Installation instructions Heat recovery appliance Renovent Excellent 180 (Plus) STORE NEAR THE APPLIANCE This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved.
Before starting installation of the heat recovery unit, check that it has been supplied complete and undamaged. The scope of delivery of the heat recovery unit Renovent Excellent 180 includes the following components: Heat recovery appliance type Renovent Excellent 180...
When ordering an appliance always state the correct type; sub- sequent conversion to a different version is not possible. The Renovent Excellent 180 comes ready to plug in with a 230 V mains plug and a connection for a low-voltage multiple switch on the outside of the appliance.
Chapter 3 Version 3.1 Technical information Renovent Excellent 180 Supply voltage [V/Hz] 230/50 Protection degree IP30 Dimensions (w x h x d) [mm] 560 x 600 x 315 Duct diameter [mm] Ø 125 External diameter condensate discharge [mm] Ø 20...
Chapter 3 Version 3.2 Fan graph Note: The value stated in the circle is the capacity per fan (in Watt) Flow rate [m Fan graph Renovent Excellent 180 Renovent Excellent 180 Rev. E...
Contains the various control inputs and outputs; only for Plus version 16 Extra gland For instance for cable to RH (humidity) sensor 17 Extra gland For instance for 230 V cable to preheater or postheater; only for Plus version Renovent Excellent 180 Rev. E...
Chapter 3 Version 3.4 Connections and dimensions Renovent Excellent 180 3.4.1 Renovent Excellent right-handed version 10 mm Placing the wall mounting kit Renovent Excellent 180 right-handed 4/0 = To dwelling 3.4.2 Renovent Excellent 180 left-handed version = To atmosphere = From dwelling...
4.3 Renovent Excellent Plus version The Renovent Excellent 180 is also available as “Plus” version. This version is equipped with a different control board with 2 additional connectors (X14 & X15) with more connection op- tions for various applications.
A = Minimum height > 60 mm 5.4 Connecting ducts contact the Brink Consultancy Department if you have any vent condensation on the outside of the outdoor air supply duct and the air exhaust duct downstream of the Renovent Excel-...
Page 14
Chapter 5 Installation 60 mm 1 = Renovent Excellent 180 left-handed 4/0 (install level) 6 = Preferred location exhaust ventilation air; use Brink insu- 2 = Preferred ventilation air supply lated ventilation roof sleeve. 3 = Ventilation air supply under the tiles...
X1-2 to X1-2; the appliance will not work when these contacts are interchanged! 2-pole eBus connector The optionally available Brink Air control must be connected to these eBus connector. Cables to be connected by installer (wire diameter at least 0,34 mm nr.2...
A = display B = 4 control keys Function key Menu Scroll; modify value; Switching on or off the Renovent Excellent from operating mode (press for 5 seconds) Scroll; modify value Renovent Excellent 180 Rev. E...
With application of a 3-way switch, mode cannot be used. fan. fans differ, for instance when using an external switch con- When the appliance is switched off through software, the text “OFF” appears here (see §7.1). Renovent Excellent 180 Rev. E...
§11.6. V1 or V2 When the text “CN1 or CN2” ap- pears on the display, one of the (Only for Plus external 0 - 10 V inputs is active, version) also see§11.7. Renovent Excellent 180 Rev. E...
2 (CO sensor only as an option for Plus version) Readout CO sensor 3 (CO sensor only as an option for Plus version) Readout CO sensor 4 (CO sensor only as an option for Plus version) Renovent Excellent 180 Rev. E...
All fault messages can be deleted by pressing the “R” key in explanation the service menu during 5 seconds; This is only possible when No. fault message there is no active fault! Renovent Excellent 180 Rev. E...
Warning When working on the appliance, always take The appliance can be switched on by pressing the ‘-’ key during 5 seconds. it off through software and subsequently pulling the power plug. > 5 sec. Renovent Excellent 180 Rev. E...
Renovent Excellent was supplied from the factory; all message codes / fault codes will be erased from the service menu as well. press > 10 sec. simultaneously 3 sec. displayed operating mode Renovent Excellent 180 Rev. E...
E999 still appears, then replace the control board by a board of the correct type. Renovent Excellent 180 Renovent Excellent 180 Plus 8.2 Display codes Non-locking fault When the appliance detects a non-locking fault, it will still keep running (limitedly).
Page 25
If mode 2 of a multiple switch does not work, the modular connector of the multiple switch has been connected the wrong way round. Cut off one of the RJ connectors to the multiple switch and mount a new connector the other way round. Renovent Excellent 180 Rev. E...
Also when the message “FILTER” has ried out. the “counter” will be reset to zero. 5 sec. FILTER disappears; the light at the multiple switch is off and the display is back to oper- ating mode. Renovent Excellent 180 Rev. E...
Pull all connectors from the print that are connected to con- nectors at the top of the appliance. Take the earth wire from the housing. Remove the heat exchanger. Be careful not to damage the foam parts in the appliance. Remove the front cover. Renovent Excellent 180 Rev. E...
Page 28
“R” key for 5 seconds. Both fans are now accessible and can be taken out. 10 Clean the fans with a soft brush. Make sure the balancing weights do not shift! Renovent Excellent 180 Rev. E...
G = Indoor temperature sensor R = NO contact or input 0-10 V)(Plus version) H = Service connector T = Control panel K = Brink Air Control (accessory) Z = RH sensor (optional) L = Only for Renovent Plus version Renovent Excellent 180...
Note: For the modular cable used, the “tab” of both modular connectors must be mounted facing the mark on the A = Renovent Excellent 180 modular cable. B = Multiple switch with lter indication A = Renovent Excellent 180...
Page 32
All Renovents have the same air ow rates as the Renovent set as “Master”. 11.4 Connecting RH (humidity) sensor A = Renovent Excellent 180 B = Control board; to access board , see §9.2 item 1 - 5 C = RH (humidity) sensor D = The cable that comes with RH sensor;...
Page 33
OFF = switched off Preheater con- 0 = off nected ON = switched on Heater 1 = preheater 0 = off 2 = postheater Heater 1 = preheater Temp. postheater 21 °C 15°C - 30°C 2 = postheater Renovent Excellent 180 Rev. E...
Page 34
“1” to “0” or “2” makes this 0-10V input an NO contact or NC contact respectively. On application of to switch inputs, switch contact 1 (9-pole connector no. 1 & no. 2) always takes precedence over switch contact 2 (9-pole connector no. 3 & no. 4). A = Renovent Excellent 180 Plus 230 V...
If connection no. 1 and no. 2 on the 9-pole connector are programmed as second 0-10 V input, step numbers 15, 16 and 17 can be used to modify the various modes the same as for the standard 0-10 V input. When the provision is active on the optional second 0-10 V input, the display shows the text “V1”. Renovent Excellent 180 Rev. E...
Page 36
ON = Switching on geo- Switched on 0 °C heat exchanger OFF = Switched off Minimum tem- perature geo-heat 5 °C 0 - 10°C exchanger Maximum tem- perature geo-heat 25 °C 15 - 40°C exchanger Renovent Excellent 180 Rev. E...
Control board (Plus version) When replacing, please note the correct dip switch settings; see §8.1 531780 Cord with mains plug 230 V * 533009 Filter plug (2 pcs) 531841 The mains cable has a print connector. When replacing it, always order a replacement mains cable from Brink. Renovent Excellent 180 Rev. E...
Page 41
Chapter 14 ErP-values Productdatasheet conform Ecodesign (EU), nr. 1254/2014 (Annex IV) Supplier: Brink Climate Systems B.V. Model: Renovent Excellent 180 (Plus) The annual electricity The annual heating saved SEC-Value Energyclass Climate zone Type of control consumption (AHS) in kWh/m²/a (SEC)
P.O. Box 11 NL-7950 AA Staphorst, The Netherlands Product: Heat recovery appliance type: Renovent Excellent 180 Renovent Excellent 180 Plus The product described above complies with the following directives: 2014/35/EU (low voltage directive) 2014/30/EU (EMC directive) RoHS 2011/65/EU (substances directive)
Page 44
BRINK CLIMATE SYSTEMS B.V. P.O.Box 11 NL-7950 AA Staphorst The Netherlands Wethouder Wassebaliestraat 8 NL-7951 Staphorst The Netherlands T. +31 (0) 522 46 99 44 F. +31 (0) 522 46 94 00 info@brinkclimatesystems.nl www.brinkclimatesystems.nl...