• Evaporator fan control • Communication interface • Monitoring function • Error & event log • Battery protection functions • Main Switch • Log of specific parameters • Optimization of specific parameters via PC software before commencing mass production 1.4 Programming The controller can be accessed using either Interface - the Danfoss software tool, Tool4Cool® LabEdition, or - a custom interface. Please contact Danfoss for further information regarding custom interfaces. DEHC.PS.100.I1.02...
Tool4Cool® LabEdition software installation CD NTC temperature sensor (alternative: mechanical thermostat) DC line cords Product key for BD compressor controller DH3TT6RBAD1GW8G68ZM1N8G62ZMCOO916IER6GH2YZEIR (not necessary with Tool4Cool® Version 1.02) Danfoss One Wire/LIN gateway with connection cables • Gateway • One Wire/LIN gateway Communication cable • USB port connector to PC •...
USB port connector to PC Serial RS232 Cable with USB Voltage Supply Power supply cable Wiring diagram option 2 One Wire LIN Gateway Danfoss One Wire LIN Gateway One Wire / LIN Code n o.: 105N9501 RS232/485 Electronics USB 2.0...
Operating Instructions BD Controller 101N07xx Series 24 V DC The compressor control unit has the following connections: I, C, + Modbus data communication. I = communication C & + power supply. C, T Thermostat connection. A Danfoss NTC temperature sensor (option 2) can be connected or a mechanical ON/OFF thermostat (option 1) Fe, + Evaporator fan (Optional) 24 V DC, 0-24 V, max 60 Watt power output, pulse width modulated. Fc, + Condenser fan (optional) 24 V DC, 0-24 V, max 40 Watt power output, pulse width modulated. -, + Main supply voltage. Nominal voltage 24 V DC, range: 17 to 31.5 V DC Wire dimensions Size Max. length* 24V operation...
TOOL COOL ® 3. Tool4Cool® software interface BD Controller 101N07xx Series 24 V DC 3.1 User interface The controller can be programmed and optimized from a PC using the Tool4Cool® software An example of the Tool4Cool® user interface showing the main parameter groups of the BD350GH compressor is shown below. Example: 3.2 Operation The Tool4Cool® software enables the user to observe and document certain aspects of the compressor operation via the controller. The output of the software is in the form of data logs and plots. Using Tool4Cool® the user can also change the settings of the controller parameters, and copy settings from one controller to another.
TOOL COOL ® 4. Parameters BD Controller 101N07xx Series 24 V DC The user can change settings and observe real-time measurements (read-only) in the following parameters. The table in 4.1 Parameter Overview is intended for easy reference. For more detail, please refer to 4.2 Description of Parameter Groups. 4.1 Parameter Overview Parameter Group...
Page 14
Unit name for the unit can be entered here Setting information (optional) Vendor name Vendor name Measurement Product code no Danfoss product code number Measurement Software version Controller software version Measurement Unit ID Danfoss unit ID Measurement Production date Danfoss production date...
Operating Instructions BD Controller 101N07xx Series 24 V DC 4.2 Description of 4.2.1 Main Functions Parameters In order to start and stop the compressor the Main Switch can be set to ON or OFF . OEMs making an interface with custom design electronics via Modbus must be able to control the CCU ON / OFF via the Main Switch.
Operating Instructions BD Controller 101N07xx Series 24 V DC Measurements Name Description Step Unit Cut-in level Calculated value. Cutin = Cutout + Diff. Volt Supply voltage Real-time - voltage measured on + & - terminals Volt 4.2.3 Compressor The speed and thereby the capacity of the compressor is set using the Requested speed parameter. During start up, the compressor can be run at a lower speed, Start speed, than Requested speed.
Operating Instructions BD Controller 101N07xx Series 24 V DC 4.2.4 Condenser fan The speed of the condenser fan can be controlled in order to save energy, reduce noise and optimize the fan operation. The fan is synchronized with the compressor operation. Start and stop delays can be set up as a function of the state of the parameter Thermostat. Furthermore, the fan can be set to run continuously (forced ON operation). Some fan defects are detectable, and are displayed in the parameter Error. The speed of the fan can be controlled in the range from 40% to 100%. Settings Name Default...
Operating Instructions BD Controller 101N07xx Series 24 V DC 4.2.6 Thermostat Thermostat type Two types of thermostat can be utilized for temperature control. Electronic thermostat (NTC sensor) Disconnected sensor error alarm (NTC sensor failure) is sent when the measured temperature is > +100ºC Short circuited sensor error alarm (NTC sensor failure) is sent when the measured temperature < - 60ºC Mechanical thermostat A mechanical ON/OFF thermostat can be connected at terminals C & T.
Operating Instructions BD Controller 101N07xx Series 24 V DC 4.2.7 ECO function Operation in ECO mode reduces energy consumption and noise by controlling compressor speed as a function of temperature. ECO mode can be selected only when using an NTC temperature sensor. In ECO mode, • when operating below ECO temperature, compressors run at the set ECO speed, and the Start speed setting will be overruled, if it differs from ECO speed.
Operating Instructions BD Controller 101N07xx Series 24 V DC 4.2.8 Compressor safety In order to prevent the compressor from short cycling a minimum restart time is built in. After timeout of Compressor restart time a new start of the compressor is permitted. Settings Name Default...
Serial no 4.2.11 Customer register The customer register enables the user to set and change values in custom-designed interface modules. These parameters are visible even when in protected mode. Contact Danfoss for further information. Settings Name Default Max value Min value...
Operating Instructions BD Controller 101N07xx Series 24 V DC 4.2.13 Inverter Temperature (PCB) The controller overheating protection system ensures that the controller does not operate at extremely high temperatures, because under these conditions the quality of the soldered joints will be endangered. When the unit reaches 100ºC the system will shut down and an alarm error (Alarm 6: Thermal failure) will be sent.
Page 23
Operating Instructions BD Controller 101N07xx Series 24 V DC DEHC.PS.100.I1.02...
101N07xx Series 24 V DC Model Code number Description BD350GH 24 V DC supply 102Z3016 BD350/350GH 24 V DC supply - twin compressor 102Z3017 Electronic control unit 24 V DC 101N0715 40W/60W fan output, ECO function 24 V DC line cord, 900 mm, 6mm 105N9542 accessories 24 V DC line cord, 2000 mm, 6 mm 105N9540 accessories 24 V DC line cord, 5000 mm, 6 mm 105N9538...
Tool4Cool® LabEdition software and Danfoss One Wire/LIN gateway DEHC.PS.100.J__.02 Quick Start Guide Danfoss One Wire/LIN Gateway 105N9501 DEHC.PI.100.K__.02 Instructions Electronic Unit for BD350GH Compressor 101N0715 24 V DC DEHC.EI.100.Z__.02 Instructions Electronic Unit for BD350GH Compressor 101N0710 24 V DC (discontinued) DEHC.EI.100.P__.02 Instructions DC Line Cords for BD350GH Electronic Unit 24V DEHC.EI.100.E__.02...