Tmlo, Timo, Tmho, And Tmso (Off-Delay Timer) - IDEC MicroSmart pentra FC5A-C10R2 User Manual

Fc5a series
Hide thumbs Also See for MicroSmart pentra FC5A-C10R2:
Table of Contents

Advertisement

TMLO, TIMO, TMHO, and TMSO (Off-Delay Timer)

Four types of timedown off-delay timers are available; 1-sec off-delay timer TMLO, 100-ms off-delay timer TIMO, 10-ms
off-delay timer TMHO, and 1-ms off-delay timer TMSO. A total of 256 on- and off-delay timers can be programmed in a
user program for any type of CPU module. Each timer must be allocated to a unique number T0 through T255.
These instructions are available on upgraded CPU modules with system program version 200 or higher.
Timer
TMLO (1-sec off-delay timer)
TIMO (100-ms off-delay timer)
TMHO (10-ms off-delay timer)
TMSO (1-ms off-delay timer)
The valid device range depends on the CPU module type. For details, see pages 6-1 and 6-2.
The preset value can be 0 through 65535 and designated using a constant or a data register.
TMLO (1-sec Off-delay Timer)
Ladder Diagram (TMLO)
TMLO
T0
4
I0
I1
T0
Q0
TIMO (100-ms Off-delay Timer)
Ladder Diagram (TIMO)
TIMO
T1
20
I0
I1
T1
Q1
TMHO (10-ms Off-delay Timer)
Ladder Diagram (TMHO)
TMHO
T2
100
I0
I1
T2
Q2
TMSO (1-ms Off-delay Timer)
Ladder Diagram (TMSO)
TMSO
T3
500
I0
I1
T3
Q3
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Device Address
Range
T0 to T255
0 to 65535 sec
T0 to T255
0 to 6553.5 sec
T0 to T255
0 to 655.35 sec
T0 to T255
0 to 65.535 sec
Program List
Instruction
Data
LOD
I0
TMLO
T0
4
LOD
I1
AND
T0
OUT
Q0
Program List
Instruction
Data
LOD
I0
TIMO
T1
20
LOD
I1
AND
T1
OUT
Q1
Program List
Instruction
Data
LOD
I0
TMHO
T2
100
LOD
I1
AND
T2
OUT
Q2
Program List
Instruction
Data
LOD
I0
TMSO
T3
500
I1
LOD
AND
T3
OUT
Q3
FC5A M
S
U
'
ICRO
MART
SER
S
Increments
1 sec
Constant:
100 ms
Data registers: D0 to D1999
10 ms
1 ms
Timing Chart
ON
I0
OFF
ON
T0
OFF
ON
I1
OFF
ON
Q0
OFF
Timing Chart
ON
I0
OFF
ON
T1
OFF
ON
I1
OFF
ON
Q1
OFF
Timing Chart
ON
I0
OFF
ON
T2
OFF
ON
I1
OFF
ON
Q2
OFF
Timing Chart
ON
I0
OFF
ON
T3
OFF
ON
I1
OFF
ON
Q3
OFF
M
FC9Y-B1268
ANUAL
7: B
I
ASIC
NSTRUCTIONS
Preset Value
0 to 65535
D2000 to D7999
D10000 to D49999
4 sec
2 sec
1 sec
0.5 sec
7-11