Power requirements for fan controllers

The power requirements for Big Ass Fans controllers are shown in the specification table in the introduction.
If multiple controls are connected to one feeder circuit, the circuit required is the sum of the feeder circuit
requirements listed on the chart. For example, if two 240 V, 3 Φ controllers are connected to a single feeder
circuit, that circuit needs to be rated for 20 amps. This type of installation will also require that each fan control be
installed downstream from a dedicated over-current protection device
Mounting the wall controller
Mount the controller to a wall using a #8–#10 screw. Adhere to the following guidelines when selecting the
controller location:
• Install the controller on a flat surface that is readily accessible, free from vibration, and where there is adequate
distance from foreign objects or moving equipment.
• Do not mount any controller adjacent to or above a heat source or heat-producing equipment.
• The ambient temperature must be between 14º F (-10º C) and 122º F (50º C).
• Do not expose the controller to a corrosive atmosphere or direct sunlight.
• When mounting the controller, keep in mind that the fan should be visible from the controller.
• A minimum distance of 6" (15.2 cm) should be maintained between fan controllers.
Note: Multiple fan controllers are available as a special order only. Please contact Customer Service for more information.
Input power conditioning
Line reactors should be installed if AC supply is subject to any of the following:
• Low line impedance
• Frequent power interruptions
• Phase-to-ground voltage in excess of 125% nominal phase-to-phase voltage
• Distribution system exceeds established kVA limit for your specific model (contact Big Ass Fans for more
information).
• Power factor correction capacitors
• Intermittent noise spikes (lightning)
24
6.25" (159 mm)
5.95" (151 mm)
WARNING
DO NOT USE THIS
DISCONNECT TO
START AND STOP THE
FAN. PERMANENT
DAMAGE WILL
SCA M E
SCA M E
RESULT!
AUTO
FWD
RUN
REV
M
R
F
STOP
1 2 5 6
1 2 5 6
25 4 11
25 4 11

13A13B13C 14 30 16 17

13A13B13C 14 30 16 17
L1
L2
PE
U
V
W
L1
L2
L3
/T1
/T2
/T3
L3
WWW.BIGASSSOLUTIONS.COM
© 2015 DELTA T CORP.
ALL RIGHTS RESERVED.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents