DA1-34... series
Physical quantity
Rated operational current
Overload current for 60 s every 600 s
Apparent power at rated
operation
Assigned Instance Motor Power
Power side (primary side):
Number of phases
Rated operating voltage
Input current (phase current)
Minimum braking resistance
Switching frequency (pulse
frequency)
Default settings
Setting range
Maximum leakage current to earth (PE),
without motor
Efficiency
Heat dissipation at I
e
Frame size
Symbol
Unit
I
A
e
i
A
l
400 V
S
kVA
480 V
S
kVA
400 V
P
kW
460 V
P
HP
U
V
LN
I
A
LN
R
Ω
B
f
kHz
PWM
f
kHz
PWM
I
mA
PE
η
P
W
V
DA1 Variable Frequency Drives 11/16 MN04020005Z-EN www.eaton.com
110
150
180
110
150
180
165
225
270
76.2
104
125
91.5
125
150
55
75
90
75
120
150
three-phase
380 V - 10 % - 480 V +10 %, 50/60 Hz (342 - 528 V ±0 %, 48 - 62 Hz ±0 %)
126
165
192
6
6
6
4
4
4
4 - 16
4 - 12
4 - 8
2.68
2.68
2.68
0.98
0.98
0.98
1210
1575
1800
FS6
FS6
FS6
6 Technical Data
6.2 Specific rated operational data
202
240
302
202
240
302
303
360
453
140
166
209
168
200
251
110
132
160
175
200
250
211
241
299
6
6
6
4
4
4
4 - 16
4 - 12
4 - 8
4.75
4.75
4.75
0.98
0.98
0.98
2090
2375
3040
FS7
FS7
FS7
370
450
370
456
555
675
256
311
307
332
200
250
300
350
377
459
2
2
4
4
4 - 8
4 - 8
N/A
N/A
N/A
N/A
4000
5000
FS8
FS8
153