SENTRY
RCBO
®
(Residual Current Operated
Circuit reaker with Integral
Over-Current Protection)
ontents
Introduction
2
B Product Range
3
C Product Specification
4
D Standards Compliance
6
E Safety Instructions
6
F Installation - General Notes
8
G Installation
10
H Testing
11
I
14
J Guarantee
15
Please leave this leaflet with the
end user for future reference
52778PL Rev
C. PRODUCT SPECIFIC TION
( ont.)
Mechanical
Terminal Capacity
Line in - 25mm
2
Line and Neutral out - 25mm
Product Width
18mm
Product Height above
76mm
Din Rail
Product Length
118mm
Suitable Mounting
MK Sentry Consumer Unit
Enclosure
(select from the MK range)
Method of Mounting
Top Hat Mounting (DIN)
in Enclosure
Rail to EN 50022
Environmental
mbient Temperature Range
-5°C to +40°C
Storage Temperature Range
-30°C to +85°C
Protection, Un-installed Device
IP 20
Protection, Installed in the
Consumer Unit
IP 40
5
. INTRODUCTION
ln this range of Single Module Width RCBO's, each
product provides dual protection; from Over-current via
its MCB section, and from Earth Leaking Fault Current
(Residual Current) via its RCD section.
These devices provide RCD protection in full
compliance with the requirements of the Standard
BS EN 61009-1. They also provide very effective RCD
protection in the Supply Voltage Range of 110V to
253V a.c., meeting the requirements of the Standard
for sensitivity and trip speed at
n and
IΔ
They meet the requirement of the current edition of the
UK Wiring Regulations (BS 7671), as regards ability to
trip with Earth Loop Impedance of up to 1667 Ω (for a
30m RCD), by being able to operate with Earth Loop
Impedance of up to 10,000 Ω.
2
D. ST ND RDS COMPLI NCE
The products in this range comply with the requirements of the
following standards:
2
BS EN 61009-1
BS IEC 61009-2-2
EN 61543 for EMC
E. S FETY INSTRUCTIONS
1. This product must be installed by a competent person (e.g. a
qualified electrician) in accordance with these instructions and
the appropriate clauses of the current edition of the IEE Wiring
Regulations (BS7671) and Building Regulations.
2. The RCBO must be installed within a SENTRY
(select from the range of MK consumer units).
3. The RCBO should not be regarded as a substitute for basic safety
precautions.
4. Test the RCBO quarterly, as detailed in the current edition of the IEE
Wiring Regulations (BS 7671), by pressing the TEST BUTTON marked
T, provided on the product (see label on the Consumer Unit).
6
B. PRODUCT R NGE
The product range is given in Table 1 below.
ll products in the range have an RCD trip current
rating of 30m .
Type B RCBO
List No.
MCB Current
Rating
07932s
6
2
n.
IΔ
07933s
10
07934s
16
07935s
20
07936s
32
07937s
40
07938s
45
07939s
50
E. S FETY INSTRUCTIONS
Do not use the product if
it fails to trip during this
operation. Failure to trip
indicates either no supply to
the RCBO or a faulty device.
Consult a qualified electrician
or contact MK Technical Sales
and Service Department.
Telephone:
01268 563720
(National)
+44 (0) 1268 563758
(International)
5. Choose an RCBO from T BLE 1,
®
Consumer Unit
with the correct ratings, for the
circuit to be protected.
6. The RCBO's in this range must
not be used in ambient
temperatures outside their
specified range.
C. PRODUCT SPECIFIC TION
Electrical
Number of Poles
Rated Supply Voltage
Table 1
Type C RCBO
Supply Voltage Range
List No.
MCB Current
Supply Frequency Range
Rating
Supply Voltage Range for
08932s
6
Test Device Operation
08933s
10
RCD Trip Current Rating
08934s
16
Operating Characteristics
08935s
20
MCB
08936s
32
Rated Short Circuit
Capacity Icn
08937s
40
Neutral Connection
08938s
45
Earth Connection
08939s
50
3
F. INST LL TION - GENER L NOTES
( ont.)
Blue Flying
1. The RCBO shall be installed at the source of the circuit
Curled Neutral
Supply Lead
in which the Earth Fault and Over-current protection is
L
OUT
required.
N
White or
OUT
Cream
2. The RCBO's may be installed alongside other SENTRY
Load
Flying Earth
N
L
FE
N
OUT
OUT
(White)
Supply Lead
IN-Supply
(Blue)
Modular Products, as part of a larger assembly.
3. The RCBO is a sensitive device designed for fixed
L
IN-Supply
BS EN61009-1
must not be installed as part of a portable system which
may be subject to mechanical shocks and vibration.
4. n adhesive label giving test instructions is provided
ON
with each RCBO. This label shall be placed in a
prominent position close to the RCBO (preferably on the
Consumer Unit Cover).
B32
7936s
6000
5. Upon completion of the installation, please leave this
3
I
n 30mA
∆
230V
instruction leaflet in close proximity to the RCBO, for
future reference.
L
Figure 1
IN
Line Supply
7
Single Pole with Solid
Neutral
230V a.c. +10%, -15%
110V to 253V a.c.
45 to 66Hz
195V to 253V a.c.
30 m
Type C
Type B, C
6 k
Flying Lead
Flying Lead
4
®
8
Need help?
Do you have a question about the SENTRY RCBO and is the answer not in the manual?
Questions and answers
doing a cable calc using 32A type b RCBO and need specific time current characteristic data and let through energy figures