, select a suitable model and installation pro- cedure so that if the refrigerant accidentally leaks out, its...
  • Page 4: Precautions For Installation Using New Refrigerant

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM Precautions for Installation Using New Refrigerant 1. Care regarding tubing 1-1. Process tubing Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless Pipes and Tubes.” For tubes of ø7/8" (ø22.22 mm) or larger, use C1220 T-1/2H material or H material, and do not bend the tubes. Tubing size: Be sure to use the sizes indicated in the table below.
  • Page 5: New Refrigerant R410A Cannot Be Used For Earlier Models

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 3-2. Use R410A exclusive cylinder only. New refrigerant R410A cannot be used for earlier models 1. Compressor specifications are different. If recharging a R22 or R407C compressor with R410A, durability will significantly decrease since some of the materials used for compressor parts are different.
  • Page 6: Table Of Contents

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM IMPORTANT! ......2 Please Read Before Starting Check of Density Limit Precautions for Installation Using New Refrigerant New refrigerant R410A cannot be used for earlier models...
  • Page 7 07-007 W-2WAY_II_NA 1/23/07 6:09 PM 6. HOW TO PROCESS TUBING 6-1. Connecting the Refrigerant Tubing 6-2. Connecting Tubing Between Indoor and Outdoor Units 6-3. Insulating the Refrigerant Tubing 6-4. Taping the Tubes 6-5. Finishing the Installation 7. AIR PURGING ......67 I Air Purging with a Vacuum Pump (for Test Run) Preparation 8.
  • Page 8: General

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 1. GENERAL This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the outdoor unit and make sure all accessory parts listed are with the system before beginning. 1-1.
  • Page 9 07-007 W-2WAY_II_NA 1/23/07 6:09 PM Table 1-2 (4-Way Air Discharge Semi-Concealed) Part Name Full-scale installation diagram Drain hose Hose band Drain insulator Flare insulator Insulating tape Packing Wiring cover Screw Washer Screw Table 1-3 (1-Way Air Discharge Semi-Concealed) Part Name Full-scale installation diagram Drain hose Hose band...
  • Page 10 07-007 W-2WAY_II_NA 1/23/07 6:09 PM Table 1-5 (Concealed Duct High-Static Pressure) Part Name Washer Flare insulator Drain socket Table 1-6 (Ceiling-Mounted) Part Name Full-scale installation diagram Washer Flare insulator Insulating tape Vinyl clamp Drain hose Hose band Drain insulator Gum eyelet Table 1-7 (Wall-Mounted) Part Name Tapping screw...
  • Page 11: Tubing Length

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 1-5. Tubing Length Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure below. Main tubing length LM = LA + LB … ≤ 262 ft Main distribution tubes LC –...
  • Page 12: Tubing Size

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 1-6. Tubing Size Table 1-9 Main Tubing Size (LA) BTU/h 95,500 (kW) (28.0) Total system horsepower Combined outdoor units ø7/8" Gas tubing (ø22.22) ø3/8" Liquid tubing (ø9.52) *1: If future extension is planned, select the tubing diameter based on the total horsepower after extension. However extension is not possible if the resulting tubing size is two ranks higher.
  • Page 13: Straight Equivalent Length Of Joints

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 1-7. Straight Equivalent Length of Joints Design the tubing system by referring to the following table for the straight equivalent length of joints. Table 1-13 Straight Equivalent Length of Joints Gas tubing size (in. (mm)) 90°...
  • Page 14: Check Of Limit Density

    1-10. Check of Limit Density When installing an air conditioner in a room, it is necessary to ensure that even if the refrigerant gas accidentally leaks out, its density does not exceed the limit level for that room.
  • Page 15: Optional Distribution Joint Kits

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 1-12. Optional Distribution Joint Kits See the installation instructions packaged with the distribution joint kit for the installation procedure. Table 1-18 Model name Cooling capacity after distribution 1. APR-CHP680BA 232,000 BTU/h (68.0 kW) or less 2.
  • Page 16 07-007 W-2WAY_II_NA 1/23/07 6:09 PM 3. APR-P160BA Use: For indoor unit (Capacity after distribution joint is 76,400 BTU/h (22.4 kW) or less.) Example: 4-21/64 3-13/16 Distribution Insulation Joint Table 1-21 Size of connection point on each part (Shown are inside diameters of tubing) Size Part A Part B...
  • Page 17: Example Of Tubing Size Selection And Refrigerant Charge Amount

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 1-13. Example of Tubing Size Selection and Refrigerant Charge Amount Additional refrigerant charging Based on the values in Tables 1-9, 10, 11, 12 and 15, use the liquid tubing size and length, and calculate the amount of additional refrigerant charge using the formula below.
  • Page 18 2455 ft. (floor area 279 ft. ) for refrigerant of 418 oz. <Determination by calculation> Overall refrigerant charge amount for the air conditioner: oz (Minimum room volume for indoor unit: ft. 418 (oz) = 0.29 (oz/ft.
  • Page 19: Selecting The Installation Site

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 2. SELECTING THE INSTALLATION SITE 2-1. Indoor Unit AVOID: G areas where leakage of flammable gas may be expected. G places where large amounts of oil mist exist. G direct sunlight. G locations near heat sources which may affect the performance of the unit.
  • Page 20: Outdoor Unit

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 2-2. Outdoor Unit AVOID: G heat sources, exhaust fans, etc. G damp, humid or uneven locations G indoors (no-ventilation location) G choose a place as cool as possible. G choose a place that is well ventilated. G allow enough room around the unit for air intake/ exhaust and possible maintenance.
  • Page 21: Shield For Horizontal Exhaust Discharge

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 2-3. Shield for Horizontal Exhaust Discharge It is necessary to install an air-discharge chamber (field supply) to direct exhaust from the fan horizontally if it is diffi- cult to provide a minimum space of 7 ft. between the air-dis- charge outlet and a nearby obstacle.
  • Page 22: Dimensions Of Wind Ducting

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 2-6. Dimensions of Wind Ducting Reference diagram for air-discharge chamber (field supply) Ceiling panel 33-3/16 Air direction: Front direction 35-3/64 (Ceiling panel dimensions) 35-15/64 2-11/64 (Maximum bracket dimensions) Front view Note: Can be installed so that the air direction is to the front, right, left or rear direction. 2-unit installation 74-7/32 (2-unit installation: maximum dimensions) 33-3/16...
  • Page 23: Dimensions Of Snow Ducting

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 2-7. Dimensions of Snow Ducting Reference diagram for snow-proof ducting (field supply) 9-13/32 35-3/64 (Ceiling panel dimensions) 53-55/64 1 pc. 4 pc. Front view Note: Can be installed so that the air direction is to the front, right, left or rear direction. 2-unit installation Installation hole pitch Installation hole pitch...
  • Page 24: How To Install The Indoor Unit

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 3. HOW TO INSTALL THE INDOOR UNIT I 4-Way Air Discharge Semi-Concealed Type (X Type) 3-1. Preparation for Suspending This unit uses a drain pump. Use a carpenter’s level to check that the unit is level. 3-2.
  • Page 25: Installing The Drain Piping

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM (2) The length of suspension bolts must be appropriate for a distance between the bottom of the bolt and the bottom of the unit of more than 19/32 in. as shown in Fig. 3-5. (3) Thread the 3 hexagonal nuts and 2 washers (field supply) onto each of the 4 suspension bolts as shown in Fig.
  • Page 26: Checking The Drainage

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM CAUTION In cases where it is necessary to raise the height of the drain piping, the drain piping can be raised to a maximum height of 33-15/32" above the bottom surface of the ceiling. Under no conditions attempt to raise it higher than 33-15/32"...
  • Page 27: How To Install The Ceiling Panel

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 3-6. How to Install the Ceiling Panel 3-6-1. Before Installing the Ceiling Panel Checking the unit position (1) Check that the ceiling hole is within this range: 33-55/64 × 33-55/64 to 35-53/64 × 35-53/64 in. (2) Use the full-scale installation diagram (from the packaging) that was supplied with the unit to determine the positioning of the unit on the ceiling...
  • Page 28 07-007 W-2WAY_II_NA 1/23/07 6:09 PM 3-6-2. Installing the Ceiling Panel After completing the wiring process, install the supplied wiring cover before installing the panel. It is not possible to install the wiring cover after installing the panel. The power must be turned ON in order to change the flap angle.
  • Page 29 07-007 W-2WAY_II_NA 1/23/07 6:09 PM 3-6-3. Wiring the Ceiling Panel (1) Open the cover of the electrical component box. (2) Connect the 7P wiring connector (red) from the ceiling panel to the connector in the unit electrical component box. If the connectors are not connected, the Auto flap will not operate.
  • Page 30: Special Remarks

    Never attempt to move the louver by hand. Proper air flow depends on the location of the air conditioner, the layout of the room and furniture, etc. If cooling or heating seems inadequate, try changing the direction of the air flow.
  • Page 31: I 1-Way Air Discharge Semi-Concealed Type (A Type)

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM I 1-Way Air Discharge Semi-Concealed Type (A Type) 3-8. Suspending the Indoor Unit (1) Follow the diagrams to make the holes in the ceiling. (Figs. 3-29 and 3-30) (2) Depending on the ceiling type: Insert suspension bolts as shown in Fig. 3-31 Use existing ceiling supports or construct a suitable support as shown in Fig.
  • Page 32: Placing The Unit Inside The Ceiling

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 3-9. Placing the Unit Inside the Ceiling Be sure to use a level gauge CAUTION and confirm that the unit is level. If it is not level, water leakage may occur. (1) Use the supplied M5 or 3/16" screws (4) to attach the full-size installation diagram to the indoor unit suspension lugs, in order to obtain the ceiling opening dimensions for suspending the unit.
  • Page 33: Installing The Drain Piping

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM CAUTION The indoor unit includes a drain pump. Be sure to use a level gauge and verify that the unit is level. Before inserting the ceiling material, complete as much of the drain piping work and refrigerant tubing work as possible.
  • Page 34: Checking The Drainage

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM CAUTION Do not install an air bleeder as this may cause water to spray from the drain pipe outlet. (Fig. 3-41) In cases where it is necessary to raise the height of the drain piping, the drain piping can be raised to a maximum height of 33-15/32"...
  • Page 35: Electrical Power Wiring

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 3-12. Electrical Power Wiring (1) Wiring connections The power inlet is on the side of the indoor unit where the refrigerant tubing is located. The electrical component box is on the lower air intake surface of the indoor unit. (Fig.
  • Page 36 07-007 W-2WAY_II_NA 1/23/07 6:09 PM Removing the intake grille Slide the intake grille hooks (2 locations) in the direction of the arrow to open the intake grille. (fig. 3-49a) When the intake grille is open, press a flathead screwdriver against the rear tabs (2 locations) and pull out the intake grille.
  • Page 37 07-007 W-2WAY_II_NA 1/23/07 6:09 PM (5) Align the installation holes on the panel with the bolt holes on the unit. (6) Insert the supplied washer head bolts into the 4 panel installation holes, and tighten until the panel is securely fastened against the unit. (Fig. 3-54) (7) Verify that the panel is securely fastened against the unit.
  • Page 38 07-007 W-2WAY_II_NA 1/23/07 6:09 PM 3-13-3. Wiring the ceiling panel (1) Loosen the 2 screws on the electrical component box lid, and remove the lid. (Fig. 3-57) (2) Fasten the wiring connector (7P, red) which comes out from the ceiling panel using the lead wire clamps (2 locations) on the unit.
  • Page 39: I Concealed Duct Type (U Type)

    I Concealed Duct Type (U Type) 3-14. Required Minimum Space for Installation and Service This air conditioner is usually installed above the ceiling so that the indoor unit and ducts are not visible. Only the air intake and air outlet ports are visible from below.
  • Page 40: Suspending The Indoor Unit

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 3-15. Suspending the Indoor Unit Depending on the ceiling type: • Insert suspension bolts as shown in Fig. 3-63 • Use existing ceiling supports or construct a suitable support as shown in Fig. 3-64. It is important that you use extreme care WARNING in supporting the indoor unit inside the ceiling.
  • Page 41: Installing The Drain Piping

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 3-16. Installing the Drain Piping (1) Prepare standard hard PVC pipe (O.D. 1-1/4") for the drain and use the supplied hose band to prevent water leaks. The PVC pipe must be purchased separately. The transparent drain part on the unit allows you to check drainage.
  • Page 42 07-007 W-2WAY_II_NA 1/23/07 6:09 PM Be careful since the fan will start when you CAUTION short the pin on the indoor control board. (4) When the check of drainage is complete, open the check pin (CHK) and remount the insulator and drain cap onto the drain inspection port. 3-18.
  • Page 43: I Concealed Duct High-Static Pressure Type (D Type)

    I Concealed Duct High-Static Pressure Type (D Type) 3-19. Required Minimum Space for Installation and Service This air conditioner is usually installed above the ceiling so that the indoor unit and ducts are not visible. Only the air intake and air outlet ports are visible from below.
  • Page 44: Suspending The Indoor Unit

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 3-20. Suspending the Indoor Unit Depending on the ceiling type: Insert suspension bolts as shown in Fig. 3-79 Use existing ceiling supports or construct a suitable support as shown in Fig. 3-80. It is important that you use extreme care WARNING in supporting the indoor unit inside the ceiling.
  • Page 45: Installing The Drain Piping

    / air flow noise increases. If the air conditioner is to be installed in a room such as an office or meeting room which needs a low sound level, provide a supply and return noise absorption chamber with an acoustic liner.
  • Page 46: I Ceiling-Mounted Type (T Type)

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM I Ceiling-Mounted Type (T Type) 3-24. Required Minimum Space for Installation and Service (1) Dimensions of suspension bolt pitch and unit Table 3-6 Dimension Type 12, 18 33-21/32 35-53/64 8-17/64 44-19/64 46-29/64 8-17/64 (2) Refrigerant tubing • drain hose position Left side 9-7/8 Closed with rubber stopper at time of shipment.
  • Page 47: Suspending The Indoor Unit

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM (4) Wall and ceiling side opening position Figure shows view from front ø3-15/16 wall side opening 3-35/64 ø3-15/16 wall side opening (for left-side drain hose) * If the optional drain up kit is installed, create a ø3-15/16" hole along the dotted line (part marked with * in figure). 3-25.
  • Page 48 07-007 W-2WAY_II_NA 1/23/07 6:09 PM (5) Before suspending the indoor unit, remove the 2 or 3 screws on the latch of the air-intake grilles, open the grilles, and remove them by pushing the claws of the hinges as shown in Fig. 3-95. Then remove both side panels sliding them along the unit toward the front after removing the 2 attachment screws.
  • Page 49: Duct For Fresh Air

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 3-26. Duct for Fresh Air There is a duct connection port (knock-out hole) at the right- rear of the top panel of the indoor unit for drawing in fresh air. If it is necessary to draw in fresh air, remove the cover by opening the hole and connecting the duct to the indoor unit through the connection port.
  • Page 50 07-007 W-2WAY_II_NA 1/23/07 6:09 PM Never allow traps to occur in the course of the piping. Insulate any piping inside the room to prevent drip- ping. After the drain piping, pour water into the drain pan to check that the water drains smoothly. If the drain hose is to be raised, use the optional drain up kit.
  • Page 51: I Wall-Mounted Type (K Type)

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM I Wall-Mounted Type (K Type) 3-29. Removing the Rear Panel from the Unit (1) Remove the set screws used to fasten the rear panel to the indoor unit during transportation. (2) Press up on the frame at the 2 locations shown by the arrows in the figure at right, and remove the rear panel.
  • Page 52: Removing The Grille To Install The Indoor Unit

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM (2) Check with a tape measure or carpenter’s level. This is important so that the unit is correctly installed. (Fig. 3-117) (3) Make sure the panel is flush against the wall. Any space between the wall and unit will cause noise and vibration. b) If the Wall is Brick, Concrete or Similar Drill 3/16"...
  • Page 53: Shaping The Tubing

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM (3) To mount the indoor unit on the rear panel. 1. When installing the indoor unit, position the indoor unit onto the installation tabs on the upper part of the rear panel. (Fig. 3-123) 2. Press on the air outlet to hold it in place, and press the lower part of the indoor unit until a “click”...
  • Page 54: When Using Wireless Remote Controller Instead Of Wired Remote Controller

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 3-36. When Using Wireless Remote Controller Instead Of Wired Remote Controller When the wireless remote controller is to be used, slide the switch on the indoor unit control PCB. • If this setting is not made, an alarm will occur. (The operation lamp on the display blinks.) •...
  • Page 55: How To Install The Outdoor Unit

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 4. HOW TO INSTALL THE OUTDOOR UNIT 4-1. Transporting When transporting the unit, have it delivered as close to the installation site as possible without unpacking. Use a hook for suspending the unit. (Fig. 4-1) CAUTION G When hoisting the outdoor unit, pass ropes or straps under the bottom plate as shown in the figure at right.
  • Page 56: Routing The Tubing

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 4-3. Routing the Tubing G The tubing can be routed out either from the front or from the bottom. (Fig. 4-6) G The connecting valve is contained inside the unit. Therefore, remove the front panel. (Fig. 4-6) (1) If the tubing is routed out from the front, use cutting pliers or a similar tool to cut out the tubing outlet slit (part indicated ) from the tubing cover.
  • Page 57: Prepare The Tubing

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 4-4. Prepare the Tubing G Material: Use C1220 phosphorous deoxidized copper as described in JIS H3300, “Copper and Copper Alloy Seamless Pipes and Tubes.” (For tubes that are ø7/8" G Tubing size Use the tubing size indicated in the table below. G When cutting the tubing, use a tube cutter, and be sure to remove any burrs.
  • Page 58 07-007 W-2WAY_II_NA 1/23/07 6:09 PM Refrigerant tube port G Use caulking, putty, or a similar material to fill any gaps at the refrigerant tube port ( ) in order to prevent rainwater, dust or foreign substances from entering the unit. * Perform this work even if the tubing is routed out in a downward direction.
  • Page 59: Electrical Wiring

    LOCAL ELECTRICAL CODES before beginning. You must ensure that installation complies with all relevant rules and regulations. (8) To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows: G The remote control wiring and the inter-unit control wiring should be wired apart from the inter-unit power wiring.
  • Page 60: Wiring System Diagram

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 5-3. Wiring System Diagram Power supply 208 / 230V, 1ø, ~60Hz Ground Remote controller Power supply 208 / 230V, 1ø, ~60Hz Ground Remote controller Group control: Power supply 208 / 230V, 1ø, ~60Hz Ground Power supply 208 / 230V, 1ø, ~60Hz Ground Remote...
  • Page 61 07-007 W-2WAY_II_NA 1/23/07 6:09 PM CAUTION (1) When linking outdoor units in a network (S-net link system), disconnect the terminal extended from the short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one of the outdoor units.
  • Page 62 07-007 W-2WAY_II_NA 1/23/07 6:09 PM (5) Use shielded wires for inter-unit control wiring (c) and ground the shield on both sides, otherwise misoperation from noise may occur. (Fig. 5-4) Connect wiring as shown in Section “5-3. Wiring System Diagram.” Loose wiring may cause the terminal to overheat or result WARNING in unit malfunction.
  • Page 63: How To Process Tubing

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 6. HOW TO PROCESS TUBING The liquid tubing side is connected by a flare nut, and the gas tubing side is connected by brazing. 6-1. Connecting the Refrigerant Tubing Use of the Flaring Method Many of conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units.
  • Page 64: Connecting Tubing Between Indoor And Outdoor Units

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM Caution Before Connecting Tubes Tightly (1) Apply a sealing cap or water-proof tape to prevent dust or water from entering the tubes before they are used. (2) Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together.
  • Page 65: Insulating The Refrigerant Tubing

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 6-3. Insulating the Refrigerant Tubing Tubing Insulation G Thermal insulation must be applied to all unit tubing, including the distribution joint (purchased separately). * For gas tubing, the insulation material must be heat resistant to 248°F or above. For other tubing, it must be heat resistant to 176°F or above.
  • Page 66: Taping The Tubes

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 6-4. Taping the Tubes (1) At this time, the refrigerant tubes (and electrical wiring if local codes permit) should be taped together with armoring tape in 1 bundle. To prevent the condensation from overflowing the drain pan, keep the drain hose separate from the refrigerant tubing.
  • Page 67: Air Purging

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 7. AIR PURGING Air and moisture in the refrigerant system may have undesirable effects as indicated below. G pressure in the system rises G operating current rises G cooling (or heating) efficiency drops G moisture in the refrigerant circuit may freeze and block capillary tubing G water may lead to corrosion of parts in the refrigerant system Therefore, the indoor unit and tubing between the indoor and...
  • Page 68 07-007 W-2WAY_II_NA 1/23/07 6:09 PM (4) Do a leak test of all joints of the tubing (both indoor and outdoor) and both gas and liquid service valves. Bub- bles indicate a leak. Wipe off the soap with a clean cloth after a leak test.
  • Page 69 07-007 W-2WAY_II_NA 1/23/07 6:09 PM NOTE The required time in the above table is calculated based on the assumption that the ideal (or target) vacuum condition is less than –14.7 psig (–755 mmHg, 5 Torr). (2) When the desired vacuum is reached, close the “Lo” knob of the manifold valve and turn off the vacuum pump.
  • Page 70: Test Run

    1/23/07 6:09 PM 8. TEST RUN 8-1. Preparing for Test Run G Before attempting to start the air conditioner, check the following. (1) All loose matter is removed from the cabinet especially steel filings, bits of wire, and clips. (2) The control wiring is correctly connected and all electrical connections are tight.
  • Page 71: Items To Check Before The Test Run

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 8-2. Test Run Procedure <Outdoor unit control PCB> Unit No. setting switch (S007) <Outdoor unit control PCB> Unit No. setting switch (S006) <Outdoor unit control PCB> Unit No. setting switch (S004 and S005) (Check the link wiring.) <Outdoor unit control PCB>...
  • Page 72: Main Outdoor Unit Pcb Setting

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 72 8-3. Main Outdoor Unit PCB Setting S003 S002 S004 S005 S006 S007 CN100 CN101 CN003 Fig. 8-4...
  • Page 73 07-007 W-2WAY_II_NA 1/23/07 6:09 PM ● Examples of the No. of indoor units settings (S005, S004) No. of indoor units 1 unit (factory setting) 11 units 21 units 31 units 40 units ● Examples of refrigerant circuit (R.C.) address settings (required when link wiring is used) (S003, S002) System address No.
  • Page 74: Auto Address Setting

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 8-4. Auto Address Setting Basic wiring diagram: Example (1) • If link wiring is not used (The inter-unit control wires are not connected to multiple refrigerant systems.) Indoor unit addresses can be set without operating the compressors. No.
  • Page 75 07-007 W-2WAY_II_NA 1/23/07 6:09 PM Basic wiring diagram: Example (2) No. 1 Refrigerant circuit No. 1 (main outdoor unit) settings System address (system 1 setting) (S002) (S003) No. of (S006) outdoor units (3 units setting) Outdoor unit system 1 Indoor unit Remote controller No.
  • Page 76 07-007 W-2WAY_II_NA 1/23/07 6:09 PM Case 2 Automatic Address Setting (no compressor operation) G Indoor and outdoor unit power can be turned ON for each system separately. Indoor unit addresses can be set without operating the compressors. Automatic Address Setting from Outdoor Unit 1.
  • Page 77 07-007 W-2WAY_II_NA 1/23/07 6:09 PM Case 3A Automatic Address Setting in Heating Mode G Indoor and outdoor unit power cannot be turned ON for each system separately. In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating. Therefore perform this process only after completing all refrigerant tubing work.
  • Page 78 07-007 W-2WAY_II_NA 1/23/07 6:09 PM Case 3B Automatic Address Setting in Cooling Mode G Indoor and outdoor unit power cannot be turned ON for each system separately. In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating. Therefore perform this process only after completing all refrigerant tubing work.
  • Page 79 07-007 W-2WAY_II_NA 1/23/07 6:09 PM Display during automatic address setting G On outdoor main unit PCB * Do not short-circuit the automatic address setting pin (CN100) again while automatic address set- ting is in progress. Doing so will cancel the setting operation and will cause LEDs 1 and 2 to turn OFF.
  • Page 80: Remote Controller Test Run Settings

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM Request concerning recording the indoor/outdoor unit combination Nos. After automatic address setting has been completed, be sure to record them for future reference. List the outdoor main unit system address and the addresses of the indoor units in that system in an easily visible location (next to the nameplate), using a permanent marking pen or similar means that cannot be abraded easily.
  • Page 81: Caution For Pump Down

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 8-6. Caution for Pump Down Pump down means refrigerant gas in the system is returned to the outdoor unit. Pump down is used when the unit is to be moved, or before servicing the refrigerant circuit. (Refer to the Service Manual) G This outdoor unit cannot CAUTION...
  • Page 82: Meaning Of Alarm Messages

    07-007 W-2WAY_II_NA 1/23/07 6:09 PM 8-7. Meaning of Alarm Messages Table of Self-Diagnostics Functions and Description of Alarm Displays Alarm messages are indicated by the blinking of LED 1 and 2 (D72, D75) on the outdoor unit PCB. They are also displayed on the wired remote controller.
  • Page 83 07-007 W-2WAY_II_NA 1/23/07 6:09 PM Possible cause of malfunction Activation of Protective device in indoor unit protective is activated. device Protective device in outdoor unit is activated. Indoor thermistor is either open Thermistor or damaged. fault Outdoor thermistor is either open or damaged.
  • Page 84 07-007 W-2WAY_II_NA 1/23/07 6:09 PM Alarm messages displayed on system controller Serial Error in transmitting serial communication communication signal errors Mis-setting Error in receiving serial communication signal Activation of Protective device of sub indoor protective unit in group control is activated. device NOTE 1.
  • Page 85: Appendix

    NAME OF PARTS X type (4-WAY) CARE AND CLEANING 1. For safety, be sure to turn the air conditioner off and also to disconnect the power before WARNING cleaning. 2. Do not pour water on the indoor unit to clean it. This will damage the internal compo- nents and cause an electric shock hazard.
  • Page 86: Tips For Energy Saving

    Care: After a prolonged idle period Care: Before a prolonged idle period TROUBLESHOOTING If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or a service center. Trouble Air conditioner does not run at all 1.
  • Page 87: 1-Way Air Discharge Semi-Concealed Type (A Type)

    SEMI-CONCEALED A type (1-WAY) I CARE AND CLEANING 1. For safety, be sure to turn the air conditioner off and also to disconnect the power WARNING before cleaning. 2. Do not pour water on the indoor unit to clean it. This will damage the internal compo- nents and cause an electric shock hazard.
  • Page 88: Troubleshooting

    Care: After a prolonged idle period Care: Before a prolonged idle period I TROUBLESHOOTING If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or a service center. Trouble Air conditioner does not run at all 1.
  • Page 89: Concealed Duct (High-Static Pressure) Type (U, D Type)

    *Concealed duct type (U, D): An air filter is not provided with this air conditioner at the time of shipment. To get clean air and to extend the service life of the air conditioner, an air filter must be installed in the air intake.
  • Page 90 1/23/07 6:09 PM I TROUBLESHOOTING If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or a service center. Trouble Air conditioner does not run at all 1.
  • Page 91: Ceiling-Mounted Type (T Type)

    9-4. Ceiling-Mounted Type (T Type) I NAME OF PARTS I CARE AND CLEANING 1. For safety, be sure to turn the air conditioner off and also to disconnect the power before WARNING cleaning. 2. Do not pour water on the indoor unit to clean it. This will damage the internal components and cause an electric shock hazard.
  • Page 92 Care: After a prolonged idle period Care: Before a prolonged idle period I TROUBLESHOOTING If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or a service center. Trouble Air conditioner does not run at all 1.
  • Page 93: Wall-Mounted Type (K Type)

    NAME OF PARTS K Type (Wall-Mounted) CARE AND CLEANING 1. For safety, be sure to turn the air conditioner off and also to disconnect the power before WARNING cleaning. 2. Do not pour water on the indoor unit to clean it. This will damage the internal compo- nents and cause an electric shock hazard.
  • Page 94 Care: After a prolonged idle period Care: Before a prolonged idle period TROUBLESHOOTING If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or a service center. Trouble Air conditioner does not run at all 1.

Table of Contents