Safety Instructions; Standards And Directives; Shipping And Storage; Commissioning - ABB 1HDS112160R0001 Product Manual

Vacuum pump set for hydromechanical operating mechanisms
Table of Contents

Advertisement

4
P R O D U C T M A N U A L VA C U U M P U M P S E T - 1 H D S 6 8 0 6 3 2 R E V A
5

Safety instructions

• When using the vacuum pump set regard all local regulations concerning safety on work and those
regulations of the operator of the installation.
• Do not install the vacuum pump on high exposed GIS parts. This may cause hazards. The spiral hose
has sufficient length to operate the vacuum pump on the floor or an occasional working table.
• There is a risk of stumbling and slipping. Block the working place to prevent stumbling over the
associated parts.
• Only personnel which has been trained on hydromechanical operating mechanisms and switching
apparatus shall operate the vacuum pump set.
• Wear safety glasses, oil-resistant gloves and safety shoes during work.
• Do not release hydraulic oil of the operating mechanism or lubricating oil of the vacuum pump to the
environment. Dispose oil-soaked clothes environmentally compatible. Hydraulic and lubricating oil is
harmful to the environment.
• Avoid direct contact to hydraulic or lubricant oil. Direct contact may cause irritations. Clean affected
sites with abundant amount of water.
• Do not breathing or swallowing hydraulic or lubricant vapor, mist and oil. Breathing high concentration
levels or swallowing may cause damages to health or death.
• Do not put defective or damaged parts into operation. Replace damaged parts and parts which recom-
mended period of use is exceeded by new parts. The device shall only be repaired by the manufacturer.
• For following switching operations of the operating mechanism on the coupled breaker, it has to be
secured that the switching device is filled with SF 6 gas at appropriate operating pressure. The mnimal
oil level at fully charged operating mechanism should not be lower than the oil level given in the oil level
charts of the technical description of the oil handling kit 1HDS680617P0001.

6 Standards and directives

The vacuum pump set is in conformance with the machine directive 2006/42/EG.
Additional directives do not apply.
7

Shipping and storage

Transport and store the vacuum pump set only in the supplied transportation case to prevent damage and
protect especially the spiral hose and the expansion tank from sunlight.
Store only in dry and dust-free areas. Storage temperature: +5°C ... +40°C

8 Commissioning

Check all parts of the vacuum pump set for damages before commissioning:
1. Check the vacuum pump for damages. If the vacuum pump is damaged do not put it into operation!
2. Check the expansion tank for damages. If the expansion tank is damaged it has to be replaced by a
new one before commissioning!
3. Check the spiral and the hydraulic hose as well as the pipe connections for damages. If the spiral and
the hydraulic hose or the pipe connections are damaged they have to be replaced by a new one before
commissioning!
4. Check the period of use of the spiral and hydraulic hose. We recommend to replace the spiral and the
hydraulic hose by a new one at least five years after purchase to prevent leakages and malfunctions.