Learn process

EasyStart "Learns" the start characteristic for your compressor over the first five starts. We
recommend that these starts are done on a 20 amp or greater utility power source with all other loads
in the RV turned off.
Installations that do not have access to utility power can do the learn process on a generator,
but with some risk and it is not recommended. Generators must have a continuous rated output
capable of supporting the air conditioner. Any low RPM economy or ECO mode must be switched off so
the compressor can start with the maximum capacity of the generator.
1. Breaker on the air conditioning unit.
2. Set the thermostat to start the air conditioner compressor. Heat mode may be used if you
are using a heat pump model.
3. The compressor will start up shortly after the fan starts. Let the compressor run for 30
seconds.
4. Set the thermostat to turn off the compressor.
5. Set the thermostat to start the compressor again.
6. EasyStart will wait 5 minutes from the time the compressor stopped in step 4 to restart the
compressor.
7. The compressor will start up shortly after the fan starts. Let the compressor run for 30
seconds.
8. Set the thermostat to turn off the compressor.
9. Repeat steps 5 to 8 three more times to complete the learn process.
Once the learn process is complete, EasyStart does not learn again. EasyStart can now be used
on generators, inverters or utility power to provide low-current starts every time.