UL, ULC Listed; FM, CSFM,
and MEA (NYC) Approved*
Features
Individual Addressable Relay Module (Relay
IAM):
IDNet addressable control for use with Simplex
alarm control panel models 4100ES, 4100U, 4010ES
and 4010
A single addressable point provides control and status
tracking of a Form "C" contact
Low power latching relay design allows IDNet
communications to supply both data and module power
Compact, sealed construction:
Enclosed design minimizes dust infiltration
Mounts in standard 4" (102 mm) square electrical box
Screw terminals for wiring connections
Visible LED flashes to indicate communications
Optional covers are available to allow LED to be
viewed after installation
UL listed to Standard 864
Description
IDNet Relay IAMs allow fire alarm control panels to
control a remotely located Form "C" contact using IDNet
addressable communications for both data and module
power. Typical applications would be for switching local
power for control functions such as elevator capture, or
control of HVAC components, pressurization fans,
dampers, etc. Relay status is also communicated requiring
only one device address.
Product Selection
Model
Description
4090-9002
Relay IAM
Optional Trim Plates
Model
Description
For semi-flush
4090-9801
mounted box
For surface
4090-9802
mounted box
*
This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing
7300-0026:223 for allowable values and/or conditions concerning material presented in this
document. It is subject to re-examination, revision, and possible cancellation. Accepted for
use – City of New York Department of Buildings – MEA35-93E. Additional listings may be
applicable; contact your local Simplex product supplier for the latest status. Listings and
approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products
Westminster.
®
fire
Trim plate, galvanized
steel, with LED viewing
window; includes
mounting screws
Multi-Application Peripherals
IDNet™ Communicating Devices
Model 4090-9002 Relay IAM
1
-
2
-
+IDNET
3
4
- IDNET
1
2
3
SIMPLEX TIME RECORDER CO.
4090-9002
RELAY IAM
INST. INSTR. 574-184
4
DATE CODE:
4090 Series IDNet Relay IAM Package
(shown approximately 1/2 size)
Specifications
4100ES, 4100U, 4010ES or 4010
Communications
IDNet communications, 1 address per
device
Relay IAM Power
Supplied by IDNet communications
Contact Ratings* (not rated for incandescent switching)
Type
Form C, SPDT
2 A @ 24 VDC, resistive
Power-Limited
1 A @ 24 VDC, inductive
Nonpower-Limited 0.5 A @ 120 VAC, resistive
* Provide circuit fusing and transient suppression as
required per application. DC inductive loads can typically
be diode suppressed; 120 VAC loads may require RC
networks or varistors, depending on device type. Refer to
Installation Instructions 574-184 for additional information.
Screw terminals for in/out wiring,
Wire Connections
18 to 14 AWG wire (0.82 to 2.08 mm
Up to 2500 ft ( 762 m) from control
panel
IDNet Wiring
Up to 10,000 ft ( 3048 m) total wiring
Reference
distance (including T-Taps)
Compatible with Simplex 2081-9044
Overvoltage Protectors
4-1/8" H x 4-1/8" W x 1-3/8" D
Dimensions
(105 mm x 105 mm x 35 mm)
Housing Material
Black thermoplastic
Mounting Plate
Sheet metal, galvanized
Temperature
32° to 120° F (0° to 49° C),
Range
intended for indoor operation
Humidity Range
Up to 93% RH at 100° F (38° C)
N.C.
5
COM
6
N.O.
7
-
8
5
6
7
8
1
from listed
fire alarm
supply
2
S4090-0002-7
)
Need help?
Do you have a question about the IDNet 4090-9002 and is the answer not in the manual?
Questions and answers