Timer Instructions
Overview
1
Timer and Counter Instructions
Timers and counters are output instructions that let you control operations
based on time or a number of events. The following Timer and Counter
Instructions are described in this chapter:
Instruction
TON - Timer, On-Delay
TOF - Timer, Off-Delay
RTO - Retentive Timer On
CTU - Count Up
CTD - Count Down
RES - Reset
For information on using the High-Speed Counter output(s), see Using the
High-Speed Counter on page 5-1.
Timers in a controller reside in a timer file. A timer file can be assigned as
any unused data file. When a data file is used as a timer file, each timer
element within the file has three sub-elements. These sub-elements are:
• Timer Control and Status
• Preset - This is the value that the timer must reach before the timer
times out. When the accumulator reaches this value, the DN status bit
is set (TON and RTO only). The preset data range is from 0 to 32767.
The minimum required update interval is 2.55 seconds regardless of
the time base.
• Accumulator - The accumulator counts the time base intervals. It
represents elapsed time. The accumulator data range is from 0 to
32767.
Timers can be set to any one of three time bases:
Table 8.1 Timer Base Settings
Time Base
0.001 seconds
0.01 seconds
1.00 seconds
Used To:
Delay turning on an output on a true rung
Delay turning off an output on a false rung
Delay turning on an output from a true rung.
The accumulator is retentive.
Count up
Count down
Reset the RTO and counter's ACC and status
bits (not used with TOF timers).
Timing Range
0 to 32.767 seconds
0 to 327.67 seconds
0 to 32,767 seconds
8
Chapter
Page
8-4
8-5
8-6
8-9
8-9
8-10
Publication 1762-RM001C-EN-P